| SENTRON, measuring device, 7KM PAC4200, LCD, L-L: 690 V, L-N: 400 V, 5 A, 3-phase, Modbus TCP, optional Modbus RTU / PROFINET / PROFIBUS / DI/DO, apparent/active/reactive energy / cos phi, harmonics: 2.-64., THD, class 0.2 acc. to IEC61557-12 or cl. 0.2S acc. to IEC62053-22, wide-range pwr sup. unit AC/DC, screw terminals |
| Model |
| product brand name | SENTRON |
| product designation | 7KM PAC4200 |
| design of the product | compact |
| product type designation | Measuring instrument |
| Measurements |
| measuring procedure | |
| ● for voltage measurement | TRMS |
| ● for current measurement | TRMS |
| type of measured value detection | complete |
| voltage curve | Sinusoidal or distorted |
| measurable line frequency | |
| ● initial value | 45 Hz |
| ● full-scale value | 65 Hz |
| operating mode for measured value detection automatic line frequency detection | Yes |
| operating mode for measured value detection | |
| ● set at 50 Hz | No |
| ● set to 60 Hz | No |
| Supply voltage |
| design of the power supply | Wide-range power supply |
| type of voltage of the supply voltage | AC/DC |
| Degree of protection protection class |
| protection class IP on the front | IP65 |
| operating resource protection class when installed | safety class II |
| Suitability |
| suitability for operation | Installation in stationary control panels in closed rooms |
| Product Functions |
| product function | |
| ● voltage measurement | Yes |
| ● current measurement | Yes |
| ● active power measurement | Yes |
| ● reactive power measurement | Yes |
| ● frequency measurement | Yes |
| Display and operation |
| design of the display | LCD |
| height of the display | 54 mm |
| width of the display | 72 mm |
| color of the background of the display | white |
| illuminance of display backlight adjustable | Yes |
| time-controlled reduction of the illuminance of display backlight possible | Yes |
| display contrast adjustable | Yes |
| national language on the display screen is supported | ger, en, fr, spa, ita, por, tur, rus, chi, pol |
| number of keys | 4 |
| Communication |
| number of interfaces according to Fast Ethernet | 1 |
| type of electrical connection of the fast Ethernet interface | RJ45 (8P8C) |
| protocol at the Ethernet interface is supported | MODBUS TCP |
| transfer rate 1 for Ethernet | 10 Mbit/s |
| transfer rate 2 for Ethernet | 100 Mbit/s |
| Fault limits |
| reference condition for metering accuracy | Acc. to IEC61557-12 |
| formula for relative total measurement inaccuracy | |
| ● for measured variable voltage | +/- 0,2 % |
| ● for measured variable current | +/- 0,2 % |
| ● for measured variable output factor | +/- 2 % |
| ● for measured variable active energy | Class 0.2 according to IEC61557-12 and/or class 0.2S according to IEC62053-22 |
| ● for measured variable reactive energy | Class 2 according to IEC61557-12 and/or IEC62053-23 |
| Inputs Outputs |
| number of digital inputs | 2 |
| type of electrical connection at the digital inputs | screw-type terminals |
| operating conditions for digital inputs external voltage supply | Yes |
| input voltage at digital input at DC maximum | 30 V |
| number of digital outputs | 2 |
| type of switching output | solid state |
| digital output version | switching or pulse output function |
| operating voltage as output voltage at DC maximum permissible | 30 V |
| type of electrical connection at the digital outputs | screw-type terminals |
| output current | |
| ● at digital output with signal <0> maximum | 0.2 mA |
| ● at digital output for signal <1> maximum | 27 mA |
| ● at the digital outputs at DC limited to 100 ms maximum | 300 mA |
| internal resistance at the digital outputs | 55 Ω |
| standard for pulse emitter | according to IEC62053-31 |
| pulse duration | |
| ● initial value | 30 ms |
| ● full-scale value | 500 ms |
| adjustable time period minimum | 10 ms |
| switching frequency at digital output maximum | 20 Hz |
| property of the output short-circuit proof | Yes |
| measuring category for digital signals | CATI |
| Measuring inputs |
| measurable supply voltage between (PE)N and L at AC maximum rated value | 400 V |
| measurable supply voltage between (PE)N and L at AC | |
| ● minimum | 11.5 V |
| ● maximum | 480 V |
| measurable supply voltage between the line conductors at AC maximum rated value | 690 V |
| measurable supply voltage between the line conductors at AC | |
| ● minimum | 20 V |
| ● maximum | 828 V |
| voltage measuring range extension with external voltage transformers | yes |
| line conductors and neutral conductors internal resistance for voltage measurement | 1.05 MΩ |
| measuring category for voltage measurement | CATIII |
| measurable current | |
| ● 1 at AC rated value | 1 A |
| ● 2 at AC rated value | 5 A |
| relative measurable current at AC | |
| ● minimum | 1 % |
| ● maximum | 120 % |
| current measuring range extension with external current transformers | yes |
| zero point suppression for current measurement | 0 ... 10 % |
| measuring category for current measurement | CATIII |
| Connections |
| type of connectable conductor cross-sections | |
| ● at the measurement inputs for voltage solid | 1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²) |
| ● at the measurement inputs for voltage finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
| ● at the measurement inputs for voltage at AWG cables solid | 2x 20 to 14 |
| ● at the measurement inputs for current solid | 1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²) |
| ● at the measurement inputs for current finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
| ● at the measurement inputs for current at AWG cables solid | 2x 20 to 14 |
| type of electrical connection | |
| ● at the measurement inputs for voltage | screw-type terminals |
| ● at the measurement inputs for current | screw-type terminals |
| Mechanical Design |
| fastening method standard rail mounting | No |
| size of Power Monitoring Device | size 96 |
| height | 96 mm |
| width | 96 mm |
| depth | 82 mm |
| installation depth | 77 mm |
| net weight | 543 g |
| mounting position | vertical |
| Environmental conditions |
| ambient temperature during operation | |
| ● minimum | -10 °C |
| ● maximum | 55 °C |
| ambient temperature during storage | |
| ● minimum | -25 °C |
| ● maximum | 70 °C |
| relative humidity at 25 °C without condensation during operation maximum | 95 % |
| installation altitude at height above sea level maximum | 2 000 m |
| degree of pollution | 2 |
| Certificates |
| certificate of suitability as EC Declaration of Conformity | IEC 61010-1: 2001 (2nd Ed.) with Corr. 1, EN 61010-1: 2001 (2nd Ed.) and DIN EN 61010-1:2002 with "Berichtigung 1" |
| reference code according to EN 61346-2 | P |
Downloads and manuals |
|
| Further information |
Information- and Downloadcenter (catalogues, leaflets,...) |
Industry Mall (Online ordering system) |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...) |
CAx-Online-Generator |
Tender specifications |
|
|
|
|
|
| |
Date 5/3/2022 | Subject to change without notice © Copyright Siemens 2022 |