SIEMENS 5SU1354-7VK16 5SU1354-7VK16 SIEMENS RCBO, 10 kA, 1P+N, type A, short-time-delayed K, 30 mA, C-Char, In: 16 A, Un AC: 230 V View larger
Images are for illustrative purposes only. Please refer to data sheet for details

5SU1354-7VK16 SIEMENS RCBO, 10 kA, 1P+N, type A, short-time-delayed K, 30 mA, C-Char, In: 16 A, Un AC: 230 V

5SU1354-7VK16

13547

SIEMENS

1 Pcs.

RCBO, 10 kA, 1P+N, type A, short-time-delayed K, 30 mA, C-Char, In: 16 A, Un AC: 230 V

Automation > Earth leakage circuit breaker
Tertiary differential switches up to 80 A

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

ETIM: EC000905 - Earth leakage circuit breaker

Value Unit
Disconnection characteristic (EF012587) -
Number of poles (total) (EF008618) 2
Number of protected poles (EF005548) 1
Rated voltage (EF000228) 230V
Rated insulation voltage Ui (EF001366) 264V
Rated impulse withstand voltage Uimp (EF011980) 4.0kV
Rated current (EF000227) 16A
Rated fault current (EF002358) 0.03A
Leakage current type (EF002560) A
Current limiting class (EF002568) 3
Rated short-circuit breaking capacity according to EN 61009 (EF012628) 10.0kA
Rated short-circuit breaking capacity IEC 60947-2 (EF006065) 20.0kA
Rated short-circuit breaking capacity Icn according to EN 61009-1 (EF011981) 10.0kA
Surge current capacity (EF002564) 3.0kA
Voltage type (EF000187) AC
Frequency (EF005455) 50 Hz
Release characteristic (EF000889) C
Concurrently switching N-neutral (EF005997) true
With interlocking device (EF007385) true
Over voltage category (EF002569) 3
Pollution degree (EF002570) 2
Ambient temperature during operating (EF007515) ['-25', '55']°C
Width in number of modular spacings (EF002950) 2
Built-in depth (EF000218) 70.0mm
Suitable for flush-mounted installation (EF006573) true
Anti-nuisance tripping version (EF009497) true
Degree of protection (IP) (EF005474) IP20
Connectable conductor cross section solid-core (EF007337) ['0.75', '35.0']mm²
Connectable conductor cross section multi-wired (EF007343) ['0.75', '35.0']mm²


RCBO, 10 kA, 1P+N, type A, short-time-delayed K, 30 mA, C-Char, In: 16 A, Un AC: 230 V
Model
product brand nameSENTRON
Product designationRCBO
Design of the productSuper resistant K
General technical data
number of poles2
Number of poles / Note1P+N
Number of poles / with protection1
Tripping characteristic classC
circuit-breaker / Design5SU1
Mechanical service life (switching cycles) / typical10 000
overvoltage categoryIII
Degree of pollution2
Voltage
Surge current resistance / at (8/20) µs3 kA
Supply voltage
type of voltageAC
Operating current / at AC / rated value16 A
Supply voltage
● at AC / rated value230/240 V
● for testing equipment / minimum195 V
Operating frequency50/60 Hz
Supply voltage frequency / rated value50 Hz
Protection class
Protection class IPIP20, if the distribution board is installed, with connected conductors
Switching capacity
Breaking capacity short-circuit current (Icn) / according to EN 61009-1 / rated value10 kA
Switching capacity current
● acc. to EN 60898 / rated value10 kA
● acc. to IEC 60947-2 / rated value20 kA
Rated residual switching capacity (IΔm) / according to IEC 61009-110 kA
Energy limiting class3
Dissipation
● Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole2.8 W
● power loss [W] / maximum5.6 W
Current
Tripping residual current / rated value30 mA
Tripping residual / rated value / derated current
● at 30 Cel16 A
● at 40 Cel15.2 A
● at 45 Cel14.88 A
● at 50 Cel14.4 A
● at 55 Cel13.92 A
● at 60 Cel13.6 A
● at 65 Cel12.96 A
● at 70 Cel12.32 A
Type of fault currentA
Product details
Product function / neutral conductor switchingYes
Product feature / Touch protectionYes
product feature
● halogen-freeYes
● silicon-freeYes
Connections
connectable conductor cross-section / solid
● minimum0.75 mm²
● maximum35 mm²
Connectable conductor cross-section / stranded
● minimum0.75 mm²
● maximum35 mm²
connectable conductor cross-section / finely stranded / with core end processing
● minimum0.75 mm²
● maximum25 mm²
Tightening torque / with screw-type terminals
● minimum2.5 N·m
● maximum3 N·m
Position / of power supply cordEither top or bottom
Mechanical Design
Height90 mm
Width36 mm
Depth77 mm
installation depth70 mm
number of width units2
mounting positionany
net weight286 g
Environmental conditions
influence of the surrounding temperatureMax. 95% humidity
Ambient temperature
● minimum-25 °C
● maximum55 °C
Ambient temperature / during storage
● minimum-40 °C
● maximum75 °C
Number of test cycles / for environmental testing / acc. to IEC 60068-2-3028
Certificates
● reference code / acc. to DIN EN 61346-2F
● Reference code / acc. to DIN EN 81346-2F
General Product ApprovalDeclaration of ConformityTest Certificates

IMQ

VDE

Miscellaneous

RCM

EC/EU-Declaration of Conformity

Special Test Certificate

otherRailway

Miscellaneous

Vibration and Shock

Confirmation

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
Industry Mall (Online ordering system)
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
CAx-Online-Generator
Tender specifications


Product
Article Number (Market Facing Number)5SU1354-7VK16
Product DescriptionRCBO, 10 kA, 1P+N, type A, short-time-delayed K, 30 mA, C-Char, In: 16 A, Un AC: 230 V
Product familyNot available
Product Lifecycle (PLM)PM490:Start of final year of support
PLM Effective DateProduct discontinued since: 28.06.2020
Notes
Product is no longer available. Successor:5SU1354-7LB16
Successor information
Successor5SU1354-7LB16
Successor DescriptionRCBO, 10 kA, 1P+N, type A, short-time-delayed G, super-resistant K, 30 mA, C-Char, In: 16 A, Un AC: 230 V
Price data
Price Group11D
Surcharge for Raw MaterialsNone
Metal FactorL-O-----
Delivery information
Export Control RegulationsECCN : N / AL : N
Standard lead time ex-works5 Day/Days
Net Weight (kg)0,276 Kg
Product Dimensions (W x L x H)Not available
Packaging Dimension40,00 x 96,00 x 82,00
Package size unit of measureMM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4001869357065
UPCNot available
Commodity Code85362010
LKZ_FDB/ CatalogIDLV10.1
Product Group5516
Group CodeP310
Country of originRomania
Compliance with the substance restrictions according to RoHS directiveSince: 01.06.2006
Product classB: return restricted, please contact your Siemens partner/contact
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
Not available

Product Datasheet