View larger
5SU1356-6KK10 SIEMENS RCBO, 6 kA, 1P+N, type A, 30 mA, B char., In: 10 A, Un AC: 230 V
5SU1356-6KK10
13566
SIEMENS
1 Pcs.
Automation > Earth leakage circuit breaker
Tertiary differential switches up to 80 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Siemens RCBO, part number 5SU1356-6KK10, provides integrated short-circuit protection, overload protection, and residual current detection within a single modular housing. Such devices are essential for maintaining safety compliance and preventing electrical accidents in modern facility power architectures.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- product designation: RCBO
- design of the product: Instantaneous
- General technical data number of poles: 2
- number of poles / with protection: 1
- tripping characteristic class: B
- mechanical service life (switching cycles) / typical: 10 000
- overvoltage category: III
- degree of pollution: 2
- Voltage type of voltage / of the operating voltage: AC
- insulation voltage (Ui) / rated value: 264 V
- surge voltage resistance / rated value: 4 000 V
- surge current resistance / at (8/20) µs: 1 kA
- ● at AC / rated value: 230/240 V
- ● for testing equipment / minimum: 195 V
- operating frequency: 50 Hz
- supply voltage frequency / rated value: 50 Hz
More info
▲Technical data
Additional data
| Product | |||||||||||||||||||||||||||||||||||||
| Article Number (Market Facing Number) | 5SU1356-6KK10 | ||||||||||||||||||||||||||||||||||||
| Product Description | RCBO, 6 kA, 1P+N, type A, 30 mA, B char., In: 10 A, Un AC: 230 V | ||||||||||||||||||||||||||||||||||||
| Product family | RCBOs | ||||||||||||||||||||||||||||||||||||
| Product Lifecycle (PLM) | PM300:Active Product | ||||||||||||||||||||||||||||||||||||
| Price data | |||||||||||||||||||||||||||||||||||||
| Region Specific PriceGroup / Headquarter Price Group | 11D / 1BC | ||||||||||||||||||||||||||||||||||||
| Surcharge for Raw Materials | None | ||||||||||||||||||||||||||||||||||||
| Metal Factor | None | ||||||||||||||||||||||||||||||||||||
| Delivery information | |||||||||||||||||||||||||||||||||||||
| Export Control Regulations | AL : N / ECCN : N | ||||||||||||||||||||||||||||||||||||
| Standard lead time ex-works | 40 Day/Days | ||||||||||||||||||||||||||||||||||||
| Net Weight (kg) | 0,269 Kg | ||||||||||||||||||||||||||||||||||||
| Packaging Dimension | 40,00 x 96,00 x 82,00 | ||||||||||||||||||||||||||||||||||||
| Package size unit of measure | MM | ||||||||||||||||||||||||||||||||||||
| Quantity Unit | 1 Piece | ||||||||||||||||||||||||||||||||||||
| Packaging Quantity | 1 | ||||||||||||||||||||||||||||||||||||
| Additional Product Information | |||||||||||||||||||||||||||||||||||||
| EAN | 4001869306704 | ||||||||||||||||||||||||||||||||||||
| UPC | 754554942315 | ||||||||||||||||||||||||||||||||||||
| Commodity Code | 85362010 | ||||||||||||||||||||||||||||||||||||
| LKZ_FDB/ CatalogID | LV10.1 | ||||||||||||||||||||||||||||||||||||
| Product Group | 5532 | ||||||||||||||||||||||||||||||||||||
| Group Code | P310 | ||||||||||||||||||||||||||||||||||||
| Country of origin | Romania | ||||||||||||||||||||||||||||||||||||
| Compliance with the substance restrictions according to RoHS directive | Since: 01.06.2006 | ||||||||||||||||||||||||||||||||||||
| Product class | B: return restricted, please contact your Siemens partner/contact | ||||||||||||||||||||||||||||||||||||
| WEEE (2012/19/EU) Take-Back Obligation | Yes | ||||||||||||||||||||||||||||||||||||
| REACH Art. 33 Duty to inform according to the current list of candidates |
| ||||||||||||||||||||||||||||||||||||
| Classifications | |||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||
ETIM data
ETIM: EC000905 - Earth leakage circuit breaker
| Value | Unit | |
|---|---|---|
| Disconnection characteristic (EF012587) | - | |
| Number of poles (total) (EF008618) | 2 | |
| Number of protected poles (EF005548) | 1 | |
| Rated voltage (EF000228) | 230 | V |
| Rated insulation voltage Ui (EF001366) | 264 | V |
| Rated impulse withstand voltage Uimp (EF011980) | 4.0 | kV |
| Rated current (EF000227) | 10 | A |
| Rated fault current (EF002358) | 0.03 | A |
| Leakage current type (EF002560) | A | |
| Current limiting class (EF002568) | 3 | |
| Rated short-circuit breaking capacity according to EN 61009 (EF012628) | 6.0 | kA |
| Rated short-circuit breaking capacity IEC 60947-2 (EF006065) | 15.0 | kA |
| Rated short-circuit breaking capacity Icn according to EN 61009-1 (EF011981) | 6.0 | kA |
| Surge current capacity (EF002564) | 1.0 | kA |
| Voltage type (EF000187) | AC | |
| Frequency (EF005455) | 50 Hz | |
| Release characteristic (EF000889) | B | |
| Concurrently switching N-neutral (EF005997) | true | |
| With interlocking device (EF007385) | true | |
| Over voltage category (EF002569) | 3 | |
| Pollution degree (EF002570) | 2 | |
| Ambient temperature during operating (EF007515) | ['-25', '55'] | °C |
| Width in number of modular spacings (EF002950) | 2 | |
| Built-in depth (EF000218) | 70.0 | mm |
| Suitable for flush-mounted installation (EF006573) | true | |
| Anti-nuisance tripping version (EF009497) | true | |
| Degree of protection (IP) (EF005474) | IP20 | |
| Connectable conductor cross section solid-core (EF007337) | ['0.75', '35.0'] | mm² |
| Connectable conductor cross section multi-wired (EF007343) | ['0.75', '35.0'] | mm² |