View larger
3RA2210-1HA16-2BB4 SIEMENS FUSELESS LOAD FEEDER REVERSING OPERATION, AC 400V, S00 5.5. . .8A, 4KW, DC 24V SC..
3RA2210-1HA16-2BB4
22101
SIEMENS
1 Pcs.
Automation > Motor starter/Motor starter combination
Contactors for switching motors
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
3RA2210-1HA16-2BB4 SIEMENS FUSELESS LOAD FEEDER REVERSING OPERATION, AC 400V, S00 5.5. . .8A, 4KW, DC 24V SC.. functions as a complete fuseless reversing load feeder designed to manage bi-directional motor operation. This modular combination unit incorporates necessary switching and protective components to safely reverse drive rotations in manufacturing equipment. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- product designation: Reversing starter
- design of the product: for standard rail or screw mounting
- product type designation: 3RA22
- ● of the supplied contactor: 3RT2016-1BB42
- ● of the supplied circuit-breakers: 3RV2011-1HA10
- ● of the supplied link module: 3RA1921-1DA00
- General technical data size of the circuit-breaker: S00
- size of load feeder: S00
- surge voltage resistance rated value: 6 kV
- shock resistance according to IEC 60068-2-27: 6g / 11 ms
- type of assignment: 1
- type of protection according to ATEX directive 2014/34/EU: Ex II (2) GD
- Substance Prohibitance (Date): 10/01/2009
- ● during operation: -20 ... +60 °C
- ● during storage: -50 ... +80 °C
- ● during transport: -50 ... +80 °C
More info
▲Technical data
| FUSELESS LOAD FEEDER REVERSING OPERATION, AC 400V, S00 5.5. . .8A, 4KW, DC 24V SCREW TERMINAL FOR RAIL MOUNTING, TYPE OF ASSIGNMENT 1,IQ = 150KA 1NC (CONTACTOR) | ||||||||||||||||||||||||||||||||||||||||||||||||||
| product brand name | SIRIUS | |||||||||||||||||||||||||||||||||||||||||||||||||
| product designation | Reversing starter | |||||||||||||||||||||||||||||||||||||||||||||||||
| design of the product | for standard rail or screw mounting | |||||||||||||||||||||||||||||||||||||||||||||||||
| product type designation | 3RA22 | |||||||||||||||||||||||||||||||||||||||||||||||||
| manufacturer's article number | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● of the supplied contactor | 3RT2016-1BB42 | |||||||||||||||||||||||||||||||||||||||||||||||||
| ● of the supplied circuit-breakers | 3RV2011-1HA10 | |||||||||||||||||||||||||||||||||||||||||||||||||
| ● of the supplied link module | 3RA1921-1DA00 | |||||||||||||||||||||||||||||||||||||||||||||||||
| General technical data | ||||||||||||||||||||||||||||||||||||||||||||||||||
| size of the circuit-breaker | S00 | |||||||||||||||||||||||||||||||||||||||||||||||||
| size of load feeder | S00 | |||||||||||||||||||||||||||||||||||||||||||||||||
| insulation voltage with degree of pollution 3 at AC rated value | 690 V | |||||||||||||||||||||||||||||||||||||||||||||||||
| surge voltage resistance rated value | 6 kV | |||||||||||||||||||||||||||||||||||||||||||||||||
| degree of protection NEMA rating | other | |||||||||||||||||||||||||||||||||||||||||||||||||
| shock resistance according to IEC 60068-2-27 | 6g / 11 ms | |||||||||||||||||||||||||||||||||||||||||||||||||
| mechanical service life (switching cycles) of contactor typical | 30 000 000 | |||||||||||||||||||||||||||||||||||||||||||||||||
| type of assignment | 1 | |||||||||||||||||||||||||||||||||||||||||||||||||
| type of protection according to ATEX directive 2014/34/EU | Ex II (2) GD | |||||||||||||||||||||||||||||||||||||||||||||||||
| certificate of suitability according to ATEX directive 2014/34/EU | DMT 02 ATEX F 001 | |||||||||||||||||||||||||||||||||||||||||||||||||
