View larger
3RA1130-4GB36-0BB4 SIEMENS Load feeder fuseless direct-on-line starting, 400 V AC 36...45 A, 24 V DC Size S2..
3RA1130-4GB36-0BB4
11304
SIEMENS
1 Pcs.
Automation > Motor starter/Motor starter combination
Contactors for switching motors
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Siemens 3RA1130-4GB36-0BB4 is a fuseless direct-on-line load feeder designed to start and safeguard heavy-duty industrial electric motors. Size S2 load feeders combine robust contactors and circuit breakers to deliver dependable switching performance in demanding operating environments.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Direct online starter (DOL)
- With short-circuit release (EF006691): true
- Rated control supply voltage Us at DC (EF003980): ['-', '-']
- Voltage type for actuating (EF008242): DC / #NO_DATA#
- Rated operation power at AC-3, 400 V (EF001364): 22.0
- Rated operation current Ie (EF001443): 41
- Rated operation current at AC-3, 400 V (EF009602): 41
- Overload release current setting (EF002336): ['36', '45']
- Type of electrical connection of main circuit (EF006819): Screw connection
- With transformer (EF000278): false
- Coordination class according to IEC 60947-4-3 (EF012390): Class 2
- Number of indicator lights (EF001965): 0
- With fuse (EF006693): false
- Degree of protection (IP) (EF005474): IP20
- Supporting protocol for ASI (EF003051): false
- Width (EF000008): 55.0
More info
▲ETIM: EC001037 - Motor starter/Motor starter combination
| Value | Unit | |
|---|---|---|
| Supporting protocol for DeviceNet Safety (EF007520) | - | |
| Rated power, 460 V, 60 Hz, 3-phase (EF009600) | - | kW |
| Degree of protection (NEMA) (EF011959) | - | |
| Rated operation power at AC-3, 230 V, 3-phase (EF009599) | - | kW |
| Supporting protocol for PROFINET IO (EF007525) | - | |
| Supporting protocol for other bus systems (EF003062) | - | |
| Supporting protocol for PROFIBUS (EF003052) | - | |
| Supporting protocol for TCP/IP (EF003050) | - | |
| Supporting protocol for PROFIsafe (EF007526) | - | |
| External reset possible (EF003426) | - | |
| Temperature compensated overload protection (EF009604) | - | |
| Rated conditional short-circuit current, type 2, 400 V (EF009605) | - | A |
| Rated power, 575 V, 60 Hz, 3-phase (EF009601) | - | kW |
| Supporting protocol for SafetyBUS p (EF007527) | - | |
| Supporting protocol for SERCOS (EF006657) | - | |
| Supporting protocol for DeviceNet (EF003059) | - | |
| Supporting protocol for CAN (EF003053) | - | |
| Supporting protocol for LON (EF003017) | - | |
| Supporting protocol for AS-Interface Safety at Work (EF007519) | - | |
| Rated conditional short-circuit current, type 2, 230 V (EF009606) | - | A |
| Supporting protocol for Foundation Fieldbus (EF007522) | - | |
| Release class (EF006668) | - | |
| Supporting protocol for INTERBUS-Safety (EF006662) | - | |
| Supporting protocol for SUCONET (EF003060) | - | |
| Suitable for emergency stop (EF001433) | - | |
| Number of command positions (EF001372) | - | |
| Rated conditional short-circuit current, type 1, 600 Y/347 V (EF009608) | - | A |
| Supporting protocol for INTERBUS (EF003054) | - | |
| Rail mounting possible (EF003972) | - | |
| Supporting protocol for PROFINET CBA (EF007524) | - | |
| Rated conditional short-circuit current, type 1, 480 Y/277 V (EF009607) | - | A |
| Supporting protocol for Modbus (EF003057) | - | |
| Supporting protocol for Data-Highway (EF003058) | - | |
| Type of electrical connection for auxiliary- and control current circuit (EF006979) | - | |
| Supporting protocol for EtherNet/IP (EF007521) | - | |
| Ambient temperature, upper operating limit (EF009603) | - | °C |
| Type of motor starter (EF009598) | Direct online starter (DOL) | |
| With short-circuit release (EF006691) | true | |
| Rated control supply voltage Us at DC (EF003980) | ['-', '-'] | V |
| Voltage type for actuating (EF008242) | DC / #NO_DATA# | |
| Rated operation power at AC-3, 400 V (EF001364) | 22.0 | kW |
| Rated operation current Ie (EF001443) | 41 | A |
| Rated operation current at AC-3, 400 V (EF009602) | 41 | A |
| Overload release current setting (EF002336) | ['36', '45'] | A |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 | |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 | |
| Type of electrical connection of main circuit (EF006819) | Screw connection | |
| With transformer (EF000278) | false | |
| Coordination class according to IEC 60947-4-3 (EF012390) | Class 2 | |
| Number of indicator lights (EF001965) | 0 | |
| With fuse (EF006693) | false | |
| Degree of protection (IP) (EF005474) | IP20 | |
| Supporting protocol for ASI (EF003051) | false | |
| Width (EF000008) | 55.0 | mm |
| Height (EF000040) | 295.0 | mm |
| Depth (EF000049) | 173.0 | mm |
| Rated control supply voltage Us at AC 50HZ (EF003978) | - | V |
| Rated control supply voltage Us at AC 60HZ (EF003979) | - | V |
