View larger
3UF7510-1AA00-0
75101
SIEMENS
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Ground fault module with analog residual current detection for connection of a residual-current transformer 3UL23, max. 1 ground fault module per, for SIMOCODE pro V basic unit | ||||||||||||||||||||||||||
| product brand name | SIRIUS | |||||||||||||||||||||||||
| product designation | ground fault modules | |||||||||||||||||||||||||
| manufacturer's article number | ||||||||||||||||||||||||||
| ● 1 of residual current transformer connectable | 3UL2302-1A | |||||||||||||||||||||||||
| ● 2 of residual current transformer connectable | 3UL2303-1A | |||||||||||||||||||||||||
| ● 3 of residual current transformer connectable | 3UL2304-1A | |||||||||||||||||||||||||
| ● 4 of residual current transformer connectable | 3UL2305-1A | |||||||||||||||||||||||||
| ● 5 of residual current transformer connectable | 3UL2306-1A | |||||||||||||||||||||||||
| ● 6 of residual current transformer connectable | 3UL2307-1A | |||||||||||||||||||||||||
| General technical data | ||||||||||||||||||||||||||
| type of current for monitoring | AC and pulse-shaped direct currents (type A) | |||||||||||||||||||||||||
| response time maximum | 100 ms | |||||||||||||||||||||||||
| product component | ||||||||||||||||||||||||||
| ● input for thermistor connection | No | |||||||||||||||||||||||||
| ● input for analog temperature sensors | No | |||||||||||||||||||||||||
| ● input for ground fault detection | Yes | |||||||||||||||||||||||||
| consumed active power | 0.1 W | |||||||||||||||||||||||||
| protection class IP | IP20 | |||||||||||||||||||||||||
| shock resistance according to IEC 60068-2-27 | 15g / 11 ms | |||||||||||||||||||||||||
| vibration resistance according to IEC 60068-2-6 | 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g | |||||||||||||||||||||||||
| Substance Prohibitance (Date) | 05/01/2012 | |||||||||||||||||||||||||
| measurable line frequency initial value | 400 Hz | |||||||||||||||||||||||||
| measurable line frequency full-scale value | 16 Hz | |||||||||||||||||||||||||
| relative measurement deviation of residual current transformer | 2.5 % | |||||||||||||||||||||||||
| Electromagnetic compatibility | ||||||||||||||||||||||||||
| EMC emitted interference according to IEC 60947-1 | class A | |||||||||||||||||||||||||
| EMC immunity according to IEC 60947-1 | corresponds to degree of severity 3 | |||||||||||||||||||||||||
| conducted interference | ||||||||||||||||||||||||||
| ● due to burst according to IEC 61000-4-4 | 1 kV | |||||||||||||||||||||||||
| ● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV | |||||||||||||||||||||||||
| ● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV | |||||||||||||||||||||||||
| ● due to high-frequency radiation according to IEC 61000-4-6 | 10 V | |||||||||||||||||||||||||
| field-based interference according to IEC 61000-4-3 | 10 V/m | |||||||||||||||||||||||||
| electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge | |||||||||||||||||||||||||
| field-bound HF interference emission according to CISPR11 | corresponds to degree of severity A | |||||||||||||||||||||||||
| Inputs/ Outputs | ||||||||||||||||||||||||||
| number of inputs | 1 | |||||||||||||||||||||||||
| number of digital inputs | 0 | |||||||||||||||||||||||||
| number of analog inputs | 1 | |||||||||||||||||||||||||
| number of sensor inputs for ground fault detection | 1 | |||||||||||||||||||||||||
| number of outputs | 0 | |||||||||||||||||||||||||
| number of semiconductor outputs | 0 | |||||||||||||||||||||||||
| number of outputs as contact-affected switching element | 0 | |||||||||||||||||||||||||