| Substance Prohibitance (Date) | 10/01/2009 | |||||||||||||||||||||||||||||||||||||||||||||||||
| Ambient conditions | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ambient temperature | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● during operation | -20 ... +60 °C | |||||||||||||||||||||||||||||||||||||||||||||||||
| ● during storage | -50 ... +80 °C | |||||||||||||||||||||||||||||||||||||||||||||||||
| ● during transport | -50 ... +80 °C | |||||||||||||||||||||||||||||||||||||||||||||||||
| temperature compensation | -20 ... +60 °C | |||||||||||||||||||||||||||||||||||||||||||||||||
| relative humidity during operation | 10 ... 95 % | |||||||||||||||||||||||||||||||||||||||||||||||||
| Main circuit | ||||||||||||||||||||||||||||||||||||||||||||||||||
| number of poles for main current circuit | 3 | |||||||||||||||||||||||||||||||||||||||||||||||||
| design of the switching contact | electromechanical | |||||||||||||||||||||||||||||||||||||||||||||||||
| adjustable current response value current of the current-dependent overload release | 5.5 ... 8 A | |||||||||||||||||||||||||||||||||||||||||||||||||
| operating voltage | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● rated value | 690 V | |||||||||||||||||||||||||||||||||||||||||||||||||
| ● at AC-3 rated value maximum | 690 V | |||||||||||||||||||||||||||||||||||||||||||||||||
| operating frequency rated value | 50 ... 60 Hz | |||||||||||||||||||||||||||||||||||||||||||||||||
| operational current at AC-3 at 400 V rated value | 6.5 A | |||||||||||||||||||||||||||||||||||||||||||||||||
| operating power at AC-3 | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● at 400 V rated value | 3 000 W | |||||||||||||||||||||||||||||||||||||||||||||||||
| Control circuit/ Control | ||||||||||||||||||||||||||||||||||||||||||||||||||
| type of voltage of the control supply voltage | DC | |||||||||||||||||||||||||||||||||||||||||||||||||
| control supply voltage at DC | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● rated value | 24 V | |||||||||||||||||||||||||||||||||||||||||||||||||
| ● rated value | 24 ... 24 V | |||||||||||||||||||||||||||||||||||||||||||||||||
| holding power of magnet coil at DC | 4 W | |||||||||||||||||||||||||||||||||||||||||||||||||
| Auxiliary circuit | ||||||||||||||||||||||||||||||||||||||||||||||||||
| product extension auxiliary switch | Yes | |||||||||||||||||||||||||||||||||||||||||||||||||
| Protective and monitoring functions | ||||||||||||||||||||||||||||||||||||||||||||||||||
| trip class | CLASS 10 | |||||||||||||||||||||||||||||||||||||||||||||||||
| design of the overload release | thermal (bimetallic) | |||||||||||||||||||||||||||||||||||||||||||||||||
| UL/CSA ratings | ||||||||||||||||||||||||||||||||||||||||||||||||||
| full-load current (FLA) for 3-phase AC motor | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● at 480 V rated value | 8 A | |||||||||||||||||||||||||||||||||||||||||||||||||
| yielded mechanical performance [hp] | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● for 3-phase AC motor | ||||||||||||||||||||||||||||||||||||||||||||||||||
| — at 220/230 V rated value | 2 hp | |||||||||||||||||||||||||||||||||||||||||||||||||
| — at 460/480 V rated value | 5 hp | |||||||||||||||||||||||||||||||||||||||||||||||||
| — at 575/600 V rated value | 5 hp | |||||||||||||||||||||||||||||||||||||||||||||||||
| Short-circuit protection | ||||||||||||||||||||||||||||||||||||||||||||||||||
| product function short circuit protection | Yes | |||||||||||||||||||||||||||||||||||||||||||||||||
| design of the short-circuit trip | magnetic | |||||||||||||||||||||||||||||||||||||||||||||||||
