SIEMENS 3RV1011-0CA15 3RV1011-0CA15 SIEMENS Circuit breaker size S00 for motor protection, CLASS 10 A-release 0.18...0.25 A N-rele.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

3RV1011-0CA15 SIEMENS Circuit breaker size S00 for motor protection, CLASS 10 A-release 0.18...0.25 A N-rele..

3RV1011-0CA15

10110

SIEMENS

1 Pcs.

Circuit breaker size S00 for motor protection, CLASS 10 A-release 0.18...0.25 A N-release 3.3 A Screw terminal Standard switching capacity with transverse auxiliary switch 1 NO+1 NC

Automation > Motor protection circuit-breaker
Motor protection switches

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Circuit breaker size S00 for motor protection, CLASS 10 A-release 0.18...0.25 A N-release 3.3 A Screw terminal Standard switching capacity with transverse auxiliary switch 1 NO+1 NC
product brand nameSIRIUS
product designationCircuit breaker
design of the productFor motor protection
product type designation3RV1
General technical data
size of the circuit-breakerS00
size of contactor can be combined company-specificS00
product extension auxiliary switchYes
power loss [W] for rated value of the current
● at AC in hot operating state5.5 W
● at AC in hot operating state per pole1.8 W
insulation voltage with degree of pollution 3 at AC rated value690 V
surge voltage resistance rated value6 kV
maximum permissible voltage for safe isolation in networks with grounded star point
● between main and auxiliary circuit400 V
● between main and auxiliary circuit400 V
mechanical service life (switching cycles)
● of the main contacts typical100 000
● of auxiliary contacts typical100 000
electrical endurance (switching cycles) typical100 000
reference code according to IEC 81346-2Q
Substance Prohibitance (Date)01/01/2013
Ambient conditions
installation altitude at height above sea level maximum2 000 m
ambient temperature
● during operation-20 ... +60 °C
● during storage-50 ... +80 °C
● during transport-50 ... +80 °C
temperature compensation-20 ... +60 °C
relative humidity during operation10 ... 95 %
Main circuit
number of poles for main current circuit3
adjustable current response value current of the current-dependent overload release0.18 ... 0.25 A
operating voltage
● rated value690 V
● rated value20 ... 690 V
● at AC-3 rated value maximum690 V
operating frequency rated value50 ... 60 Hz
operational current rated value0.25 A
operational current
● at AC-3 at 400 V rated value0.25 A
operating power
● at AC-3
— at 230 V rated value0 kW
— at 400 V rated value0.1 kW
— at 500 V rated value0.1 kW
— at 690 V rated value0.1 kW
operating frequency
● at AC-3 maximum15 1/h
Auxiliary circuit
design of the auxiliary switchtransverse
number of NC contacts for auxiliary contacts1
● note1
number of NO contacts for auxiliary contacts1
● note1
number of CO contacts for auxiliary contacts0
operational current of auxiliary contacts at AC-15
● at 24 V2 A
● at 110 V2 A
● at 120 V2 A
● at 125 V2 A
● at 230 V0.5 A
operational current of auxiliary contacts at DC-13
● at 24 V1 A
● at 60 V0.15 A
Protective and monitoring functions
product function
● ground fault detectionNo
● phase failure detectionYes
trip classCLASS 10
design of the overload releasethermal
breaking capacity operating short-circuit current (Ics) at AC
● at 240 V rated value100 kA
● at 400 V rated value100 kA
● at 500 V rated value100 kA
● at 690 V rated value100 kA
breaking capacity maximum short-circuit current (Icu)
● at AC at 240 V rated value100 kA
● at AC at 400 V rated value100 kA
● at AC at 500 V rated value100 kA
● at AC at 690 V rated value100 kA
response value current of instantaneous short-circuit trip unit3.3 A
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value0.25 A
● at 600 V rated value0.25 A
contact rating of auxiliary contacts according to ULC300 / R300
Short-circuit protection
product function short circuit protectionYes
design of the short-circuit tripmagnetic
design of the fuse link
● for short-circuit protection of the auxiliary switch requiredfuse gG: 10 A, miniature circuit breaker C 6 A (short-circuit current Ik < 400 A)
design of the fuse link for IT network for short-circuit protection of the main circuit
● at 240 Vnone required
● at 400 VNone required
● at 500 VNone required
● at 690 VNone required
Installation/ mounting/ dimensions
mounting positionany
fastening methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
height90 mm
width45 mm
depth75 mm
required spacing
● for grounded parts at 400 V
— downwards20 mm
— upwards20 mm
— at the side9 mm
● for live parts at 400 V
— downwards20 mm
— upwards20 mm
— at the side9 mm
● for grounded parts at 500 V
— downwards20 mm
— upwards20 mm
— at the side9 mm
● for live parts at 500 V
— downwards20 mm
— upwards20 mm
— at the side9 mm
● for grounded parts at 690 V
— downwards20 mm
— upwards20 mm
— backwards0 mm
— at the side9 mm
— forwards0 mm
● for live parts at 690 V
— downwards20 mm
— upwards20 mm
— backwards0 mm
— at the side9 mm
— forwards0 mm
Connections/ Terminals
product component removable terminal for auxiliary and control circuitNo
type of electrical connection
● for main current circuitscrew-type terminals
● for auxiliary and control circuitscrew-type terminals
arrangement of electrical connectors for main current circuitTop and bottom
type of connectable conductor cross-sections
● for main contacts
— solid or stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x (1 ... 4 mm²)
— finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
type of connectable conductor cross-sections
● for auxiliary contacts
— solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
tightening torque
● for main contacts with screw-type terminals0.8 ... 1.2 N·m
● for auxiliary contacts with screw-type terminals0.8 ... 1.2 N·m
size of the screwdriver tipPozidriv size 2
design of the thread of the connection screw
● for main contactsM3
● of the auxiliary and control contactsM3
Safety related data
B10 value
● with high demand rate according to SN 319205 000
proportion of dangerous failures
● with low demand rate according to SN 3192050 %
● with high demand rate according to SN 3192050 %
failure rate [FIT]
● with low demand rate according to SN 3192050 FIT
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
display version for switching statusRocker switch
Certificates/ approvals

