| Capacitor contactor, AC-6b 75 kVAr, / 400 V 2 NC, 110 V AC, 50 Hz 3-pole, Size S3 screw terminal |
| product brand name | SIRIUS |
| product designation | capacitor contactors |
| product type designation | 3RT26 |
| General technical data |
| size of contactor | S3 |
| product extension auxiliary switch | Yes |
| insulation voltage | |
| ● of main circuit with degree of pollution 3 rated value | 1 000 V |
| ● of auxiliary circuit with degree of pollution 3 rated value | 690 V |
| surge voltage resistance | |
| ● of main circuit rated value | 8 kV |
| ● of auxiliary circuit rated value | 6 kV |
| maximum permissible voltage for safe isolation between coil and main contacts according to EN 60947-1 | 400 V |
| shock resistance at rectangular impulse | |
| ● at AC | 6.8g / 5 ms, 4g / 10 ms |
| shock resistance with sine pulse | |
| ● at AC | 10.6g / 5 ms, 6.2g / 10 ms |
| mechanical service life (switching cycles) | |
| ● of the contactor with added auxiliary switch block typical | 3 000 000 |
| electrical endurance (switching cycles) | 200 000 |
| reference code according to IEC 81346-2 | Q |
| Substance Prohibitance (Date) | 06/26/2017 |
| Ambient conditions |
| installation altitude at height above sea level maximum | 2 000 m |
| ambient temperature | |
| ● during operation | -25 ... +60 °C |
| ● during storage | -55 ... +80 °C |
| relative humidity minimum | 10 % |
| relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95 % |
| Main circuit |
| number of NO contacts for main contacts | 3 |
| number of NC contacts for main contacts | 0 |
| operational current at AC-6b at 690 V at ambient temperature 60 °C rated value | 108 A |
| operating reactive power at AC-6b | |
| ● at 230 V at 50/60 Hz at ambient temperature 60 °C rated value | 14 ... 43 kvar |
| ● at 400 V at 50/60 Hz at ambient temperature 60 °C rated value | 25 ... 75 kvar |
| ● at 500 V at 50/60 Hz at ambient temperature 60 °C rated value | 31 ... 94 kvar |
| ● at 690 V at 50/60 Hz at ambient temperature 60 °C rated value | 43 ... 129 kvar |
| no-load switching frequency | |
| ● at AC | 500 1/h |
| operating frequency at AC-6b | |
| ● at 230 V maximum | 200 1/h |
| ● at 240 V maximum | 200 1/h |
| ● at 400 V maximum | 100 1/h |
| ● at 480 V maximum | 60 1/h |
| ● at 500 V maximum | 60 1/h |
| ● at 600 V maximum | 40 1/h |
| ● at 690 V maximum | 40 1/h |
| Control circuit/ Control |
| type of voltage | AC |
| type of voltage of the control supply voltage | AC |
| control supply voltage at AC | |
| ● at 50 Hz rated value | 110 V |
| control supply voltage frequency | |
| ● 1 rated value | 50 Hz |
| operating range factor control supply voltage rated value of magnet coil at AC | |
| ● at 50 Hz | 0.8 ... 1.1 |
| apparent pick-up power of magnet coil at AC | 296 VA |
| inductive power factor with closing power of the coil | 0.61 |
| apparent holding power of magnet coil at AC | 19 VA |
| inductive power factor with the holding power of the coil | 0.38 |
| closing delay | |
| ● at AC | 13 ... 50 ms |
| opening delay | |
| ● at AC | 11 ... 20 ms |
| arcing time | 10 ... 20 ms |
| control version of the switch operating mechanism | Standard A1 - A2 |
| Auxiliary circuit |
| number of NC contacts for auxiliary contacts | 2 |
| ● attachable | 1 |
| ● instantaneous contact | 2 |
| number of NO contacts for auxiliary contacts | 0 |
| ● attachable | 1 |
| ● instantaneous contact | 0 |
| operational current of auxiliary contacts at AC-12 maximum | 10 A |
| operational current of auxiliary contacts at AC-15 | |
| ● at 230 V | 6 A |
| ● at 400 V | 3 A |
| operational current of auxiliary contacts at DC-13 | |
| ● at 24 V | 6 A |
| ● at 60 V | 2 A |
| ● at 110 V | 1 A |
| ● at 125 V | 0.9 A |
| ● at 220 V | 0.3 A |
| contact reliability of auxiliary contacts | 0.00000001 |
| UL/CSA ratings |
| contact rating of auxiliary contacts according to UL | A600 / Q600 |
| Short-circuit protection |
| design of the fuse link | |
| ● for short-circuit protection of the main circuit with type of coordination 1 required | gG: 250 A (690 V, 50 kA) |
| ● for short-circuit protection of the auxiliary switch required | gG: 10 A (500 V, 1 kA) |
| Installation/ mounting/ dimensions |
| mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
| fastening method | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
| height | 140 mm |
| width | 80 mm |
| depth | 152 mm |
| required spacing | |
| ● with side-by-side mounting at the side | 10 mm |
| ● for grounded parts at the side | 10 mm |
| Connections/ Terminals |
| type of electrical connection | |
| ● for main current circuit | screw-type terminals |
| ● for auxiliary and control circuit | screw-type terminals |
| ● at contactor for auxiliary contacts | Screw-type terminals |
| ● of magnet coil | Screw-type terminals |
| type of connectable conductor cross-sections | |
| ● for main contacts | |
| — solid | 2x (10 ... 16 mm²) |
| — stranded | 2x (10 ... 70 mm²), 1x (10 ... 70 mm²) |
| — solid or stranded | 2x (10 ... 70 mm²), 1x (10 ... 70 mm²) |
| — finely stranded with core end processing | 2x (10 ... 50 mm²) |
| ● at AWG cables for main contacts | 2x (8 ... 3/0), 1x (6 ... 3/0) |
| type of connectable conductor cross-sections | |
| ● for auxiliary contacts | |
| — solid | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm² |
| — solid or stranded | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm² |
| — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) |
| ● at AWG cables for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14), 2x 12 |
| type of minimum connectable cross-section for main contacts at AC-6b | |
| ● at 40 °C | 1x 50 mm² |
| ● at 60 °C | 2x 35 mm² |
| AWG number as coded connectable conductor cross section for main contacts | 8 |
| Safety related data |
| product function | |
| ● mirror contact according to IEC 60947-4-1 | No |
| ● positively driven operation according to IEC 60947-5-1 | No |
| protection class IP on the front according to IEC 60529 | IP20 |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
| Certificates/ approvals |
Downloads and manuals |
|
| Further information |
Information- and Downloadcenter (Catalogs, Brochures,…) |
Industry Mall (Online ordering system) |
Cax online generator |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) |
Characteristic: Tripping characteristics, I²t, Let-through current |
Further characteristics (e.g. electrical endurance, switching frequency) |
|
|
|
| last modified: | 12/8/2021 |