View larger
3RA2435-8XE32-1NB3 SIEMENS Contactor assembly for star-delta (wye-delta) start I/O-Link AC-3, 37 kW/400 V, 2..
3RA2435-8XE32-1NB3
24358
SIEMENS
1 Pcs.
Automation > Combination of contactors
Contactors for switching motors
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Siemens 3RA2435-8XE32-1NB3 Contactor assembly for star-delta (wye-delta) start I/O-Link AC-3, 37 kW/400 V, 2.. manages reduced-voltage motor starting routines to limit mechanical and electrical stress on industrial power distribution grids. These coordinated sets feature integrated communication options for modern control architectures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- product designation: Contactor assembly for star-delta (wye-delta) start
- product type designation: 3RA24
- ● 1 of the supplied contactor: 3RT2035-1NB30-0CC0
- ● 2 of the supplied contactor: 3RT2035-1NB30
- ● 3 of the supplied contactor: 3RT2027-1BB40
- ● of the supplied RS assembly kit: 3RA2933-2C
- ● of the supplied function module for communication: 3RA2711-1CA00
- General technical data size of contactor: S2
- product extension auxiliary switch: No
- ● at DC: 7.7g / 5 ms, 4.5g / 10 ms
- ● at DC: 12g / 5 ms, 7g / 10 ms
- ● of contactor typical: 10 000 000
- ● of the contactor with added auxiliary switch block typical: 10 000 000
- reference code according to IEC 81346-2: Q
- Substance Prohibitance (Date): 10/01/2014
- ● during operation: -25 ... +60 °C
More info
▲Technical data
| Contactor assembly for star-delta (wye-delta) start I/O-Link AC-3, 37 kW/400 V, 20-33 V AC/DC 3-pole, Size S2 Screw terminal Electrical and mechanical interlock 3 NO + 3 NC integrated | ||||||||||||||||||||||||||
| product brand name | SIRIUS | |||||||||||||||||||||||||
| product designation | Contactor assembly for star-delta (wye-delta) start | |||||||||||||||||||||||||
| product type designation | 3RA24 | |||||||||||||||||||||||||
| manufacturer's article number | ||||||||||||||||||||||||||
| ● 1 of the supplied contactor | 3RT2035-1NB30-0CC0 | |||||||||||||||||||||||||
| ● 2 of the supplied contactor | 3RT2035-1NB30 | |||||||||||||||||||||||||
| ● 3 of the supplied contactor | 3RT2027-1BB40 | |||||||||||||||||||||||||
| ● of the supplied RS assembly kit | 3RA2933-2C | |||||||||||||||||||||||||
| ● of the supplied function module for communication | 3RA2711-1CA00 | |||||||||||||||||||||||||
| General technical data | ||||||||||||||||||||||||||
| size of contactor | S2 | |||||||||||||||||||||||||
| product extension auxiliary switch | No | |||||||||||||||||||||||||
| shock resistance at rectangular impulse | ||||||||||||||||||||||||||
| ● at DC | 7.7g / 5 ms, 4.5g / 10 ms | |||||||||||||||||||||||||
| shock resistance with sine pulse | ||||||||||||||||||||||||||
| ● at DC | 12g / 5 ms, 7g / 10 ms | |||||||||||||||||||||||||
| mechanical service life (switching cycles) | ||||||||||||||||||||||||||
| ● of contactor typical | 10 000 000 | |||||||||||||||||||||||||
| ● of the contactor with added auxiliary switch block typical | 10 000 000 | |||||||||||||||||||||||||
| reference code according to IEC 81346-2 | Q | |||||||||||||||||||||||||
| Substance Prohibitance (Date) | 10/01/2014 | |||||||||||||||||||||||||
| Ambient conditions | ||||||||||||||||||||||||||
| installation altitude at height above sea level maximum | 2 000 m | |||||||||||||||||||||||||
| ambient temperature | ||||||||||||||||||||||||||
| ● during operation | -25 ... +60 °C | |||||||||||||||||||||||||
| ● during storage | -55 ... +80 °C | |||||||||||||||||||||||||
| Main circuit | ||||||||||||||||||||||||||
| number of poles for main current circuit | 3 | |||||||||||||||||||||||||