Downloads and manuals

General Product ApprovalFor use in hazardous locations

CSA

Confirmation

CCC

UL

EAC

ATEX-EC-Type-Examination-Certificate

For use in hazardous locationsDeclaration of ConformityTest CertificatesMarine / Shipping

IECEx

EC/EU-Declaration of Conformity

UK Declaration of Conformity

Special Test Certificate

Type Test Certificates/Test Report

ABS (American Bureau of Shipping)

Marine / Shipping

BV / Bureau Veritas

LR (Lloyds Register)

PRS / Polski Rejestr Statkow

RINA / Registro Italiano Navale

RMRS / Russian Maritime Register

DNV-GL

otherRailway

Miscellaneous

Confirmation

Household and similar appliances

Special Test Certificate

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
Industry Mall (Online ordering system)
Cax online generator
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
Characteristic: Tripping characteristics, I²t, Let-through current
Further characteristics (e.g. electrical endurance, switching frequency)
last modified:1/27/2022
Date
5/12/2022
Subject to change without notice
© Copyright Siemens 2022


Additional data

Product
Article Number (Market Facing Number)3RV1011-0CA15
Product DescriptionCircuit breaker size S00 for motor protection, CLASS 10 A-release 0.18...0.25 A N-release 3.3 A Screw terminal Standard switching capacity with transverse auxiliary switch 1 NO+1 NC
Product familySIRIUS 3RV1 motor starter protectors
Product Lifecycle (PLM)PM300:Active Product
Price data
Region Specific PriceGroup / Headquarter Price Group41E / 41E
Surcharge for Raw MaterialsNone
Metal FactorLAP-----
Delivery information
Export Control RegulationsAL : N / ECCN : N
Standard lead time ex-works70 Day/Days
Net Weight (kg)0,244 Kg
Packaging Dimension49,00 x 100,00 x 84,00
Package size unit of measureMM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4011209381698
UPC754554966441
Commodity Code85362010
LKZ_FDB/ CatalogIDCC-IC10
Product Group3715
Group CodeR711
Country of originGermany
Compliance with the substance restrictions according to RoHS directiveSince: 01.01.2013
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
VersionClassification
eClass627-37-04-01
eClass7.127-37-04-01
eClass827-37-04-01
eClass927-37-04-01
eClass9.127-37-04-01
ETIM5EC000074
ETIM6EC000074
ETIM7EC000074
ETIM8EC000074
IDEA44845
UNSPSC1439-12-16-01
UNSPSC1539-12-16-01

ETIM data

ETIM: EC000074 - Motor protection circuit-breaker

Value Unit
Overload release current setting (EF002336) ['0.18', '0.25']A
Adjustment range undelayed short-circuit release (EF007131) ['3.3', '3.3']A
With thermal protection (EF006233) thermal
Phase failure sensitive (EF007400) true
Switch off technique (EF007007) Magnetic
Rated operating voltage (EF001435) ['690', '690']V
Rated permanent current Iu (EF001389) 0.25A
Rated operation power at AC-3, 230 V (EF007025) 0.037kW
Rated operation power at AC-3, 400 V (EF001364) 0.06kW
Type of electrical connection of main circuit (EF006819) Screw connection
Type of control element (EF006976) Rocker lever
Device construction (EF008240) Built-in device fixed built-in technique
With integrated auxiliary switch (EF001387) true
With integrated under voltage release (EF001390) false
Number of poles (EF001391) 3
Rated short-circuit breaking capacity lcu at 400 V, AC (EF007049) 100.0kA
Degree of protection (IP) (EF005474) IP20
Height (EF000040) 90.0mm
Width (EF000008) 45.0mm
Depth (EF000049) 75.0mm



Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.