SIEMENS 3VT3763-2AA36-0AA0 3VT3763-2AA36-0AA0 SIEMENS circuit breaker 3VT3 standard breaking capacity Icu 36kA, 415V AC 3-pole circuit .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

3VT3763-2AA36-0AA0 SIEMENS circuit breaker 3VT3 standard breaking capacity Icu 36kA, 415V AC 3-pole circuit ..

3VT3763-2AA36-0AA0

37632

SIEMENS

1 Pcs.

circuit breaker 3VT3 standard breaking capacity Icu=36kA, 415V AC 3-pole; circuit breaker w/o Electronic Trip Unit without auxiliary release without auxiliary/alarm switch

Automation > Power circuit-breaker for trafo/generator/installation protection
POWER DISTRIBUTION AND LOW VOLTAGE SWITCHGEAR

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

ETIM: EC000228 - Power circuit-breaker for trafo/generator/installation protection

Value Unit
Rated voltage (EF003977) -V
Rated permanent current Iu (EF001389) 630.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz (EF007048) 36.0kA
Overload release current setting (EF002336) ['-', '-']A
Adjustment range short-term delayed short-circuit release (EF007129) ['-', '-']A
Adjustment range undelayed short-circuit release (EF007131) ['-', '-']A
Integrated earth fault protection (EF007296) false
Type of electrical connection of main circuit (EF006819) Screw connection
Device construction (EF008240) Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting (EF007250) true
DIN rail (top hat rail) mounting optional (EF008904) true
Number of auxiliary contacts as normally closed contact (EF001377) 0
Number of auxiliary contacts as normally open contact (EF001376) 0
Number of auxiliary contacts as change-over contact (EF003531) 0
With switched-off indicator (EF007006) false
With under voltage release (EF007518) false
Number of poles (EF001391) 3
Position of connection for main current circuit (EF006671) Front side
Type of control element (EF006976) Rocker lever
Complete device with protection unit (EF008906) true
Motor drive integrated (EF006697) false
Motor drive optional (EF007386) true
Degree of protection (IP) (EF005474) IP40


circuit breaker 3VT3 standard breaking capacity Icu=36kA, 415V AC 3-pole; circuit breaker w/o Electronic Trip Unit without auxiliary release without auxiliary/alarm switch
Model
product brand nameSENTRON
Product designation3VT1_5 molded case circuit breakers
Design of the operating mechanismtoggle handle
Type of the driving mechanism / motor driveNo
General technical data
number of poles3
Size of the circuit-breaker3VT3
Electrical endurance (switching cycles) / typical5 000
Usage categoryA
Performance class for circuit breakerN
Mechanical service life (switching cycles) / typical20 000
Operating frequency / maximum120 1/h
Voltage
Insulation voltage / rated value690 V
Surge voltage resistance / rated value8 kV
Protection class
Protection class IPIP40
Dissipation
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole25 W
Current
Continuous current / rated value630 A
Derating temperature / for the rated value of the continuous current55 °C
Main circuit
Operating frequency
● 1 / rated value50 Hz
● 2 / rated value60 Hz
Operating current
● at 40 °C / rated value630 A
● at 50 °C / rated value630 A
● at 55 °C / rated value600 A
● at 60 °C / rated value600 A
● at 65 °C / rated value540 A
● at 70 °C / rated value540 A
Auxiliary circuit
Number of CO contacts / for auxiliary contacts0
Number of NC contacts / for auxiliary contacts0
Number of NO contacts / for auxiliary contacts0
Suitability
● suitability for useContact unit without release
● Suitability for use / Disconnecting meansYes
Product details
Product component
● Trip indicatorNo
● Auxiliary switchNo
● Voltage triggerNo
● undervoltage releaseNo
● undervoltage release with leading contactNo
Product extension / optional / motor driveYes
Product function
Product function
● Ground fault protectionNo
● for neutral conductors / Short-circuit and overload proofNo
● Phase failure detectionNo
● Overload protectionNo
Short circuit
Operational short-circuit current breaking capacity (Ics)
● at 240 V / rated value40 kA
● at 415 V / rated value18 kA
● at 500 V / rated value10 kA
● at 690 V / rated value8 kA
Maximum short-circuit current breaking capacity (Icu)
● at 240 V / rated value60 kA
● at 415 V / rated value36 kA
● at 500 V / rated value20 kA
● at 690 V / rated value15 kA
Connections
Arrangement of electrical connectors / for main current circuitfront side
Type of electrical connection / for main current circuitscrew-type terminals
Mechanical Design
Height275 mm
Width140 mm
Depth117 mm
Mounting typefixed mounting
mounting positionwith vertical mounting surface +/-180° rotatable, with vertical mounting surface +/- 30° tiltable to the front and back
net weight5.986 kg
Environmental conditions
Ambient temperature / during operation
● minimum-40 °C
● maximum70 °C
Ambient temperature / during storage
● minimum-40 °C
● maximum70 °C
Certificates
● reference code / acc. to DIN EN 61346-2Q
● Reference code / acc. to DIN EN 81346-2Q
General Product ApprovalDeclaration of ConformityTest Certificatesother

CCC

EC/EU-Declaration of Conformity

Type Test Certificates/Test Report

Miscellaneous

Manufacturer Declaration

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
Industry Mall (Online ordering system)
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
CAx-Online-Generator
Tender specifications


Product
Article Number (Market Facing Number)3VT3763-2AA36-0AA0
Product Descriptioncircuit breaker 3VT3 standard breaking capacity Icu=36kA, 415V AC 3-pole; circuit breaker w/o Electronic Trip Unit without auxiliary release without auxiliary/alarm switch
Product familyNot available
Product Lifecycle (PLM)PM410:Product cancellation
PLM Effective DateProduct is cancelled since: 01.10.2019
Notes
Sucessor:Successor portfolio 3VA; further information via www.siemens.com/3VA
Price data
Price Group193
Surcharge for Raw MaterialsNone
Metal FactorLCP-----
Delivery information
Export Control RegulationsECCN : EAR99 / AL : N
Standard lead time ex-works15 Day/Days
Net Weight (kg)5,972 Kg
Product Dimensions (W x L x H)Not available
Packaging Dimension222,00 x 280,00 x 157,00
Package size unit of measureMM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4011209763166
UPCNot available
Commodity Code85362090
LKZ_FDB/ CatalogIDLV10.1
Product Group3749
Group CodeP360
Country of originCzech Republic
Compliance with the substance restrictions according to RoHS directiveSince: 01.11.2007
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates
There is currently no information on SVHC (Substances of Very High Concern http://echa.europa.eu/web/guest/candidate-list-table) from the supply chain and our established procedures for screening our products for Substances of Very High Concern.We compare our products regularly with the information of the upstream users with regard to the substances indicated in the candidate list in accordance with the requirements of the REACH regulation. As soon as we have new findings, our information will be updated accordingly.
Classifications
Not available