| SENTRON, meas. device & power quality recorder, 7KM PAC5200, standard rail housing w/o display L-L: 690 V, L-N: 400 V, 10 A, strd rail instr., 3- phase, Modbus TCP, apparent/ Active/reactive energy / cos phi, harmonics: 2. - 40., THD, class 0.5 acc. to IEC61557-12 or cl. 0.5S acc. to IEC62053-22, wide-range pwr sup. unit AC/DC, screw terminals |
| Model |
| product brand name | SENTRON |
| product designation | 7KM PAC5200 |
| design of the product | Advanced |
| product type designation | Measuring instrument and power quality recorder |
| Measurements |
| measuring procedure | |
| ● for voltage measurement | TRMS |
| ● for current measurement | TRMS |
| type of measured value detection | complete |
| voltage curve | Sinusoidal or distorted |
| measurable line frequency | |
| ● initial value | 45 Hz |
| ● full-scale value | 65 Hz |
| operating mode for measured value detection automatic line frequency detection | Yes |
| operating mode for measured value detection | |
| ● set at 50 Hz | No |
| ● set to 60 Hz | No |
| Supply voltage |
| design of the power supply | Wide-range power supply |
| type of voltage of the supply voltage | AC/DC |
| Degree of protection protection class |
| protection class IP on the front | IP20 |
| operating resource protection class when installed | safety class II |
| Suitability |
| suitability for operation | Standard mounting rail device |
| Product Functions |
| product function | |
| ● voltage measurement | Yes |
| ● current measurement | Yes |
| ● active power measurement | Yes |
| ● reactive power measurement | Yes |
| ● frequency measurement | Yes |
| Display and operation |
| design of the display | Standard mounting rail enclosure without display |
| color of the background of the display | white |
| illuminance of display backlight adjustable | No |
| time-controlled reduction of the illuminance of display backlight possible | No |
| display contrast adjustable | No |
| national language on the display screen is supported | de, en |
| number of keys | 4 |
| Communication |
| number of interfaces according to Fast Ethernet | 1 |
| type of electrical connection of the fast Ethernet interface | RJ45 (8P8C) |
| Fault limits |
| reference condition for metering accuracy | according to IEC 62053-22, IEC 62053-23, IEC 62586-1, Class S, IEC 61000-4-30, IEC 61000-4-7, IEC 61000-4-15 |
| formula for relative total measurement inaccuracy | |
| ● for measured variable voltage | +/- 0,2 % |
| ● for measured variable current | +/- 0,2 % |
| ● for measured variable output factor | +/- 0,5 % |
| ● for measured variable active energy | Cl. 0.5 acc. to... IEC62053-22 |
| ● for measured variable reactive energy | Class 2 according to IEC61557-12 and/or IEC62053-23 |
| Inputs Outputs |
| number of digital inputs | 0 |
| number of digital outputs | 2 |
| type of switching output | solid state |
| digital output version | Continuous output, pulse output |
| operating voltage as output voltage at DC maximum permissible | 250 V |
| type of electrical connection at the digital outputs | screw-type terminals |
| output current | |
| ● at digital output for signal <1> maximum | 300 mA |
| internal resistance at the digital outputs | 35 Ω |
| pulse duration | |
| ● initial value | 50 ms |
| ● full-scale value | 3 600 000 ms |
| adjustable time period minimum | 50 ms |
| switching frequency at digital output maximum | 10 Hz |
| property of the output short-circuit proof | Yes |
| measuring category for digital signals | Cat. III |
| Measuring inputs |
| measurable supply voltage between (PE)N and L at AC maximum rated value | 400 V |
| measurable supply voltage between the line conductors at AC maximum rated value | 690 V |
| measurable supply voltage between the line conductors at AC | |
| ● maximum | 831 V |
| voltage measuring range extension with external voltage transformers | yes |
| line conductors and neutral conductors internal resistance for voltage measurement | 6 MΩ |
| measuring category for voltage measurement | CATIII |
| measurable current | |
| ● 1 at AC rated value | 5 A |
| ● 2 at AC rated value | 5 A |
| relative measurable current at AC | |
| ● minimum | 1 % |
| ● maximum | 200 % |
| current measuring range extension with external current transformers | yes |
| zero point suppression for current measurement | 0 ... 10 % |
| ● for neutral conductor current | 0.0 % to 10.0 % (from Vrated, Irated) |
| measuring category for current measurement | CATIII |
| Connections |
| type of connectable conductor cross-sections | |
| ● at the measurement inputs for voltage solid | 2.5 mm² |
| ● at the measurement inputs for voltage finely stranded with core end processing | 2.5 mm² |
| ● at the measurement inputs for voltage at AWG cables solid | Screw connection |
| ● at the measurement inputs for current at AWG cables solid | Screw connection |
| type of electrical connection | |
| ● at the measurement inputs for voltage | screw-type terminals |
| ● at the measurement inputs for current | screw-type terminals |
| Mechanical Design |
| fastening method standard rail mounting | Yes |
| size of Power Monitoring Device | DIN rail |
| net weight | 754 g |
| mounting position | vertical |
| Environmental conditions |
| ambient temperature during operation | |
| ● minimum | -25 °C |
| ● maximum | 55 °C |
| ambient temperature during storage | |
| ● minimum | -40 °C |
| ● maximum | 70 °C |
| relative humidity at 25 °C without condensation during operation maximum | 95 % |
| installation altitude at height above sea level maximum | 2 000 m |
| degree of pollution | 2 |
| Certificates |
| certificate of suitability as EC Declaration of Conformity | EN 61000-6-2 and EN 61000-6-4 for EMC guideline |
Downloads and manuals |
|
| Further information |
Information- and Downloadcenter (catalogues, leaflets,...) |
Industry Mall (Online ordering system) |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) |
CAx-Online-Generator |
Tender specifications |
|
|
|
|
|
| |
Date 5/13/2022 | Subject to change without notice © Copyright Siemens 2022 |