View larger
3UG4616-2CR20 SIEMENS Digital monitoring relay for 3-phase voltage with N-conductor Phase sequence can be ac..
3UG4616-2CR20
46162
SIEMENS
1 Pcs.
Automation > Phase monitoring relay
Function relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Siemens 3UG4616-2CR20 Digital monitoring relay for 3-phase voltage with N-conductor acts as an intelligent protective controller within complex electrical distribution architectures. It constantly evaluates network quality to detect imbalances, phase errors, and voltage thresholds, ensuring critical industrial systems remain shielded from electrical degradation. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- product designation: Network monitoring relay with digital setting
- design of the product: 5 functions
- product type designation: 3UG4
- General technical data product function: Phase monitoring relay
- display version LED: No
- design of the display: LCD
- ● with degree of pollution 3 rated value: 690 V
- degree of pollution: 3
- ● for monitoring: AC
- ● of the control supply voltage: AC
- surge voltage resistance rated value: 6 kV
- protection class IP: IP20
- shock resistance according to IEC 60068-2-27: sinusoidal half-wave 15g / 11 ms
- vibration resistance according to IEC 60068-2-6: 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g
- mechanical service life (switching cycles) typical: 10 000 000
- reference code according to IEC 81346-2: K
More info
▲Technical data
Additional data
| Product | |||||||||||||||||||||||||||||||||||||
| Article Number (Market Facing Number) | 3UG4616-2CR20 | ||||||||||||||||||||||||||||||||||||
| Product Description | Digital monitoring relay for 3-phase voltage with N-conductor Phase sequence can be activated Phase failure 3 x 90 to 400 V 50 to 60 Hz AC Undervoltage and overvoltage 90-400 V Hysteresis 1-20 V 0-20 s each for Umin and Umax 1 CO for Umin 1 CO for Umax Spring-type terminal | ||||||||||||||||||||||||||||||||||||
| Product family | Line monitoring | ||||||||||||||||||||||||||||||||||||
| Product Lifecycle (PLM) | PM300:Active Product | ||||||||||||||||||||||||||||||||||||
| Price data | |||||||||||||||||||||||||||||||||||||
| Region Specific PriceGroup / Headquarter Price Group | 41H / 41H | ||||||||||||||||||||||||||||||||||||
| Surcharge for Raw Materials | None | ||||||||||||||||||||||||||||||||||||
| Metal Factor | LAO----- | ||||||||||||||||||||||||||||||||||||
| Delivery information | |||||||||||||||||||||||||||||||||||||
| Export Control Regulations | AL : N / ECCN : N | ||||||||||||||||||||||||||||||||||||
| Standard lead time ex-works | 20 Day/Days | ||||||||||||||||||||||||||||||||||||
| Net Weight (kg) | 0,151 Kg | ||||||||||||||||||||||||||||||||||||
| Packaging Dimension | 29,00 x 99,00 x 107,00 | ||||||||||||||||||||||||||||||||||||
| Package size unit of measure | MM | ||||||||||||||||||||||||||||||||||||
| Quantity Unit | 1 Piece | ||||||||||||||||||||||||||||||||||||
| Packaging Quantity | 1 | ||||||||||||||||||||||||||||||||||||
| Additional Product Information | |||||||||||||||||||||||||||||||||||||
| EAN | 4011209642591 | ||||||||||||||||||||||||||||||||||||
| UPC | 887621883720 | ||||||||||||||||||||||||||||||||||||
| Commodity Code | 85364900 | ||||||||||||||||||||||||||||||||||||
| LKZ_FDB/ CatalogID | CC-IC10 | ||||||||||||||||||||||||||||||||||||
| Product Group | 5885 | ||||||||||||||||||||||||||||||||||||
| Group Code | R711 | ||||||||||||||||||||||||||||||||||||
| Country of origin | Germany | ||||||||||||||||||||||||||||||||||||
| Compliance with the substance restrictions according to RoHS directive | Since: 01.05.2012 | ||||||||||||||||||||||||||||||||||||
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. | ||||||||||||||||||||||||||||||||||||
| WEEE (2012/19/EU) Take-Back Obligation | Yes | ||||||||||||||||||||||||||||||||||||
| REACH Art. 33 Duty to inform according to the current list of candidates |
| ||||||||||||||||||||||||||||||||||||
| Classifications | |||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||
ETIM data
ETIM: EC001441 - Phase monitoring relay
| Value | Unit | |
|---|---|---|
| Type of electric connection (EF003961) | Spring clamp connection | |
| With detachable clamps (EF003340) | true | |
| Rated control supply voltage Us at AC 50HZ (EF003978) | ['90.0', '400.0'] | V |
| Rated control supply voltage Us at AC 60HZ (EF003979) | ['90.0', '400.0'] | V |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] | V |
| Voltage type for actuating (EF008242) | AC | |
| Phase sequence monitoring (EF003412) | true | |
| Phase failure detection (EF003413) | true | |
| Function under voltage detection (EF003414) | true | |
| Function over voltage detection (EF003415) | true | |
| Phase imbalance monitoring (EF003416) | true | |
| Voltage measuring range (EF002486) | ['90', '400'] | V |
| Min. adjustable delay-on energization time (EF008190) | - | s |
| Max. permitted delay-on energization time (EF008189) | - | s |
| Min. adjustable off-delay time (EF008192) | 0.1 | s |
| Max. permitted off-delay time (EF008191) | 20 | s |
| Number of contacts as normally closed contact (EF008255) | 0 | |
| Number of contacts as normally open contact (EF008256) | 0 | |
| Number of contacts as change-over contact (EF008257) | 2 | |
| Width (EF000008) | 22.5 | mm |
| Height (EF000040) | 103.0 | mm |
| Depth (EF000049) | 91.0 | mm |