| conditional short-circuit current (Iq) | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● at 400 V according to IEC 60947-4-1 rated value | 150 000 A | |||||||||||||||||||||||||||||||||||||||||||||||||
| Installation/ mounting/ dimensions | ||||||||||||||||||||||||||||||||||||||||||||||||||
| mounting position | vertical | |||||||||||||||||||||||||||||||||||||||||||||||||
| fastening method | screw and snap-on mounting onto 35 mm standard mounting rail | |||||||||||||||||||||||||||||||||||||||||||||||||
| height | 170 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| width | 90 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| depth | 97 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| required spacing | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● for grounded parts | ||||||||||||||||||||||||||||||||||||||||||||||||||
| — forwards | 32 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| — backwards | 0 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| — upwards | 50 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| — at the side | 10 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| — downwards | 10 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| ● for live parts | ||||||||||||||||||||||||||||||||||||||||||||||||||
| — forwards | 32 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| — backwards | 0 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| — upwards | 50 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| — downwards | 10 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| — at the side | 10 mm | |||||||||||||||||||||||||||||||||||||||||||||||||
| Connections/ Terminals | ||||||||||||||||||||||||||||||||||||||||||||||||||
| type of electrical connection | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● for main current circuit | screw-type terminals | |||||||||||||||||||||||||||||||||||||||||||||||||
| ● for auxiliary and control circuit | screw-type terminals | |||||||||||||||||||||||||||||||||||||||||||||||||
| type of connectable conductor cross-sections | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● for main contacts | ||||||||||||||||||||||||||||||||||||||||||||||||||
| — stranded | 0.5 ... 4 mm², 2x (0.75 ... 2.5 mm²) | |||||||||||||||||||||||||||||||||||||||||||||||||
| ● at AWG cables for main contacts | 2x (20 ... 16), only for contactor 2x (18 ... 14), 2x 12 | |||||||||||||||||||||||||||||||||||||||||||||||||
| connectable conductor cross-section for main contacts finely stranded with core end processing | 0.5 ... 2.5 mm² | |||||||||||||||||||||||||||||||||||||||||||||||||
| Safety related data | ||||||||||||||||||||||||||||||||||||||||||||||||||
| B10 value with high demand rate according to SN 31920 | 1 000 000 | |||||||||||||||||||||||||||||||||||||||||||||||||
| proportion of dangerous failures | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● with high demand rate according to SN 31920 | 73 % | |||||||||||||||||||||||||||||||||||||||||||||||||
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front | |||||||||||||||||||||||||||||||||||||||||||||||||
| Communication/ Protocol | ||||||||||||||||||||||||||||||||||||||||||||||||||
| protocol is supported | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ● PROFINET IO protocol | No | |||||||||||||||||||||||||||||||||||||||||||||||||
| ● PROFIsafe protocol | No | |||||||||||||||||||||||||||||||||||||||||||||||||
| protocol is supported AS-Interface protocol | No | |||||||||||||||||||||||||||||||||||||||||||||||||
| Certificates/ approvals | ||||||||||||||||||||||||||||||||||||||||||||||||||