| number of analog outputs | 0 | |||||||||||||||||||||||||
| Installation/ mounting/ dimensions | ||||||||||||||||||||||||||
| mounting position | any | |||||||||||||||||||||||||
| fastening method | screw and snap-on mounting | |||||||||||||||||||||||||
| height | 92 mm | |||||||||||||||||||||||||
| width | 22.5 mm | |||||||||||||||||||||||||
| depth | 124 mm | |||||||||||||||||||||||||
| required spacing | ||||||||||||||||||||||||||
| ● top | 40 mm | |||||||||||||||||||||||||
| ● bottom | 40 mm | |||||||||||||||||||||||||
| ● left | 0 mm | |||||||||||||||||||||||||
| ● right | 0 mm | |||||||||||||||||||||||||
| diameter of inlet opening of connectable residual current transformer | 35 ... 210 mm | |||||||||||||||||||||||||
| Connections/ Terminals | ||||||||||||||||||||||||||
| type of connectable conductor cross-sections | ||||||||||||||||||||||||||
| ● solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) | |||||||||||||||||||||||||
| ● finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) | |||||||||||||||||||||||||
| ● at AWG cables solid | 1x (20 ... 14), 2x (20 ... 16) | |||||||||||||||||||||||||
| ● at AWG cables stranded | 1x (20 ... 12), 2x (20 ... 14) | |||||||||||||||||||||||||
| tightening torque with screw-type terminals | 0.8 ... 1.2 N·m | |||||||||||||||||||||||||
| tightening torque [lbf·in] with screw-type terminals | 7 ... 10.3 lbf·in | |||||||||||||||||||||||||
| Ambient conditions | ||||||||||||||||||||||||||
| installation altitude at height above sea level | ||||||||||||||||||||||||||
| ● 1 maximum | 2 000 m | |||||||||||||||||||||||||
| ● 2 maximum | 3 000 m; max. +50 °C (no protective separation) | |||||||||||||||||||||||||
| ● 3 maximum | 4 000 m; max. +40 °C (no protective separation) | |||||||||||||||||||||||||
| ambient temperature | ||||||||||||||||||||||||||
| ● during operation | -25 ... +60 °C | |||||||||||||||||||||||||
| ● during storage | -40 ... +80 °C | |||||||||||||||||||||||||
| ● during transport | -40 ... +80 °C | |||||||||||||||||||||||||
| environmental category | ||||||||||||||||||||||||||
| ● during operation according to IEC 60721 | 3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 | |||||||||||||||||||||||||
| ● during storage according to IEC 60721 | 1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4 | |||||||||||||||||||||||||
| ● during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 | |||||||||||||||||||||||||
| relative humidity during operation | 5 ... 95 % | |||||||||||||||||||||||||
| Safety related data | ||||||||||||||||||||||||||
| touch protection against electrical shock | finger-safe | |||||||||||||||||||||||||
| Galvanic isolation | ||||||||||||||||||||||||||
| (electrically) protective separation according to IEC 60947-1 | All circuits with protective separation (double creepage paths and clearances), the information in the "Protective Separation" test report, No. 2668, must be observed. | |||||||||||||||||||||||||
| Certificates/ approvals | ||||||||||||||||||||||||||
Downloads and manuals | ||||||||||||||||||||||||||
| ||||||||||||||||||||||||||
| Further information | ||||||||||||||||||||||||||
Information- and Downloadcenter (Catalogs, Brochures,…) | ||||||||||||||||||||||||||
Industry Mall (Online ordering system) | ||||||||||||||||||||||||||
Cax online generator | ||||||||||||||||||||||||||
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) | ||||||||||||||||||||||||||
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) | ||||||||||||||||||||||||||
Test report No. A0258, protective separation | ||||||||||||||||||||||||||
