SIEMENS 3RT2344-1NF30 3RT2344-1NF30 SIEMENS Contactor, AC-1, 110 A/400 V/40 °C, S3, 4-pole, 83-155 V AC/DC 1 NO+1 NC, screw termin.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

3RT2344-1NF30 SIEMENS Contactor, AC-1, 110 A/400 V/40 °C, S3, 4-pole, 83-155 V AC/DC 1 NO+1 NC, screw termin..

3RT2344-1NF30

10000

SIEMENS

1 Pcs.

Contactor, AC-1, 110 A/400 V/40 °C, S3, 4-pole, 83-155 V AC/DC 1 NO+1 NC, screw terminal contactor, 4S, AC-1:110 A AC/DC 84 -155 V 4 poles, 4S, Size S3 screw terminal Varistor 1NA+1NC integrated. Manufactured to order. Non-Cancelable Non-Returnable.

Automation > Power contactor, AC switching
Contactors for switching motors

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Contactor, AC-1, 110 A/400 V/40 °C, S3, 4-pole, 83-155 V AC/DC 1 NO+1 NC, screw terminal
product brand nameSIRIUS
product designationContactor
product type designation3RT23
General technical data
size of contactorS3
product extension
● function module for communicationNo
● auxiliary switchYes
power loss [W] for rated value of the current
● at AC in hot operating state29.2 W
● at AC in hot operating state per pole7.3 W
● without load current share typical2.7 W
insulation voltage
● of main circuit with degree of pollution 3 rated value690 V
● of the auxiliary and control circuit with degree of pollution 3 rated value690 V
surge voltage resistance
● of main circuit rated value8 kV
● of auxiliary circuit rated value6 kV
shock resistance at rectangular impulse
● at AC6.7 g / 5 ms, 4.0 g / 10 ms
shock resistance with sine pulse
● at AC10.6 g / 5 ms, 6.3 g / 10 ms
mechanical service life (switching cycles)
● of contactor typical10 000 000
● of the contactor with added auxiliary switch block typical10 000 000
reference code according to IEC 81346-2Q
Substance Prohibitance (Date)09/01/2017
Ambient conditions
installation altitude at height above sea level maximum2 000 m
ambient temperature
● during operation-25 ... +60 °C
● during storage-55 ... +80 °C
relative humidity minimum10 %
relative humidity at 55 °C according to IEC 60068-2-30 maximum95 %
Main circuit
number of poles for main current circuit4
number of NO contacts for main contacts4
operational current
● at AC-1 at 400 V at ambient temperature 40 °C rated value110 A
● at AC-1
— up to 690 V at ambient temperature 40 °C rated value110 A
— up to 690 V at ambient temperature 60 °C rated value100 A
● at AC-3
— at 400 V rated value38 A
minimum cross-section in main circuit at maximum AC-1 rated value35 mm²
short-time withstand current in cold operating state up to 40 °C
● limited to 1 s switching at zero current maximumUse minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximumUse minimum cross-section acc. to AC-1 rated value
● limited to 10 s switching at zero current maximumUse minimum cross-section acc. to AC-1 rated value
● limited to 30 s switching at zero current maximumUse minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximumUse minimum cross-section acc. to AC-1 rated value
no-load switching frequency
● at AC1 000 1/h
● at DC1 000 1/h
operating frequency at AC-1 maximum650 1/h
Control circuit/ Control
type of voltageAC/DC
type of voltage of the control supply voltageAC/DC
control supply voltage at AC
● at 50 Hz rated value83 ... 155 V
● at 60 Hz rated value83 ... 155 V
control supply voltage at DC
● rated value83 ... 155 V
operating range factor control supply voltage rated value of magnet coil at DC
● initial value0.8
● full-scale value1.1
operating range factor control supply voltage rated value of magnet coil at AC
● at 50 Hz0.8 ... 1.1
● at 60 Hz0.8 ... 1.1
design of the surge suppressorwith varistor
duration of inrush current peak50 µs
duration of locked-rotor current150 ms
apparent pick-up power of magnet coil at AC
● at 50 Hz151 VA
● at 60 Hz151 VA
apparent holding power of magnet coil at AC
● at 50 Hz3.5 VA
● at 60 Hz3.5 VA