Downloads and manuals | ||||||||||||||||||||||||||||||||||||||||||||||||||
| ||||||||||||||||||||||||||||||||||||||||||||||||||
| Further information | ||||||||||||||||||||||||||||||||||||||||||||||||||
Information- and Downloadcenter (Catalogs, Brochures,…) | ||||||||||||||||||||||||||||||||||||||||||||||||||
Industry Mall (Online ordering system) | ||||||||||||||||||||||||||||||||||||||||||||||||||
Cax online generator | ||||||||||||||||||||||||||||||||||||||||||||||||||
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) | ||||||||||||||||||||||||||||||||||||||||||||||||||
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) | ||||||||||||||||||||||||||||||||||||||||||||||||||
Characteristic: Tripping characteristics, I²t, Let-through current | ||||||||||||||||||||||||||||||||||||||||||||||||||
Further characteristics (e.g. electrical endurance, switching frequency) | ||||||||||||||||||||||||||||||||||||||||||||||||||
| last modified: | 2/16/2022 | |||||||||||||||||||||||||||||||||||||||||||||||||
| Date 5/5/2022 | Subject to change without notice © Copyright Siemens 2022 | |||||||||||||||||||||||||||||||||||||||||||||||||
Additional data
| Product | ||||||||||||||||||||||||||||||||||||||||
| Article Number (Market Facing Number) | 3RA2210-1HA16-2BB4 | |||||||||||||||||||||||||||||||||||||||
| Product Description | FUSELESS LOAD FEEDER REVERSING OPERATION, AC 400V, S00 5.5. . .8A, 4KW, DC 24V SCREW TERMINAL FOR RAIL MOUNTING, TYPE OF ASSIGNMENT 1,IQ = 150KA 1NC (CONTACTOR) | |||||||||||||||||||||||||||||||||||||||
| Product family | SIRIUS 3RA2 load feeders | |||||||||||||||||||||||||||||||||||||||
| Product Lifecycle (PLM) | PM300:Active Product | |||||||||||||||||||||||||||||||||||||||
| Price data | ||||||||||||||||||||||||||||||||||||||||
| Region Specific PriceGroup / Headquarter Price Group | 41D / 41D | |||||||||||||||||||||||||||||||||||||||
| Surcharge for Raw Materials | None | |||||||||||||||||||||||||||||||||||||||
| Metal Factor | LCO----- | |||||||||||||||||||||||||||||||||||||||
| Delivery information | ||||||||||||||||||||||||||||||||||||||||
| Export Control Regulations | AL : N / ECCN : EAR99 | |||||||||||||||||||||||||||||||||||||||
| Standard lead time ex-works | On request | |||||||||||||||||||||||||||||||||||||||
| Net Weight (kg) | 0,934 Kg | |||||||||||||||||||||||||||||||||||||||
| Packaging Dimension | 98,00 x 181,00 x 116,00 | |||||||||||||||||||||||||||||||||||||||
| Package size unit of measure | MM | |||||||||||||||||||||||||||||||||||||||
| Quantity Unit | 1 Piece | |||||||||||||||||||||||||||||||||||||||
| Packaging Quantity | 1 | |||||||||||||||||||||||||||||||||||||||
| Additional Product Information | ||||||||||||||||||||||||||||||||||||||||
| EAN | Not available | |||||||||||||||||||||||||||||||||||||||
| UPC | 040892781120 | |||||||||||||||||||||||||||||||||||||||
| Commodity Code | 8536490065 | |||||||||||||||||||||||||||||||||||||||
| LKZ_FDB/ CatalogID | CC-IC10 | |||||||||||||||||||||||||||||||||||||||
| Product Group | 5348 | |||||||||||||||||||||||||||||||||||||||
| Group Code | R711 | |||||||||||||||||||||||||||||||||||||||
| Country of origin | United States of America | |||||||||||||||||||||||||||||||||||||||
| Compliance with the substance restrictions according to RoHS directive | Since: 01.10.2009 | |||||||||||||||||||||||||||||||||||||||
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. | |||||||||||||||||||||||||||||||||||||||
| WEEE (2012/19/EU) Take-Back Obligation | Yes | |||||||||||||||||||||||||||||||||||||||
| REACH Art. 33 Duty to inform according to the current list of candidates |
