View larger
3VL4731-3NE46-0AA0 SIEMENS circuit breaker VL400L very high breaking capacity Icu 100kA, 415V AC 4-pole, lin..
3VL4731-3NE46-0AA0
47313
SIEMENS
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Moulded Case Circuit Breakers 3VL SENTRON
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Siemens circuit breaker VL400L very high breaking capacity unit offers robust protection against extreme short circuits and overloads in industrial electrical grids. Four-pole breakers of this specification are commonly installed in primary distribution switchboards to secure heavy commercial feeds. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 315.0
- Overload release current setting (EF002336): ['126', '315']
- Adjustment range undelayed short-circuit release (EF007131): ['3465', '3465']
- Integrated earth fault protection (EF007296): false
- Type of electrical connection of main circuit (EF006819): Screw connection
- Device construction (EF008240): Built-in device fixed built-in technique
- Suitable for DIN rail (top hat rail) mounting (EF007250): true
- DIN rail (top hat rail) mounting optional (EF008904): true
- With switched-off indicator (EF007006): false
- With under voltage release (EF007518): false
- Number of poles (EF001391): 4
- Position of connection for main current circuit (EF006671): Front side
- Complete device with protection unit (EF008906): true
- Motor drive integrated (EF006697): false
- Motor drive optional (EF007386): true
- Degree of protection (IP) (EF005474): IP20
More info
▲ETIM: EC000228 - Power circuit-breaker for trafo/generator/installation protection
| Value | Unit | |
|---|---|---|
| Type of control element (EF006976) | - | |
| Rated voltage (EF003977) | - | V |
| Rated permanent current Iu (EF001389) | 315.0 | A |
| Rated short-circuit breaking capacity lcu at 400 V, 50 Hz (EF007048) | 100.0 | kA |
| Overload release current setting (EF002336) | ['126', '315'] | A |
| Adjustment range short-term delayed short-circuit release (EF007129) | ['473', '3150'] | A |
| Adjustment range undelayed short-circuit release (EF007131) | ['3465', '3465'] | A |
| Integrated earth fault protection (EF007296) | false | |
| Type of electrical connection of main circuit (EF006819) | Screw connection | |
| Device construction (EF008240) | Built-in device fixed built-in technique | |
| Suitable for DIN rail (top hat rail) mounting (EF007250) | true | |
| DIN rail (top hat rail) mounting optional (EF008904) | true | |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 | |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 | |
| Number of auxiliary contacts as change-over contact (EF003531) | 0 | |
| With switched-off indicator (EF007006) | false | |
| With under voltage release (EF007518) | false | |
| Number of poles (EF001391) | 4 | |
| Position of connection for main current circuit (EF006671) | Front side | |
| Complete device with protection unit (EF008906) | true | |
| Motor drive integrated (EF006697) | false | |
| Motor drive optional (EF007386) | true | |
| Degree of protection (IP) (EF005474) | IP20 |
| Product | |||||||||||||||||||||||||||||||||||||
| Article Number (Market Facing Number) | 3VL4731-3NE46-0AA0 | ||||||||||||||||||||||||||||||||||||
| Product Description | circuit breaker VL400L very high breaking capacity Icu=100kA, 415V AC 4-pole, line protection Electronic Trip Unit ETU20, LSI In=315A, rated current IR=128...315A, overload protection, ISD=1.5 to 10xIR, II=11xIN short-circuit protection without auxiliary release ETU communication-capable without auxiliary/alarm switch | ||||||||||||||||||||||||||||||||||||
| Product family | Not available | ||||||||||||||||||||||||||||||||||||
| Product Lifecycle (PLM) | PM400:Phase Out Started | ||||||||||||||||||||||||||||||||||||
| PLM Effective Date | Product phase-out since: 01.10.2016 | ||||||||||||||||||||||||||||||||||||
| Notes | Sucessor:3VA2340-7JP42-0A.. | ||||||||||||||||||||||||||||||||||||
| Price data | |||||||||||||||||||||||||||||||||||||
| Price Group | 12N | ||||||||||||||||||||||||||||||||||||
| Surcharge for Raw Materials | None | ||||||||||||||||||||||||||||||||||||
| Metal Factor | LBO----- | ||||||||||||||||||||||||||||||||||||
| Delivery information | |||||||||||||||||||||||||||||||||||||
| Export Control Regulations | ECCN : EAR99 / AL : N | ||||||||||||||||||||||||||||||||||||
| Standard lead time ex-works | 5 Day/Days | ||||||||||||||||||||||||||||||||||||
| Net Weight (kg) | 7,900 Kg | ||||||||||||||||||||||||||||||||||||
| Product Dimensions (W x L x H) | Not available | ||||||||||||||||||||||||||||||||||||
| Packaging Dimension | 220,00 x 372,00 x 174,00 | ||||||||||||||||||||||||||||||||||||
| Package size unit of measure | MM | ||||||||||||||||||||||||||||||||||||
| Quantity Unit | 1 Piece | ||||||||||||||||||||||||||||||||||||
| Packaging Quantity | 1 | ||||||||||||||||||||||||||||||||||||
| Additional Product Information | |||||||||||||||||||||||||||||||||||||
| EAN | 4011209814264 | ||||||||||||||||||||||||||||||||||||
| UPC | Not available | ||||||||||||||||||||||||||||||||||||
| Commodity Code | 85362090 | ||||||||||||||||||||||||||||||||||||
| LKZ_FDB/ CatalogID | LV10.1 | ||||||||||||||||||||||||||||||||||||
| Product Group | 3740 | ||||||||||||||||||||||||||||||||||||
| Group Code | P360 | ||||||||||||||||||||||||||||||||||||
| Country of origin | Germany | ||||||||||||||||||||||||||||||||||||
| Compliance with the substance restrictions according to RoHS directive | Since: 01.07.2006 | ||||||||||||||||||||||||||||||||||||
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. | ||||||||||||||||||||||||||||||||||||
| WEEE (2012/19/EU) Take-Back Obligation | Yes | ||||||||||||||||||||||||||||||||||||
| REACH Art. 33 Duty to inform according to the current list of candidates |
| ||||||||||||||||||||||||||||||||||||
| Classifications | |||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||