closing power of magnet coil at DC76 W
holding power of magnet coil at DC2.7 W
closing delay
● at AC50 ... 70 ms
● at DC50 ... 70 ms
opening delay
● at AC38 ... 57 ms
● at DC38 ... 57 ms
arcing time10 ... 20 ms
control version of the switch operating mechanismStandard A1 - A2
Auxiliary circuit
number of NC contacts for auxiliary contacts1
● attachable2
● instantaneous contact1
number of NO contacts for auxiliary contacts1
● attachable2
● instantaneous contact1
operational current at AC-12 maximum10 A
operational current at AC-15
● at 230 V rated value6 A
● at 400 V rated value3 A
● at 500 V rated value2 A
● at 690 V rated value1 A
operational current at DC-12
● at 24 V rated value10 A
● at 48 V rated value6 A
● at 60 V rated value6 A
● at 110 V rated value3 A
● at 125 V rated value2 A
● at 220 V rated value1 A
● at 600 V rated value0.15 A
operational current at DC-13
● at 24 V rated value10 A
● at 48 V rated value2 A
● at 110 V rated value1 A
● at 125 V rated value0.9 A
● at 220 V rated value0.3 A
● at 600 V rated value0.1 A
design of the miniature circuit breaker for short-circuit protection of the auxiliary switch requiredgG: 10 A (230 V, 400 A)
contact reliability of auxiliary contacts1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
contact rating of auxiliary contacts according to ULA600 / P600
Short-circuit protection
product function short circuit protectionNo
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 requiredgG: 250 A (690 V, 100 kA)
— with type of assignment 2 requiredgR: 250 A (690 V, 100 kA)
● for short-circuit protection of the auxiliary switch requiredgG: 10 A (690 V, 1 kA)
Installation/ mounting/ dimensions
mounting position+/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface
fastening methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
● side-by-side mountingYes
height140 mm
width96 mm
depth152 mm
required spacing
● with side-by-side mounting
— forwards20 mm
— upwards10 mm
— downwards10 mm
— at the side0 mm
● for grounded parts
— forwards20 mm
— upwards10 mm
— at the side10 mm
— downwards10 mm
● for live parts
— forwards20 mm
— upwards10 mm
— downwards10 mm
— at the side10 mm
Connections/ Terminals
type of electrical connection
● for main current circuitscrew-type terminals
● for auxiliary and control circuitscrew-type terminals
● at contactor for auxiliary contactsScrew-type terminals
● of magnet coilScrew-type terminals
type of connectable conductor cross-sections
● for main contacts
— stranded2x (6 ... 16 mm²), 2x (10 ... 50 mm²), 1x (10 ... 70 mm²)
— solid or stranded2x (2.5 ... 16 mm²), 2x (6 ... 16 mm²), 2x (10 ... 50 mm²), 1x (10 ... 70 mm²)
— finely stranded with core end processing2x (2.5 ... 35 mm²), 1x (2.5 ... 50 mm²)
● at AWG cables for main contacts2x (10 ... 1/0), 1x (10 ... 2)
connectable conductor cross-section for main contacts
● solid2.5 ... 16 mm²
● solid or stranded4 ... 70 mm²
● stranded6 ... 70 mm²
● finely stranded with core end processing2.5 ... 50 mm²
connectable conductor cross-section for auxiliary contacts
● solid or stranded0.5 ... 2.5 mm²
● finely stranded with core end processing0.5 ... 2.5 mm²
type of connectable conductor cross-sections
● for auxiliary contacts
— solid2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
— solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
— finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
AWG number as coded connectable conductor cross section
● for main contacts10 ... 2
● for auxiliary contacts20 ... 14
Safety related data
product function
● mirror contact according to IEC 60947-4-1Yes
● positively driven operation according to IEC 60947-5-1No
protection class IP on the front according to IEC 60529IP20
touch protection on the front according to IEC 60529finger-safe, for vertical contact from the front
Communication/ Protocol
product function bus communicationNo
Certificates/ approvals