| last modified: | 4/7/2022 | |||||||||||||||||||||||||
| Date 5/6/2022 | Subject to change without notice © Copyright Siemens 2022 | |||||||||||||||||||||||||
| Product | |||||||||||||||||||||||||||||||||||||
| Article Number (Market Facing Number) | 3UF7510-1AA00-0 | ||||||||||||||||||||||||||||||||||||
| Product Description | Ground fault module with analog residual current detection for connection of a residual-current transformer 3UL23, max. 1 ground fault module per, for SIMOCODE pro V basic unit | ||||||||||||||||||||||||||||||||||||
| Product family | SIMOCODE pro 3UF7 motor management and control devices | ||||||||||||||||||||||||||||||||||||
| Product Lifecycle (PLM) | PM300:Active Product | ||||||||||||||||||||||||||||||||||||
| Price data | |||||||||||||||||||||||||||||||||||||
| Region Specific PriceGroup / Headquarter Price Group | 42J / 42J | ||||||||||||||||||||||||||||||||||||
| Surcharge for Raw Materials | None | ||||||||||||||||||||||||||||||||||||
| Metal Factor | None | ||||||||||||||||||||||||||||||||||||
| Delivery information | |||||||||||||||||||||||||||||||||||||
| Export Control Regulations | AL : N / ECCN : EAR99 | ||||||||||||||||||||||||||||||||||||
| Standard lead time ex-works | 1 Day/Days | ||||||||||||||||||||||||||||||||||||
| Net Weight (kg) | 0,134 Kg | ||||||||||||||||||||||||||||||||||||
| Packaging Dimension | 28,00 x 108,50 x 147,00 | ||||||||||||||||||||||||||||||||||||
| Package size unit of measure | MM | ||||||||||||||||||||||||||||||||||||
| Quantity Unit | 1 Piece | ||||||||||||||||||||||||||||||||||||
| Packaging Quantity | 1 | ||||||||||||||||||||||||||||||||||||
| Additional Product Information | |||||||||||||||||||||||||||||||||||||
| EAN | 4011209912496 | ||||||||||||||||||||||||||||||||||||
| UPC | 887621549275 | ||||||||||||||||||||||||||||||||||||
| Commodity Code | 85389091 | ||||||||||||||||||||||||||||||||||||
| LKZ_FDB/ CatalogID | CC-IC10 | ||||||||||||||||||||||||||||||||||||
| Product Group | 5836 | ||||||||||||||||||||||||||||||||||||
| Group Code | R711 | ||||||||||||||||||||||||||||||||||||
| Country of origin | Germany | ||||||||||||||||||||||||||||||||||||
| Compliance with the substance restrictions according to RoHS directive | Since: 01.05.2012 | ||||||||||||||||||||||||||||||||||||
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. | ||||||||||||||||||||||||||||||||||||
| WEEE (2012/19/EU) Take-Back Obligation | Yes | ||||||||||||||||||||||||||||||||||||
| REACH Art. 33 Duty to inform according to the current list of candidates |
| ||||||||||||||||||||||||||||||||||||
| Classifications | |||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||
| Value | Unit | |
|---|---|---|
| Rated control supply voltage Us at AC 60HZ (EF003979) | - | V |
| Degree of protection (NEMA) (EF011959) | - | |
| Switching function (EF000189) | - | |
| Voltage type for actuating (EF008242) | - | |
| Rated control supply voltage Us at DC (EF003980) | - | V |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - | V |
| Model (EF000010) | Earth fault module | |
| Number of analogue inputs (EF001994) | 1 | |
| Number of analogue outputs (EF001995) | 0 | |
| Number of outputs, with contact (EF006936) | 0 | |
| Number of electronic outputs (EF006929) | 0 | |
| Number of binary inputs (EF003817) | 0 | |
| Input for thermistor connection (EF007116) | false | |
| Input for earth fault detection (EF007115) | true | |
| Input for analogue temperature sensor (EF007114) | false | |
| Type of electrical connection for auxiliary- and control current circuit (EF006979) | Screw connection | |
| Degree of protection (IP) (EF005474) | IP20 |