View larger
3VL2706-1MS36-0AA0 SIEMENS circuit breaker VL160N standard breaking capacity Icu 55kA, 415V AC 3-pole, motor..
3VL2706-1MS36-0AA0
27061
SIEMENS
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Moulded Case Circuit Breakers 3VL SENTRON
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Siemens circuit breaker VL160N standard breaking capacity Icu 55kA, 415V AC 3-pole, motor.. protects electrical circuits and machinery from overloads and short circuits in industrial switchboards. These switching devices automatically disconnect faulty paths to ensure operational safety and prevent equipment failure. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): ['25', '63']
- Adjustment range undelayed short-circuit release (EF007131): ['378', '693']
- Phase failure sensitive (EF007400): true
- Switch off technique (EF007007): Magnetic
- Rated operating voltage (EF001435): ['690', '690']
- Rated permanent current Iu (EF001389): 63.0
- Rated operation power at AC-3, 230 V (EF007025): 11.6
- Rated operation power at AC-3, 400 V (EF001364): 34.9
- Type of electrical connection of main circuit (EF006819): Screw connection
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): false
- With integrated under voltage release (EF001390): false
- Number of poles (EF001391): 3
- Degree of protection (IP) (EF005474): IP20
- Height (EF000040): 174.5
- Width (EF000008): 104.5
More info
▲ETIM: EC000074 - Motor protection circuit-breaker
| Value | Unit | |
|---|---|---|
| Type of control element (EF006976) | - | |
| With thermal protection (EF006233) | - | |
| Overload release current setting (EF002336) | ['25', '63'] | A |
| Adjustment range undelayed short-circuit release (EF007131) | ['378', '693'] | A |
| Phase failure sensitive (EF007400) | true | |
| Switch off technique (EF007007) | Magnetic | |
| Rated operating voltage (EF001435) | ['690', '690'] | V |
| Rated permanent current Iu (EF001389) | 63.0 | A |
| Rated operation power at AC-3, 230 V (EF007025) | 11.6 | kW |
| Rated operation power at AC-3, 400 V (EF001364) | 34.9 | kW |
| Type of electrical connection of main circuit (EF006819) | Screw connection | |
| Device construction (EF008240) | Built-in device fixed built-in technique | |
| With integrated auxiliary switch (EF001387) | false | |
| With integrated under voltage release (EF001390) | false | |
| Number of poles (EF001391) | 3 | |
| Degree of protection (IP) (EF005474) | IP20 | |
| Height (EF000040) | 174.5 | mm |
| Width (EF000008) | 104.5 | mm |
| Depth (EF000049) | 106.5 | mm |
| Rated short-circuit breaking capacity lcu at 400 V, AC (EF007049) | - | kA |
| Product | |||||||||||||||||||||||||||||||||||||
| Article Number (Market Facing Number) | 3VL2706-1MS36-0AA0 | ||||||||||||||||||||||||||||||||||||
| Product Description | circuit breaker VL160N standard breaking capacity Icu=55kA, 415V AC 3-pole, motor protection Electronic Trip Unit ETU30M, LI Ir=25...63A, overload prot., TC=10A...30, II=6/8/11 xIN, short-circuit protection with screw terminals without auxiliary release ETU communication-capable without auxiliary/alarm switch | ||||||||||||||||||||||||||||||||||||
| Product family | Not available | ||||||||||||||||||||||||||||||||||||
| Product Lifecycle (PLM) | PM400:Phase Out Started | ||||||||||||||||||||||||||||||||||||
| PLM Effective Date | Product phase-out since: 01.10.2016 | ||||||||||||||||||||||||||||||||||||
| Notes | Sucessor:3VA2163-5MQ32-0A.. | ||||||||||||||||||||||||||||||||||||
| Price data | |||||||||||||||||||||||||||||||||||||
| Price Group | 12N | ||||||||||||||||||||||||||||||||||||
| Surcharge for Raw Materials | None | ||||||||||||||||||||||||||||||||||||
| Metal Factor | LBO----- | ||||||||||||||||||||||||||||||||||||
| Delivery information | |||||||||||||||||||||||||||||||||||||
| Export Control Regulations | ECCN : EAR99 / AL : N | ||||||||||||||||||||||||||||||||||||
| Standard lead time ex-works | 5 Day/Days | ||||||||||||||||||||||||||||||||||||
| Net Weight (kg) | 2,447 Kg | ||||||||||||||||||||||||||||||||||||
| Product Dimensions (W x L x H) | Not available | ||||||||||||||||||||||||||||||||||||
| Packaging Dimension | 136,00 x 244,00 x 128,00 | ||||||||||||||||||||||||||||||||||||
| Package size unit of measure | MM | ||||||||||||||||||||||||||||||||||||
| Quantity Unit | 1 Piece | ||||||||||||||||||||||||||||||||||||
| Packaging Quantity | 1 | ||||||||||||||||||||||||||||||||||||
| Additional Product Information | |||||||||||||||||||||||||||||||||||||
| EAN | 4011209804241 | ||||||||||||||||||||||||||||||||||||
| UPC | Not available | ||||||||||||||||||||||||||||||||||||
| Commodity Code | 85362090 | ||||||||||||||||||||||||||||||||||||
| LKZ_FDB/ CatalogID | LV10.1 | ||||||||||||||||||||||||||||||||||||
| Product Group | 3740 | ||||||||||||||||||||||||||||||||||||
| Group Code | P360 | ||||||||||||||||||||||||||||||||||||
| Country of origin | Germany | ||||||||||||||||||||||||||||||||||||
| Compliance with the substance restrictions according to RoHS directive | Since: 01.07.2006 | ||||||||||||||||||||||||||||||||||||
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. | ||||||||||||||||||||||||||||||||||||
| WEEE (2012/19/EU) Take-Back Obligation | Yes | ||||||||||||||||||||||||||||||||||||
| REACH Art. 33 Duty to inform according to the current list of candidates |
| ||||||||||||||||||||||||||||||||||||
| Classifications | |||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||