| Contactor size 2, 2-pole DC-3 and 5, 32 A Auxiliary switch 22 (2 NO + 2 NC) Alternating current operation 500 V AC 50 Hz/600 V AC 60 Hz |
| Product designation | Contactor |
| Product type designation | 3TC |
| General technical data |
| Size of contactor | 2 |
| Product extension | |
| ● function module for communication | No |
| ● Auxiliary switch | Yes |
| Insulation voltage rated value | 800 V |
| maximum permissible voltage for safe isolation between coil and main contacts acc. to EN 60947-1 | 300 V |
| |
| ● Protection class IP | IP00 |
| ● protection class IP on the front | IP00 |
| ● Protection class IP of the terminal | IP00 |
| Shock resistance at rectangular impulse | |
| ● at AC | 7,5g / 5 ms, 3,4g / 10 ms |
| Mechanical service life (switching cycles) | |
| ● of contactor typical | 10 000 000 |
| ● of the contactor with added auxiliary switch block typical | 10 000 000 |
| Reference code acc. to DIN EN 81346-2 | Q |
| Ambient conditions |
| Ambient temperature | |
| ● during operation | -25 ... +55 °C |
| ● during storage | -50 ... +80 °C |
| Main circuit |
| number of poles | 2 |
| Number of poles for main current circuit | 2 |
| Number of NO contacts for main contacts | 2 |
| Number of NC contacts for main contacts | 0 |
| type of voltage | DC |
| Operating current | |
| ● with 2 current paths in series at DC-1 | |
| — at 24 V rated value | 32 A |
| — at 110 V rated value | 32 A |
| — at 220 V rated value | 32 A |
| — at 440 V rated value | 32 A |
| — at 600 V rated value | 32 A |
| Operating current | |
| ● at DC-3 at DC-5 | |
| — at 220 V rated value | 32 A |
| — at 440 V rated value | 29 A |
| — at 600 V rated value | 21 A |
| — at 750 V rated value | 7.5 A |
| ● with 2 current paths in series at DC-3 at DC-5 | |
| — at 24 V rated value | 32 A |
| — at 110 V rated value | 32 A |
| — at 220 V rated value | 32 A |
| — at 440 V rated value | 29 A |
| — at 600 V rated value | 21 A |
| Operating power | |
| ● at DC-1 | |
| — at 110 V rated value | 3.5 kW |
| — at 220 V rated value | 7 kW |
| — at 440 V rated value | 14 kW |
| — at 750 V rated value | 24 kW |
| ● at DC-3 at DC-5 | |
| — at 110 V rated value | 2.5 kW |
| — at 220 V rated value | 5 kW |
| — at 440 V rated value | 9 kW |
| — at 600 V rated value | 9 kW |
| — at 750 V rated value | 4 kW |
| Operating frequency | |
| ● at DC-1 maximum | 1 500 1/h |
| ● at DC-3 maximum | 750 1/h |
| ● at DC-5 maximum | 750 1/h |
| Control circuit/ Control |
| Type of voltage of the control supply voltage | AC |
| Control supply voltage at AC | |
| ● at 50 Hz rated value | 500 V |
| ● at 60 Hz rated value | 600 V |
| Operating range factor control supply voltage rated value of magnet coil at AC | |
| ● at 50 Hz | 0.8 ... 1.1 |
| Apparent pick-up power of magnet coil at AC | 68 V·A |
| ● at 50 Hz | 68 V·A |
| ● at 60 Hz | 95 V·A |
| Inductive power factor with closing power of the coil | 0.86 |
| ● at 50 Hz | 0.86 |
| ● at 60 Hz | 0.79 |
| Apparent holding power of magnet coil at AC | 10 V·A |
| ● at 50 Hz | 10 V·A |
| ● at 60 Hz | 12 V·A |
| Inductive power factor with the holding power of the coil | 0.29 |
| ● at 50 Hz | 0.29 |
| ● at 60 Hz | 0.3 |
| Arcing time | 20 ... 30 ms |
| Auxiliary circuit |
| Number of NC contacts for auxiliary contacts | 2 |
| ● instantaneous contact | 2 |
| Number of NO contacts for auxiliary contacts | 2 |
| ● instantaneous contact | 2 |