| number of NO contacts for main contacts | 3 | |||||||||||||||||||||||||
| number of NC contacts for main contacts | 0 | |||||||||||||||||||||||||
| operating voltage at AC-3 rated value maximum | 690 V | |||||||||||||||||||||||||
| operational current at AC-3 | ||||||||||||||||||||||||||
| ● at 400 V rated value | 80 A | |||||||||||||||||||||||||
| operating power | ||||||||||||||||||||||||||
| ● at AC-3 | ||||||||||||||||||||||||||
| — at 400 V rated value | 37 kW | |||||||||||||||||||||||||
| operating frequency at AC-3 maximum | 1 000 1/h | |||||||||||||||||||||||||
| Control circuit/ Control | ||||||||||||||||||||||||||
| type of voltage of the control supply voltage | AC/DC | |||||||||||||||||||||||||
| control supply voltage 1 at AC | ||||||||||||||||||||||||||
| ● at 50 Hz | 20 ... 33 V | |||||||||||||||||||||||||
| ● at 60 Hz | 20 ... 33 V | |||||||||||||||||||||||||
| control supply voltage 1 | ||||||||||||||||||||||||||
| ● at DC | 20 ... 33 V | |||||||||||||||||||||||||
| design of the surge suppressor | with varistor | |||||||||||||||||||||||||
| apparent pick-up power of magnet coil at AC | ||||||||||||||||||||||||||
| ● at 50 Hz | 82 VA | |||||||||||||||||||||||||
| ● at 60 Hz | 82 VA | |||||||||||||||||||||||||
| inductive power factor with closing power of the coil | ||||||||||||||||||||||||||
| ● at 50 Hz | 0.64 | |||||||||||||||||||||||||
| ● at 60 Hz | 0.5 | |||||||||||||||||||||||||
| apparent holding power of magnet coil at AC | ||||||||||||||||||||||||||
| ● at 50 Hz | 6 VA | |||||||||||||||||||||||||
| ● at 60 Hz | 6 VA | |||||||||||||||||||||||||
| inductive power factor with the holding power of the coil | ||||||||||||||||||||||||||
| ● at 50 Hz | 0.36 | |||||||||||||||||||||||||
| ● at 60 Hz | 0.39 | |||||||||||||||||||||||||
| closing power of magnet coil at DC | 28 W | |||||||||||||||||||||||||
| holding power of magnet coil at DC | 4 W | |||||||||||||||||||||||||
| Auxiliary circuit | ||||||||||||||||||||||||||
| number of NC contacts for auxiliary contacts | ||||||||||||||||||||||||||
| ● instantaneous contact | 3 | |||||||||||||||||||||||||
| number of NO contacts for auxiliary contacts | ||||||||||||||||||||||||||
| ● instantaneous contact | 3 | |||||||||||||||||||||||||
| contact reliability of auxiliary contacts | < 1 error per 100 million operating cycles | |||||||||||||||||||||||||
| UL/CSA ratings | ||||||||||||||||||||||||||
| contact rating of auxiliary contacts according to UL | A600 / Q600 | |||||||||||||||||||||||||
| Short-circuit protection | ||||||||||||||||||||||||||
| design of the fuse link | ||||||||||||||||||||||||||
| ● for short-circuit protection of the main circuit | ||||||||||||||||||||||||||
| — with type of coordination 1 required | gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 160 A | |||||||||||||||||||||||||
| — with type of assignment 2 required | gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 80 A | |||||||||||||||||||||||||
| ● for short-circuit protection of the auxiliary switch required | fuse gG: 10 A | |||||||||||||||||||||||||
| Installation/ mounting/ dimensions | ||||||||||||||||||||||||||
| mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface | |||||||||||||||||||||||||
| fastening method | screw fixing | |||||||||||||||||||||||||
| height | 142 mm | |||||||||||||||||||||||||
| width | 177.5 mm | |||||||||||||||||||||||||
| depth | 223 mm | |||||||||||||||||||||||||
| required spacing | ||||||||||||||||||||||||||
| ● with side-by-side mounting | ||||||||||||||||||||||||||
| — forwards | 10 mm | |||||||||||||||||||||||||
| — backwards | 0 mm | |||||||||||||||||||||||||