Downloads and manuals

General Product Approval

CSA

CCC

Confirmation

UL

KC

EAC

EMCFunctional Safety/Safety of MachineryDeclaration of ConformityTest CertificatesMarine / Shipping

RCM

Type Examination Certificate

UK Declaration of Conformity

EC/EU-Declaration of Conformity

Type Test Certificates/Test Report

ABS (American Bureau of Shipping)

Marine / Shippingother

DNV / Det Norske Veritas

LR (Lloyds Register)

PRS / Polski Rejestr Statkow

RINA / Registro Italiano Navale

RMRS / Russian Maritime Register

Confirmation

RailwayDangerous Good

Vibration and Shock

Transport Information

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
Industry Mall (Online ordering system)
Cax online generator
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
Characteristic: Tripping characteristics, I²t, Let-through current
Further characteristics (e.g. electrical endurance, switching frequency)
last modified:3/18/2022
Date
5/14/2022
Subject to change without notice
© Copyright Siemens 2022


Additional data

Product
Article Number (Market Facing Number)3RT2344-1NF30
Product DescriptionContactor, AC-1, 110 A/400 V/40 °C, S3, 4-pole, 83-155 V AC/DC 1 NO+1 NC, screw terminal
Product familySIRIUS 3RT.3 contactors, 4-pole, up to 525 A
Product Lifecycle (PLM)PM300:Active Product
Price data
Region Specific PriceGroup / Headquarter Price Group41B / 41B
Surcharge for Raw MaterialsNone
Metal FactorLEO-----
Delivery information
Export Control RegulationsAL : N / ECCN : N
Standard lead time ex-works40 Day/Days
Net Weight (kg)2,170 Kg
Packaging Dimension146,00 x 137,00 x 175,00
Package size unit of measureMM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4047621027340
UPC804766937613
Commodity Code85364900
LKZ_FDB/ CatalogIDCC-IC10
Product Group5370
Group CodeR711
Country of originGermany
Compliance with the substance restrictions according to RoHS directiveSince: 01.09.2017
Product classC: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead monoxide (lead oxide)

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
VersionClassification
eClass627-37-10-03
eClass7.127-37-10-03
eClass827-37-10-03
eClass927-37-10-03
eClass9.127-37-10-03
ETIM5EC000066
ETIM6EC000066
ETIM7EC000066
ETIM8EC000066
IDEA44755
UNSPSC1539-12-15-29

ETIM data

ETIM: EC000066 - Power contactor, AC switching

Value Unit
Rated operation power NEMA (EF011960) -kW
Rated control supply voltage Us at AC 50HZ (EF003978) ['83.0', '155.0']V
Rated control supply voltage Us at AC 60HZ (EF003979) ['83.0', '155.0']V
Rated control supply voltage Us at DC (EF003980) ['83', '155']V
Voltage type for actuating (EF008242) AC/DC
Rated operation current Ie at AC-1, 400 V (EF001393) 110A
Rated operation current Ie at AC-3, 400 V (EF001392) -A
Rated operation current Ie at AC-4, 400 V (EF008495) -A
Modular version (EF001126) true
Number of auxiliary contacts as normally open contact (EF001376) 1
Number of auxiliary contacts as normally closed contact (EF001377) 1
Type of electrical connection of main circuit (EF006819) Screw connection
Number of normally closed contacts as main contact (EF001375) -
Number of main contacts as normally open contact (EF001374) 4
Rated operation power at AC-4, 400 V (EF008496) -kW
Rated operation power at AC-3, 400 V (EF001364) -kW



Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.