| Contactor assembly for star-delta (wye-delta) start AC-3, 75 kW/400 V 110 V AC, 50/60 Hz Size S3, screw terminal electrical and mechanical interlock 3 NO+3 NC | ||||||||||||||
| product brand name | SIRIUS | |||||||||||||
| product designation | Contactor assembly for star-delta (wye-delta) start | |||||||||||||
| product type designation | 3RA24 | |||||||||||||
| manufacturer's article number | ||||||||||||||
| ● 1 of the supplied contactor | 3RT2045-1AG20 | |||||||||||||
| ● 2 of the supplied contactor | 3RT2045-1AG20 | |||||||||||||
| ● 3 of the supplied contactor | 3RT2036-1AG20 | |||||||||||||
| ● of the supplied RS assembly kit | 3RA2943-2C | |||||||||||||
| ● of the supplied function module for wye-delta circuits | 3RA2816-0EW20 | |||||||||||||
| General technical data | ||||||||||||||
| size of contactor | S3 | |||||||||||||
| product extension auxiliary switch | No | |||||||||||||
| shock resistance at rectangular impulse | ||||||||||||||
| ● at AC | 6.7 g / 5 ms, 4.0 g / 10 ms | |||||||||||||
| shock resistance with sine pulse | ||||||||||||||
| ● at AC | 10.6 g / 5 ms, 6.3 g / 10 ms | |||||||||||||
| mechanical service life (switching cycles) | ||||||||||||||
| ● of contactor typical | 10 000 000 | |||||||||||||
| ● of the contactor with added auxiliary switch block typical | 10 000 000 | |||||||||||||
| reference code according to IEC 81346-2 | Q | |||||||||||||
| Substance Prohibitance (Date) | 03/01/2017 | |||||||||||||
| Ambient conditions | ||||||||||||||
| installation altitude at height above sea level maximum | 2 000 m | |||||||||||||
| ambient temperature | ||||||||||||||
| ● during operation | -25 ... +60 °C | |||||||||||||
| ● during storage | -55 ... +80 °C | |||||||||||||
| Main circuit | ||||||||||||||
| number of poles for main current circuit | 3 | |||||||||||||
| number of NO contacts for main contacts | 3 | |||||||||||||
| number of NC contacts for main contacts | 0 | |||||||||||||
| operating voltage at AC-3 rated value maximum | 690 V | |||||||||||||
| operational current at AC-3 | ||||||||||||||
| ● at 400 V rated value | 150 A | |||||||||||||
| operating power | ||||||||||||||
| ● at AC-3 | ||||||||||||||
| — at 400 V rated value | 75 kW | |||||||||||||
| — at 690 V rated value | 110 kW | |||||||||||||
| operating frequency at AC-3 maximum | 1 000 1/h | |||||||||||||
| Control circuit/ Control | ||||||||||||||
| type of voltage of the control supply voltage | AC | |||||||||||||
| control supply voltage 1 at AC | ||||||||||||||
| ● at 50 Hz rated value | 110 V | |||||||||||||
| ● at 60 Hz rated value | 110 V | |||||||||||||
| operating range factor control supply voltage rated value of magnet coil at AC | ||||||||||||||
| ● at 50 Hz | 0.8 ... 1.1 | |||||||||||||
| ● at 60 Hz | 0.85 ... 1.1 | |||||||||||||
| apparent pick-up power of magnet coil at AC | ||||||||||||||
| ● at 50 Hz | 698 VA | |||||||||||||
| ● at 60 Hz | 594 VA | |||||||||||||
| inductive power factor with closing power of the coil | ||||||||||||||
| ● at 50 Hz | 0.62 | |||||||||||||
| ● at 60 Hz | 0.55 | |||||||||||||
| apparent holding power of magnet coil at AC | ||||||||||||||
| ● at 50 Hz | 52 VA | |||||||||||||
| ● at 60 Hz | 38 VA | |||||||||||||
| inductive power factor with the holding power of the coil | ||||||||||||||
| ● at 50 Hz | 0.35 | |||||||||||||
| ● at 60 Hz | 0.41 | |||||||||||||
| Auxiliary circuit | ||||||||||||||
| number of NC contacts for auxiliary contacts | ||||||||||||||
| ● instantaneous contact | 3 | |||||||||||||
| number of NO contacts for auxiliary contacts | ||||||||||||||
| ● instantaneous contact | 3 | |||||||||||||
| UL/CSA ratings | ||||||||||||||
| contact rating of auxiliary contacts according to UL | A600 / Q600 | |||||||||||||
| Short-circuit protection | ||||||||||||||