| — upwards | 10 mm | |||||||||||||||||||||||||
| — downwards | 10 mm | |||||||||||||||||||||||||
| — at the side | 10 mm | |||||||||||||||||||||||||
| ● for grounded parts | ||||||||||||||||||||||||||
| — forwards | 10 mm | |||||||||||||||||||||||||
| — backwards | 0 mm | |||||||||||||||||||||||||
| — upwards | 10 mm | |||||||||||||||||||||||||
| — at the side | 10 mm | |||||||||||||||||||||||||
| — downwards | 10 mm | |||||||||||||||||||||||||
| ● for live parts | ||||||||||||||||||||||||||
| — forwards | 10 mm | |||||||||||||||||||||||||
| — backwards | 0 mm | |||||||||||||||||||||||||
| — upwards | 10 mm | |||||||||||||||||||||||||
| — downwards | 10 mm | |||||||||||||||||||||||||
| — at the side | 10 mm | |||||||||||||||||||||||||
| Connections/ Terminals | ||||||||||||||||||||||||||
| type of electrical connection | ||||||||||||||||||||||||||
| ● for main current circuit | screw-type terminals | |||||||||||||||||||||||||
| ● for auxiliary and control circuit | screw-type terminals | |||||||||||||||||||||||||
| ● at contactor for auxiliary contacts | Screw-type terminals | |||||||||||||||||||||||||
| ● of magnet coil | Screw-type terminals | |||||||||||||||||||||||||
| type of connectable conductor cross-sections | ||||||||||||||||||||||||||
| ● for main contacts | ||||||||||||||||||||||||||
| — solid | 2x (1 ... 35 mm²), 1x (1 ... 50 mm²) | |||||||||||||||||||||||||
| — solid or stranded | 2x (1 ... 35 mm²), 1x (1 ... 50 mm²) | |||||||||||||||||||||||||
| — finely stranded with core end processing | 2x (1 ... 25 mm²), 1x (1 ... 35 mm²) | |||||||||||||||||||||||||
| ● at AWG cables for main contacts | 2x (18 ... 2), 1x (18 ... 1) | |||||||||||||||||||||||||
| type of connectable conductor cross-sections | ||||||||||||||||||||||||||
| ● for auxiliary contacts | ||||||||||||||||||||||||||
| — solid or stranded | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) | |||||||||||||||||||||||||
| — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²) | |||||||||||||||||||||||||
| ● at AWG cables for auxiliary contacts | 2x (20 ... 16), 2x (18 ... 14) | |||||||||||||||||||||||||
| Safety related data | ||||||||||||||||||||||||||
| B10 value with high demand rate according to SN 31920 | 1 000 000 | |||||||||||||||||||||||||
| proportion of dangerous failures | ||||||||||||||||||||||||||
| ● with low demand rate according to SN 31920 | 40 % | |||||||||||||||||||||||||
| ● with high demand rate according to SN 31920 | 73 % | |||||||||||||||||||||||||
| failure rate [FIT] with low demand rate according to SN 31920 | 100 FIT | |||||||||||||||||||||||||
| protection class IP on the front according to IEC 60529 | IP20 | |||||||||||||||||||||||||
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front | |||||||||||||||||||||||||
| Communication/ Protocol | ||||||||||||||||||||||||||
| product function bus communication | No | |||||||||||||||||||||||||
| protocol is supported AS-Interface protocol | No | |||||||||||||||||||||||||
| product function control circuit interface with IO link | Yes | |||||||||||||||||||||||||
| Certificates/ approvals | ||||||||||||||||||||||||||
Downloads and manuals | ||||||||||||||||||||||||||
| ||||||||||||||||||||||||||
| Further information | ||||||||||||||||||||||||||
Information- and Downloadcenter (Catalogs, Brochures,…) | ||||||||||||||||||||||||||
Industry Mall (Online ordering system) | ||||||||||||||||||||||||||
Cax online generator | ||||||||||||||||||||||||||
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) | ||||||||||||||||||||||||||
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) | ||||||||||||||||||||||||||
