| Digital monitoring relay for residual current monitoring with residual-current transformer 3UL23 for IO-Link Setting range 0.03 A to 40 A separate for warning threshold and switch-off value ON delay and tripping delay 0 to 999.9 s Shutdown hysteresis up to 50% Warning hysteresis 5% fixed Width 22.5mm, 2 change-over contacts with or without fault buffer screw terminal |
| product brand name | SIRIUS |
| product designation | Residual current monitoring relay with digital setting |
| product type designation | 3UG4 |
| General technical data |
| product function | for three-phase supplies |
| design of the display | LCD |
| insulation voltage | |
| ● rated value | 300 V |
| ● for overvoltage category III according to IEC 60664 | |
| — with degree of pollution 3 rated value | 300 V |
| degree of pollution | 3 |
| type of voltage of the control supply voltage | DC |
| surge voltage resistance rated value | 4 kV |
| protection class IP | IP20 |
| ● of the enclosure | IP20 |
| ● of the terminal | IP20 |
| shock resistance according to IEC 60068-2-27 | sinusoidal half-wave 15g / 11 ms |
| vibration resistance according to IEC 60068-2-6 | 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g |
| mechanical service life (switching cycles) typical | 10 000 000 |
| electrical endurance (switching cycles) at AC-15 at 230 V typical | 100 000 |
| thermal current of the switching element with contacts maximum | 5 A |
| reference code according to IEC 81346-2 | K |
| relative repeat accuracy | 1 % |
| Substance Prohibitance (Date) | 02/14/2013 |
| Product Function |
| product function | |
| ● residual current display | Yes |
| ● error memory | Yes |
| ● overcurrent detection 1 phase | Yes |
| ● undercurrent detection 1 phase | No |
| ● adjustable open/closed-circuit current principle | Yes |
| ● external reset | Yes |
| Control circuit/ Control |
| control supply voltage at DC | |
| ● rated value | 24 ... 24 V |
| operating range factor control supply voltage rated value at DC | |
| ● initial value | 0.85 |
| ● full-scale value | 1.1 |
| Measuring circuit |
| type of current for monitoring | AC |
| measurable current | 10 mA ... 43 A |
| measurable line frequency | 16 ... 400 Hz |
| adjustable operating delay time | 0 ... 999.9 s |
| adjustable current response value current | |
| ● 1 | 30 mA ... 40 A |
| ● 2 | 30 mA ... 40 A |
| adjustable response delay time | 0 ... 999.9 s |
| adjustable response delay time when starting | 0 ... 999.9 s |
| buffering time in the event of power failure minimum | 10 ms |
| accuracy of digital display | +/-1 digit |
| Precision |
| relative metering precision | 5 % |
| temperature drift per °C | 0.1 %/°C |
| Communication/ Protocol |
| protocol is supported IO-Link protocol | Yes |
| IO-Link transfer rate | COM2 (38,4 kBaud) |
| point-to-point cycle time between master and IO-Link device minimum | 10 ms |
| type of voltage supply via input/output link master | Yes |
| data volume | |
| ● of the address range of the inputs with cyclical transfer total | 4 byte |
| ● of the address range of the outputs with cyclical transfer total | 2 byte |
| Auxiliary circuit |
| number of NC contacts for auxiliary contacts | 0 |
| number of NC contacts delayed switching | 0 |
| number of NO contacts for auxiliary contacts | 0 |
| number of NO contacts delayed switching | 0 |
| number of CO contacts | |
| ● for auxiliary contacts | 2 |
| ● delayed switching | 2 |
| operating frequency with 3RT2 contactor maximum | 5 000 1/h |
| Main circuit |
| type of voltage | DC |
| operating voltage rated value | 24 ... 24 V |
| operating frequency rated value | 16 ... 400 Hz |
| ampacity of the output relay at AC-15 | |
| ● at 250 V at 50/60 Hz | 3 A |
| ● at 400 V at 50/60 Hz | 0 A |
| ampacity of the output relay at DC-13 | |
| ● at 24 V | 1 A |
| ● at 125 V | 0.2 A |
| ● at 250 V | 0.1 A |
| ampacity of the semiconductor output in SIO mode | 200 mA |
| operational current at 17 V minimum | 5 mA |
| continuous current of the DIAZED fuse link of the output relay | 4 A |
| Electromagnetic compatibility |
| conducted interference | |
| ● due to burst according to IEC 61000-4-4 | 2 kV |
| ● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
| ● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV |
| field-based interference according to IEC 61000-4-3 | 10 V/m |
| electrostatic discharge according to IEC 61000-4-2 | 4 kV contact discharge / 8 kV air discharge |
| Galvanic isolation |
| design of the electrical isolation | galvanic isolation |
| galvanic isolation | |
| ● between input and output | Yes |
| ● between the outputs | Yes |
| ● between the voltage supply and other circuits | No |
| Connections/ Terminals |
| product component removable terminal for auxiliary and control circuit | Yes |
| type of electrical connection | screw-type terminals |
| type of connectable conductor cross-sections | |
| ● solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
| ● finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
| ● at AWG cables solid | 2x (20 ... 14) |
| ● at AWG cables stranded | 2x (20 ... 14) |
| connectable conductor cross-section | |
| ● solid | 0.5 ... 4 mm² |
| ● finely stranded with core end processing | 0.5 ... 2.5 mm² |
| AWG number as coded connectable conductor cross section | |
| ● solid | 20 ... 14 |
| ● stranded | 20 ... 14 |
| tightening torque with screw-type terminals | 0.8 ... 1.2 N·m |
| Installation/ mounting/ dimensions |
| mounting position | any |
| fastening method | screw and snap-on mounting onto 35 mm standard mounting rail |
| height | 102 mm |
| width | 22.5 mm |
| depth | 91 mm |
| required spacing | |
| ● with side-by-side mounting | |
| — forwards | 0 mm |
| — backwards | 0 mm |
| — upwards | 0 mm |
| — downwards | 0 mm |
| — at the side | 0 mm |
| ● for grounded parts | |
| — forwards | 0 mm |
| — backwards | 0 mm |
| — upwards | 0 mm |
| — at the side | 0 mm |
| — downwards | 0 mm |
| ● for live parts | |
| — forwards | 0 mm |
| — backwards | 0 mm |
| — upwards | 0 mm |
| — downwards | 0 mm |
| — at the side | 0 mm |
| Ambient conditions |
| installation altitude at height above sea level maximum | 2 000 m |
| ambient temperature | |
| ● during operation | -25 ... +60 °C |
| ● during storage | -40 ... +85 °C |
| ● during transport | -40 ... +85 °C |
| Certificates/ approvals |
Downloads and manuals |
|
| Further information |
Information- and Downloadcenter (Catalogs, Brochures,…) |
Industry Mall (Online ordering system) |
Cax online generator |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) |
Characteristic: Derating |
|
|
|
| last modified: | 12/1/2021 |
Date 5/14/2022 | Subject to change without notice © Copyright Siemens 2022 |