| design of the fuse link | ||||||||||||||
| ● for short-circuit protection of the main circuit | ||||||||||||||
| — with type of coordination 1 required | gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 250 A | |||||||||||||
| — with type of assignment 2 required | gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 160 A | |||||||||||||
| ● for short-circuit protection of the auxiliary switch required | fuse gG: 10 A | |||||||||||||
| Installation/ mounting/ dimensions | ||||||||||||||
| mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface | |||||||||||||
| fastening method | screw and snap-on mounting onto 35 mm standard mounting rail | |||||||||||||
| height | 180 mm | |||||||||||||
| width | 220 mm | |||||||||||||
| depth | 244 mm | |||||||||||||
| required spacing | ||||||||||||||
| ● with side-by-side mounting | ||||||||||||||
| — forwards | 10 mm | |||||||||||||
| — backwards | 0 mm | |||||||||||||
| — upwards | 10 mm | |||||||||||||
| — downwards | 10 mm | |||||||||||||
| — at the side | 10 mm | |||||||||||||
| ● for grounded parts | ||||||||||||||
| — forwards | 10 mm | |||||||||||||
| — backwards | 0 mm | |||||||||||||
| — upwards | 10 mm | |||||||||||||
| — at the side | 10 mm | |||||||||||||
| — downwards | 10 mm | |||||||||||||
| ● for live parts | ||||||||||||||
| — forwards | 10 mm | |||||||||||||
| — backwards | 0 mm | |||||||||||||
| — upwards | 10 mm | |||||||||||||
| — downwards | 10 mm | |||||||||||||
| — at the side | 10 mm | |||||||||||||
| Connections/ Terminals | ||||||||||||||
| type of electrical connection | ||||||||||||||
| ● for main current circuit | screw-type terminals | |||||||||||||
| ● for auxiliary and control circuit | screw-type terminals | |||||||||||||
| ● at contactor for auxiliary contacts | Screw-type terminals | |||||||||||||
| ● of magnet coil | Screw-type terminals | |||||||||||||
| type of connectable conductor cross-sections | ||||||||||||||
| ● for main contacts | ||||||||||||||
| — solid or stranded | 2x (2.5 ... 16 mm²), 2x (10 ... 50 mm²), 1x (10 ... 70 mm²) | |||||||||||||
| — finely stranded with core end processing | 2x (2.5 ... 35 mm²), 1x (2.5 ... 50 mm²) | |||||||||||||
| — finely stranded without core end processing | 2x (10 ... 35 mm²), 1x (10 ... 50 mm²) | |||||||||||||
| ● at AWG cables for main contacts | 2x (10 ... 1/0), 1x (10 ... 2/0) | |||||||||||||
| type of connectable conductor cross-sections | ||||||||||||||
| ● for auxiliary contacts | ||||||||||||||
| — solid or stranded | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) | |||||||||||||
| — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) | |||||||||||||
| ● at AWG cables for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14) | |||||||||||||
| Safety related data | ||||||||||||||
| B10 value with high demand rate according to SN 31920 | 1 000 000 | |||||||||||||
| proportion of dangerous failures | ||||||||||||||
| ● with low demand rate according to SN 31920 | 40 % | |||||||||||||
| ● with high demand rate according to SN 31920 | 73 % | |||||||||||||
| failure rate [FIT] with low demand rate according to SN 31920 | 100 FIT | |||||||||||||
| protection class IP on the front according to IEC 60529 | IP20 | |||||||||||||
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front | |||||||||||||
| Communication/ Protocol | ||||||||||||||
| product function bus communication | No | |||||||||||||
| protocol is supported AS-Interface protocol | No | |||||||||||||
| product function control circuit interface with IO link | No | |||||||||||||
| Certificates/ approvals | ||||||||||||||
Downloads and manuals | ||||||||||||||
| ||||||||||||||
| Further information | ||||||||||||||
Information- and Downloadcenter (Catalogs, Brochures,…) | ||||||||||||||