| |||||||||||||||||||||||||||||||||||||||
| Classifications | ||||||||||||||||||||||||||||||||||||||||
| ||||||||||||||||||||||||||||||||||||||||
ETIM data
ETIM: EC001037 - Motor starter/Motor starter combination
| Value | Unit | |
|---|---|---|
| Supporting protocol for ASI (EF003051) | - | |
| Supporting protocol for PROFIBUS (EF003052) | - | |
| Supporting protocol for AS-Interface Safety at Work (EF007519) | - | |
| Rated conditional short-circuit current, type 1, 480 Y/277 V (EF009607) | - | A |
| Supporting protocol for CAN (EF003053) | - | |
| Suitable for emergency stop (EF001433) | - | |
| Rated conditional short-circuit current, type 2, 230 V (EF009606) | - | A |
| Rated operation power at AC-3, 230 V, 3-phase (EF009599) | - | kW |
| Supporting protocol for TCP/IP (EF003050) | - | |
| Temperature compensated overload protection (EF009604) | - | |
| Rated power, 460 V, 60 Hz, 3-phase (EF009600) | - | kW |
| Supporting protocol for PROFINET CBA (EF007524) | - | |
| Supporting protocol for DeviceNet Safety (EF007520) | - | |
| Rail mounting possible (EF003972) | - | |
| Supporting protocol for SUCONET (EF003060) | - | |
| Supporting protocol for DeviceNet (EF003059) | - | |
| Degree of protection (NEMA) (EF011959) | - | |
| Supporting protocol for INTERBUS-Safety (EF006662) | - | |
| Supporting protocol for Data-Highway (EF003058) | - | |
| Supporting protocol for INTERBUS (EF003054) | - | |
| Rated power, 575 V, 60 Hz, 3-phase (EF009601) | - | kW |
| Supporting protocol for PROFINET IO (EF007525) | - | |
| Type of electrical connection for auxiliary- and control current circuit (EF006979) | - | |
| Supporting protocol for SERCOS (EF006657) | - | |
| Supporting protocol for Foundation Fieldbus (EF007522) | - | |
| Supporting protocol for EtherNet/IP (EF007521) | - | |
| External reset possible (EF003426) | - | |
| Supporting protocol for PROFIsafe (EF007526) | - | |
| Supporting protocol for SafetyBUS p (EF007527) | - | |
| Rated conditional short-circuit current, type 2, 400 V (EF009605) | - | A |
| Rated conditional short-circuit current, type 1, 600 Y/347 V (EF009608) | - | A |
| Supporting protocol for Modbus (EF003057) | - | |
| Number of command positions (EF001372) | - | |
| Supporting protocol for LON (EF003017) | - | |
| Supporting protocol for other bus systems (EF003062) | - | |
| Ambient temperature, upper operating limit (EF009603) | - | °C |
| Type of motor starter (EF009598) | Other | |
| With short-circuit release (EF006691) | true | |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] | V |
| Voltage type for actuating (EF008242) | DC / DC | |
| Rated operation power at AC-3, 400 V (EF001364) | 3.0 | kW |
| Rated operation current Ie (EF001443) | 6.5 | A |
| Rated operation current at AC-3, 400 V (EF009602) | 6.5 | A |
| Overload release current setting (EF002336) | ['5.5', '8'] | A |
| Number of auxiliary contacts as normally open contact (EF001376) | - | |
| Number of auxiliary contacts as normally closed contact (EF001377) | - | |
| Release class (EF006668) | CLASS 10 | |
| Type of electrical connection of main circuit (EF006819) | Screw connection | |
| With transformer (EF000278) | false | |
| Coordination class according to IEC 60947-4-3 (EF012390) | Class 1 | |
| Number of indicator lights (EF001965) | 0 | |
| With fuse (EF006693) | false | |
| Degree of protection (IP) (EF005474) | IP20 | |
| Width (EF000008) | 90.0 | mm |
| Height (EF000040) | 170.0 | mm |
| Depth (EF000049) | 97.0 | mm |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - | V |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - | V |