| Circuit breaker size S2 for starter combination Rated current 36 A N-release 520 A screw terminal Standard switching capacity |
| product brand name | SIRIUS |
| product designation | Circuit breaker |
| design of the product | For starter combinations |
| product type designation | 3RV2 |
| General technical data |
| size of the circuit-breaker | S2 |
| size of contactor can be combined company-specific | S2 |
| product extension auxiliary switch | Yes |
| power loss [W] for rated value of the current | |
| ● at AC in hot operating state | 20 W |
| ● at AC in hot operating state per pole | 6.7 W |
| insulation voltage with degree of pollution 3 at AC rated value | 690 V |
| surge voltage resistance rated value | 6 kV |
| maximum permissible voltage for safe isolation in networks with grounded star point | |
| ● between main and auxiliary circuit | 400 V |
| ● between main and auxiliary circuit | 400 V |
| shock resistance according to IEC 60068-2-27 | 25g / 11 ms Sinus |
| mechanical service life (switching cycles) | |
| ● of the main contacts typical | 50 000 |
| ● of auxiliary contacts typical | 50 000 |
| electrical endurance (switching cycles) typical | 50 000 |
| reference code according to IEC 81346-2 | Q |
| Substance Prohibitance (Date) | 10/15/2014 |
| Ambient conditions |
| installation altitude at height above sea level maximum | 2 000 m |
| ambient temperature | |
| ● during operation | -20 ... +60 °C |
| ● during storage | -50 ... +80 °C |
| ● during transport | -50 ... +80 °C |
| relative humidity during operation | 10 ... 95 % |
| Main circuit |
| number of poles for main current circuit | 3 |
| operating voltage | |
| ● rated value | 690 V |
| ● rated value | 20 ... 690 V |
| ● at AC-3 rated value maximum | 690 V |
| operating frequency rated value | 50 ... 60 Hz |
| operational current rated value | 36 A |
| operational current | |
| ● at AC-3 at 400 V rated value | 36 A |
| operating power | |
| ● at AC-3 | |
| — at 400 V rated value | 18.5 kW |
| — at 500 V rated value | 22 kW |
| — at 690 V rated value | 30 kW |
| operating frequency | |
| ● at AC-3 maximum | 15 1/h |
| Auxiliary circuit |
| number of NC contacts for auxiliary contacts | 0 |
| number of NO contacts for auxiliary contacts | 0 |
| Protective and monitoring functions |
| product function | |
| ● ground fault detection | No |
| ● phase failure detection | No |
| breaking capacity operating short-circuit current (Ics) at AC | |
| ● at 240 V rated value | 100 kA |
| ● at 400 V rated value | 30 kA |
| ● at 500 V rated value | 5 kA |
| ● at 690 V rated value | 2 kA |
| breaking capacity maximum short-circuit current (Icu) | |
| ● at AC at 240 V rated value | 100 kA |
| ● at AC at 400 V rated value | 65 kA |
| ● at AC at 500 V rated value | 10 kA |
| ● at AC at 690 V rated value | 4 kA |
| response value current of instantaneous short-circuit trip unit | 520 A |
| UL/CSA ratings |
| full-load current (FLA) for 3-phase AC motor | |
| ● at 480 V rated value | 36 A |
| ● at 600 V rated value | 36 A |
| yielded mechanical performance [hp] | |
| ● for single-phase AC motor | |
| — at 110/120 V rated value | 3 hp |
| — at 230 V rated value | 7.5 hp |
| ● for 3-phase AC motor | |
| — at 200/208 V rated value | 15 hp |
| — at 220/230 V rated value | 15 hp |
| — at 460/480 V rated value | 30 hp |
| — at 575/600 V rated value | 40 hp |
| Short-circuit protection |
| product function short circuit protection | Yes |
| design of the short-circuit trip | magnetic |
| design of the fuse link for IT network for short-circuit protection of the main circuit | |
| ● at 240 V | none required |
| ● at 400 V | 125 |
| ● at 500 V | 100 |
| ● at 690 V | 80 |
| Installation/ mounting/ dimensions |
| mounting position | any |
| fastening method | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715 |
| height | 140 mm |
| width | 55 mm |
| depth | 149 mm |
| required spacing | |
| ● for grounded parts at 400 V | |
| — downwards | 50 mm |
| — upwards | 50 mm |
| — at the side | 10 mm |
| ● for live parts at 400 V | |
| — downwards | 50 mm |
| — upwards | 50 mm |
| — at the side | 10 mm |
| ● for grounded parts at 500 V | |
| — downwards | 50 mm |
| — upwards | 50 mm |
| — at the side | 10 mm |
| ● for live parts at 500 V | |
| — downwards | 50 mm |
| — upwards | 50 mm |
| — at the side | 10 mm |
| ● for grounded parts at 690 V | |
| — downwards | 50 mm |
| — upwards | 50 mm |
| — backwards | 0 mm |
| — at the side | 10 mm |
| — forwards | 0 mm |
| ● for live parts at 690 V | |
| — downwards | 50 mm |
| — upwards | 50 mm |
| — backwards | 0 mm |
| — at the side | 10 mm |
| — forwards | 0 mm |
| Connections/ Terminals |
| product component removable terminal for auxiliary and control circuit | No |
| type of electrical connection | |
| ● for main current circuit | screw-type terminals |
| arrangement of electrical connectors for main current circuit | Top and bottom |
| type of connectable conductor cross-sections | |
| ● for main contacts | |
| — solid or stranded | 2x (1 ... 25 mm²), 1x (1 ... 35 mm²) |
| — finely stranded with core end processing | 2x (1 ... 16 mm²), 1x (1 ... 25 mm²) |
| ● at AWG cables for main contacts | 2x (18 ... 3), 1x (18 ... 2) |
| tightening torque | |
| ● for main contacts with screw-type terminals | 3 ... 4.5 N·m |
| design of screwdriver shaft | Diameter 5 to 6 mm |
| size of the screwdriver tip | Pozidriv size 2 |
| design of the thread of the connection screw | |
| ● for main contacts | M6 |
| Safety related data |
| B10 value | |
| ● with high demand rate according to SN 31920 | 5 000 |
| proportion of dangerous failures | |
| ● with low demand rate according to SN 31920 | 50 % |
| ● with high demand rate according to SN 31920 | 50 % |
| failure rate [FIT] | |
| ● with low demand rate according to SN 31920 | 50 FIT |
| protection class IP on the front according to IEC 60529 | IP20 |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
| display version for switching status | Handle |
| Certificates/ approvals |
Downloads and manuals |
|
| Further information |
Information- and Downloadcenter (Catalogs, Brochures,…) |
Industry Mall (Online ordering system) |
Cax online generator |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) |
Characteristic: Tripping characteristics, I²t, Let-through current |
Further characteristics (e.g. electrical endurance, switching frequency) |
|
|
|
| last modified: | 1/27/2022 |
Date 5/6/2022 | Subject to change without notice © Copyright Siemens 2022 |