Industry Mall (Online ordering system) | ||||||||||||||
Cax online generator | ||||||||||||||
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) | ||||||||||||||
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) | ||||||||||||||
Characteristic: Tripping characteristics, I²t, Let-through current | ||||||||||||||
Further characteristics (e.g. electrical endurance, switching frequency) | ||||||||||||||
| last modified: | 12/1/2021 | |||||||||||||
| Date 5/6/2022 | Subject to change without notice © Copyright Siemens 2022 | |||||||||||||
| Product | |||||||||||||||||||||||||||||||||||||
| Article Number (Market Facing Number) | 3RA2445-8XF32-1AG2 | ||||||||||||||||||||||||||||||||||||
| Product Description | Contactor assembly for star-delta (wye-delta) start AC-3, 75 kW/400 V 110 V AC, 50/60 Hz Size S3, screw terminal electrical and mechanical interlock 3 NO+3 NC | ||||||||||||||||||||||||||||||||||||
| Product family | SIRIUS 3RA24 contactor assemblies for star-delta (wye-delta) starting, up to 90 kW | ||||||||||||||||||||||||||||||||||||
| Product Lifecycle (PLM) | PM300:Active Product | ||||||||||||||||||||||||||||||||||||
| Price data | |||||||||||||||||||||||||||||||||||||
| Region Specific PriceGroup / Headquarter Price Group | 41B / 41B | ||||||||||||||||||||||||||||||||||||
| Surcharge for Raw Materials | None | ||||||||||||||||||||||||||||||||||||
| Metal Factor | LCO----- | ||||||||||||||||||||||||||||||||||||
| Delivery information | |||||||||||||||||||||||||||||||||||||
| Export Control Regulations | AL : N / ECCN : N | ||||||||||||||||||||||||||||||||||||
| Standard lead time ex-works | On request | ||||||||||||||||||||||||||||||||||||
| Net Weight (kg) | 5,440 Kg | ||||||||||||||||||||||||||||||||||||
| Packaging Dimension | 252,00 x 331,00 x 267,00 | ||||||||||||||||||||||||||||||||||||
| Package size unit of measure | MM | ||||||||||||||||||||||||||||||||||||
| Quantity Unit | 1 Piece | ||||||||||||||||||||||||||||||||||||
| Packaging Quantity | 1 | ||||||||||||||||||||||||||||||||||||
| Additional Product Information | |||||||||||||||||||||||||||||||||||||
| EAN | 4047621031163 | ||||||||||||||||||||||||||||||||||||
| UPC | 195125247499 | ||||||||||||||||||||||||||||||||||||
| Commodity Code | 85364900 | ||||||||||||||||||||||||||||||||||||
| LKZ_FDB/ CatalogID | CC-IC10 | ||||||||||||||||||||||||||||||||||||
| Product Group | 5339 | ||||||||||||||||||||||||||||||||||||
| Group Code | R711 | ||||||||||||||||||||||||||||||||||||
| Country of origin | Germany | ||||||||||||||||||||||||||||||||||||
| Compliance with the substance restrictions according to RoHS directive | Since: 01.03.2017 | ||||||||||||||||||||||||||||||||||||
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. | ||||||||||||||||||||||||||||||||||||
| WEEE (2012/19/EU) Take-Back Obligation | Yes | ||||||||||||||||||||||||||||||||||||
| REACH Art. 33 Duty to inform according to the current list of candidates |
| ||||||||||||||||||||||||||||||||||||
| Classifications | |||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||
| Value | Unit | |
|---|---|---|
| Degree of protection (NEMA) (EF011959) | - | |
| Function (EF000030) | Star-delta contactor | |
| Rated control supply voltage Us at AC 50HZ (EF003978) | ['-', '110'] | V |
| Rated control supply voltage Us at AC 60HZ (EF003979) | ['-', '110'] | V |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] | V |
| Voltage type for actuating (EF008242) | AC | |
| Rated operation current Ie at AC-3, 400 V (EF001392) | 150 | A |
| Rated operation power at AC-3, 400 V (EF001364) | 75.0 | kW |
| Type of electrical connection of main circuit (EF006819) | Screw connection | |
| Degree of protection (IP) (EF005474) | IP20 | |
| Rated operation power NEMA (EF011960) | - | kW |