Characteristic: Tripping characteristics, I²t, Let-through current | ||||||||||||||||||||||||||
Further characteristics (e.g. electrical endurance, switching frequency) | ||||||||||||||||||||||||||
| last modified: | 12/1/2021 | |||||||||||||||||||||||||
| Date 5/12/2022 | Subject to change without notice © Copyright Siemens 2022 | |||||||||||||||||||||||||
Additional data
| Product | |||||||||||||||||||||||||||||||||||||
| Article Number (Market Facing Number) | 3RA2435-8XE32-1NB3 | ||||||||||||||||||||||||||||||||||||
| Product Description | Contactor assembly for star-delta (wye-delta) start I/O-Link AC-3, 37 kW/400 V, 20-33 V AC/DC 3-pole, Size S2 Screw terminal Electrical and mechanical interlock 3 NO + 3 NC integrated | ||||||||||||||||||||||||||||||||||||
| Product family | SIRIUS 3RA24 contactor assemblies for star-delta (wye-delta) starting, up to 90 kW | ||||||||||||||||||||||||||||||||||||
| Product Lifecycle (PLM) | PM300:Active Product | ||||||||||||||||||||||||||||||||||||
| Price data | |||||||||||||||||||||||||||||||||||||
| Region Specific PriceGroup / Headquarter Price Group | 41B / 41B | ||||||||||||||||||||||||||||||||||||
| Surcharge for Raw Materials | None | ||||||||||||||||||||||||||||||||||||
| Metal Factor | LDO----- | ||||||||||||||||||||||||||||||||||||
| Delivery information | |||||||||||||||||||||||||||||||||||||
| Export Control Regulations | AL : N / ECCN : N | ||||||||||||||||||||||||||||||||||||
| Standard lead time ex-works | 20 Day/Days | ||||||||||||||||||||||||||||||||||||
| Net Weight (kg) | 2,450 Kg | ||||||||||||||||||||||||||||||||||||
| Packaging Dimension | 249,00 x 327,00 x 237,00 | ||||||||||||||||||||||||||||||||||||
| Package size unit of measure | MM | ||||||||||||||||||||||||||||||||||||
| Quantity Unit | 1 Piece | ||||||||||||||||||||||||||||||||||||
| Packaging Quantity | 1 | ||||||||||||||||||||||||||||||||||||
| Additional Product Information | |||||||||||||||||||||||||||||||||||||
| EAN | 4011209937994 | ||||||||||||||||||||||||||||||||||||
| UPC | 887621914295 | ||||||||||||||||||||||||||||||||||||
| Commodity Code | 85364900 | ||||||||||||||||||||||||||||||||||||
| LKZ_FDB/ CatalogID | CC-IC10 | ||||||||||||||||||||||||||||||||||||
| Product Group | 5339 | ||||||||||||||||||||||||||||||||||||
| Group Code | R711 | ||||||||||||||||||||||||||||||||||||
| Country of origin | Germany | ||||||||||||||||||||||||||||||||||||
| Compliance with the substance restrictions according to RoHS directive | Since: 01.10.2014 | ||||||||||||||||||||||||||||||||||||
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. | ||||||||||||||||||||||||||||||||||||
| WEEE (2012/19/EU) Take-Back Obligation | Yes | ||||||||||||||||||||||||||||||||||||
| REACH Art. 33 Duty to inform according to the current list of candidates |
| ||||||||||||||||||||||||||||||||||||
| Classifications | |||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||
ETIM data
ETIM: EC000010 - Combination of contactors
| Value | Unit | |
|---|---|---|
| Degree of protection (NEMA) (EF011959) | - | |
| Function (EF000030) | Star-delta contactor | |
| Rated control supply voltage Us at AC 50HZ (EF003978) | ['20', '33'] | V |
| Rated control supply voltage Us at AC 60HZ (EF003979) | ['20', '33'] | V |
| Rated control supply voltage Us at DC (EF003980) | ['20', '33'] | V |
| Voltage type for actuating (EF008242) | AC/DC | |
| Rated operation current Ie at AC-3, 400 V (EF001392) | 80 | A |
| Rated operation power at AC-3, 400 V (EF001364) | 37.0 | kW |
| Type of electrical connection of main circuit (EF006819) | Screw connection | |
| Degree of protection (IP) (EF005474) | IP20 | |
| Rated operation power NEMA (EF011960) | - | kW |