LOAD FEEDER FUSE LINE DIRECT START, 400 V AC, SIZE S2 28...40 A, 230 V AC, 50 HZ, SCREW CONNECTION 1NO+1NC (CIRCUIT-BREAKER) FOR SCREW AND SNAP FIXING ASSIGN. TYPE 2, IQ = 50 KA (COMPLY ALSO ASSIGN. TYPE 1)

Automation > Motor starter/Motor starter combination
Contactors for switching motors

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

product brand name SIRIUS
Product designation non-fused load feeder
Design of the product direct starter
Manufacturer's article number
● of the supplied contactor 3RT1035-1AL20
● of the supplied circuit-breakers 3RV1031-4FA10
● of the supplied link module 3RA1931-1AA00
● of the supplied standard mounting rail adapter 3RA1932-1AA00
General technical data:
Size of load feeder S2
Insulation voltage
● rated value 690 V
Degree of pollution 3
Surge voltage resistance rated value 6 kV
Protection class IP
● on the front IP20
Shock resistance 8g
Mechanical service life (switching cycles)
● of contactor typical 10 000 000
Type of assignment 2
Equipment marking
● acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 Q
● acc. to DIN EN 61346-2 Q
● acc. to DIN EN 81346-2 Q
Ambient conditions:
Installation altitude at height above sea level maximum 2 000 m
Ambient temperature
● during operation -20 ... +70 °C
● during storage -55 ... +80 °C
Main circuit:
Number of poles for main current circuit 3
Design of the switching contact electromechanical
Adjustable pick-up value current of the current-dependent overload release 28 ... 40 A
Type of the motor protection bimetal
Operating voltage
● at AC-3 rated value maximum 400 V
Operating current
● at AC-3
— at 400 V rated value 35 A
Operating power
● at AC-3
— at 400 V rated value 18.5 kW
No-load switching frequency 15 1/s
Control circuit/ Control:
Type of voltage of the control supply voltage AC
Control supply voltage 1 at AC
● at 50 Hz rated value 230 V
● at 60 Hz rated value 230 V
Control supply voltage frequency 1 50 ... 60 Hz
Auxiliary circuit:
Product extension Auxiliary switch Yes
Number of NC contacts
● for auxiliary contacts 1
Number of NO contacts
● for auxiliary contacts 1
Number of CO contacts
● for auxiliary contacts 0
Protective and monitoring functions:
Maximum short-circuit current breaking capacity (Icu)
● at 400 V rated value 50 kA
Short-circuit protection
Product function
● Short circuit protection Yes
Design of short-circuit protection circuit-breakers
Installation/ mounting/ dimensions:
Mounting position with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
Mounting type snap-on mounting
Height 295 mm
Width 55 mm
Depth 173 mm
Required spacing
● with side-by-side mounting
— at the side 0 mm
● for grounded parts
— forwards 10 mm
— Backwards 0 mm
— upwards 50 mm
— at the side 10 mm
● for live parts
— forwards 10 mm
— Backwards 10 mm
— downwards 0 mm
— at the side 50 mm
Connections/Terminals:
Type of electrical connection
● for main current circuit screw-type terminals
Type of connectable conductor cross-sections
● for main contacts
— solid 0.7 ... 35 mm², 2x (0.75 ... 25 mm²)
— stranded 0.7 ... 35 mm², 2x (0.75 ... 25 mm²)
— finely stranded with core end processing 0.75 ... 25 mm², 2x (0.75 ... 16 mm²)
● at AWG conductors for main contacts 2x (30 ... 2)
Connectable conductor cross-section for main contacts
● single or multi-stranded 0.7 ... 35 mm²
● finely stranded with core end processing 0.75 ... 25 mm²
AWG number as coded connectable conductor cross section
● for main contacts 30 ... 2
Communication/ Protocol:
Product function Bus communication No
Protocol
● is supported PROFIBUS DP protocol No
● is supported PROFINET protocol No
Protocol is supported
● AS-interface protocol No
Inputs/ Outputs:
Number of digital inputs 0

Product Datasheet