| Number of CO contacts | |
| ● for auxiliary contacts | 0 |
| Identification number and letter for switching elements | 22 |
| Operating current at AC-12 maximum | 10 A |
| Operating current at AC-15 | |
| ● at 230 V rated value | 5.6 A |
| ● at 400 V rated value | 3.6 A |
| ● at 500 V rated value | 2.5 A |
| Operating current at DC-12 | |
| ● at 24 V rated value | 10 A |
| ● at 48 V rated value | 10 A |
| ● at 60 V rated value | 10 A |
| ● at 110 V rated value | 3.2 A |
| ● at 125 V rated value | 2.5 A |
| ● at 220 V rated value | 0.9 A |
| ● at 600 V rated value | 0.22 A |
| Operating current at DC-13 | |
| ● at 24 V rated value | 10 A |
| ● at 48 V rated value | 5 A |
| ● at 60 V rated value | 5 A |
| ● at 110 V rated value | 1.14 A |
| ● at 125 V rated value | 0.98 A |
| ● at 220 V rated value | 0.48 A |
| ● at 600 V rated value | 0.07 A |
| contact reliability of auxiliary contacts | one incorrect switching operation of 100 million switching operations (17 V, 5 mA) |
| UL/CSA ratings |
| Contact rating of auxiliary contacts according to UL | A600 / P600 |
| Short-circuit protection |
| Design of the fuse link | |
| ● for short-circuit protection of the main circuit | |
| — with type of coordination 1 required | gG: 50 A (690 V, 100 kA) |
| — with type of assignment 2 required | gG: 35 A (690 V, 100 kA) |
| ● for short-circuit protection of the auxiliary switch required | gG: 16 A (500 V, 1 kA) |
| Installation/ mounting/ dimensions |
| mounting position | +/-22,5° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface; standing, on horizontal mounting surface |
| Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
| ● Side-by-side mounting | Yes |
| Height | 85 mm |
| Width | 70 mm |
| Depth | 104 mm |
| Required spacing | |
| ● with side-by-side mounting | |
| — forwards | 15 mm |
| — Backwards | 0 mm |
| — upwards | 10 mm |
| — downwards | 10 mm |
| — at the side | 10 mm |
| ● for grounded parts | |
| — forwards | 30 mm |
| — Backwards | 0 mm |
| — upwards | 10 mm |
| — at the side | 10 mm |
| — downwards | 10 mm |
| ● for live parts | |
| — forwards | 30 mm |
| — Backwards | 0 mm |
| — upwards | 10 mm |
| — downwards | 10 mm |
| — at the side | 10 mm |
| Connections/ Terminals |
| |
| ● type of electrical connection | screw-type terminals |
| ● Type of electrical connection for main current circuit | screw-type terminals |
| ● Type of electrical connection for auxiliary and control current circuit | screw-type terminals |
| Type of connectable conductor cross-sections | |
| ● for main contacts | |
| — single or multi-stranded | 2x (2,5 ... 10 mm²) |
| — finely stranded with core end processing | 2x (1.5 ... 4 mm²) |
| Type of connectable conductor cross-sections | |
| ● for auxiliary contacts | |
| — single or multi-stranded | 2x (1 ... 2,5 mm²) |
| — finely stranded with core end processing | 2x (0.75 ... 2.5 mm²) |
| Safety related data |
| Protection against electrical shock | finger-safe only with terminal cover |
| Certificates/ approvals |
|
| Further information |
Information- and Downloadcenter (Catalogs, Brochures,…) |
Industry Mall (Online ordering system) |
Cax online generator |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) |
Characteristic: Tripping characteristics, I²t, Let-through current |
Further characteristics (e.g. electrical endurance, switching frequency) |
|
|
|
| last modified: | 08/13/2020 |