| Load feeder fuseless direct-on-line starting, 400 V AC 36...45 A, 24 V DC Size S2 Screw terminal on adapter Screw and snap-on mounting Type of coordination 2, Iq = 50 kA (also fulfills type of coordination 1) !!! Phased-out product !!! Successor is SIRIUS 3RA2 Preferred successor type is >>3RA2130-4VA36-0NB3<< | ||||||||||||||||||||||||||
| product brand name | SIRIUS | |||||||||||||||||||||||||
| Product designation | non-fused load feeder | |||||||||||||||||||||||||
| Design of the product | direct starter | |||||||||||||||||||||||||
| Manufacturer's article number | ||||||||||||||||||||||||||
| ● of the supplied contactor | 3RT1036-1BB40 | |||||||||||||||||||||||||
| ● of the supplied circuit-breakers | 3RV1031-4GA10 | |||||||||||||||||||||||||
| ● of the supplied link module | 3RA1931-1BA00 | |||||||||||||||||||||||||
| ● of the supplied standard mounting rail adapter | 3RA1932-1AA00 | |||||||||||||||||||||||||
| General technical data | ||||||||||||||||||||||||||
| Size of load feeder | S2 | |||||||||||||||||||||||||
| Product extension | ||||||||||||||||||||||||||
| ● Auxiliary switch | Yes | |||||||||||||||||||||||||
| ● Insulation voltage rated value | 690 V | |||||||||||||||||||||||||
| Degree of pollution | 3 | |||||||||||||||||||||||||
| Surge voltage resistance rated value | 6 kV | |||||||||||||||||||||||||
| ● protection class IP on the front | IP20 | |||||||||||||||||||||||||
| Shock resistance | 8g | |||||||||||||||||||||||||
| Mechanical service life (switching cycles) | ||||||||||||||||||||||||||
| ● of contactor typical | 10 000 000 | |||||||||||||||||||||||||
| Type of assignment | 2 | |||||||||||||||||||||||||
| ● certificate of suitability | UL / CSA / CCC / GL / LRS / BV / DNV / PRS | |||||||||||||||||||||||||
| Reference code acc. to DIN EN 81346-2 | Q | |||||||||||||||||||||||||
| Ambient conditions | ||||||||||||||||||||||||||
| Installation altitude at height above sea level | ||||||||||||||||||||||||||
| ● maximum | 2 000 m | |||||||||||||||||||||||||
| Ambient temperature | ||||||||||||||||||||||||||
| ● during operation | -20 ... +70 °C | |||||||||||||||||||||||||
| ● during storage | -55 ... +80 °C | |||||||||||||||||||||||||
| Main circuit | ||||||||||||||||||||||||||
| Number of poles for main current circuit | 3 | |||||||||||||||||||||||||
| design of the switching contact | electromechanical | |||||||||||||||||||||||||
| adjustable pick-up value current of the current-dependent overload release | 36 ... 45 A | |||||||||||||||||||||||||
| Type of the motor protection | bimetal | |||||||||||||||||||||||||
| Operating voltage | ||||||||||||||||||||||||||
| ● at AC-3 rated value maximum | 400 V | |||||||||||||||||||||||||
| Operating current | ||||||||||||||||||||||||||
| ● at AC-3 | ||||||||||||||||||||||||||
| — at 400 V rated value | 41 A | |||||||||||||||||||||||||
| Operating power | ||||||||||||||||||||||||||
| ● at AC-3 | ||||||||||||||||||||||||||
| — at 400 V rated value | 22 kW | |||||||||||||||||||||||||
| No-load switching frequency | 15 1/s | |||||||||||||||||||||||||
| Control circuit/ Control | ||||||||||||||||||||||||||
| Type of voltage of the control supply voltage | DC | |||||||||||||||||||||||||
| Control supply voltage 1 | ||||||||||||||||||||||||||
| ● at DC rated value | 24 V | |||||||||||||||||||||||||
| Auxiliary circuit | ||||||||||||||||||||||||||
| Number of NC contacts for auxiliary contacts | 0 | |||||||||||||||||||||||||
| Number of NO contacts for auxiliary contacts | 0 | |||||||||||||||||||||||||
| Number of CO contacts | ||||||||||||||||||||||||||
| ● for auxiliary contacts | 0 | |||||||||||||||||||||||||
| Protective and monitoring functions | ||||||||||||||||||||||||||
| Maximum short-circuit current breaking capacity (Icu) | ||||||||||||||||||||||||||
| ● at 400 V rated value | 50 kA | |||||||||||||||||||||||||
| Short-circuit protection | ||||||||||||||||||||||||||
| product function short circuit protection | Yes | |||||||||||||||||||||||||
| Design of short-circuit protection | circuit-breakers | |||||||||||||||||||||||||
| Installation/ mounting/ dimensions | ||||||||||||||||||||||||||
| ● mounting position | with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back | |||||||||||||||||||||||||
| Mounting type | snap-on fastening on 35 mm standard rail | |||||||||||||||||||||||||
| Height | 295 mm | |||||||||||||||||||||||||
| Width | 55 mm | |||||||||||||||||||||||||
| Depth | 173 mm | |||||||||||||||||||||||||
| Required spacing | ||||||||||||||||||||||||||
| ● with side-by-side mounting | ||||||||||||||||||||||||||
| — at the side | 0 mm | |||||||||||||||||||||||||
| ● for grounded parts | ||||||||||||||||||||||||||
| — forwards | 10 mm | |||||||||||||||||||||||||
| — Backwards | 0 mm | |||||||||||||||||||||||||
| — upwards | 50 mm | |||||||||||||||||||||||||
| — at the side | 10 mm | |||||||||||||||||||||||||
| ● for live parts | ||||||||||||||||||||||||||
| — forwards | 10 mm | |||||||||||||||||||||||||
| — Backwards | 10 mm | |||||||||||||||||||||||||
| — downwards | 0 mm | |||||||||||||||||||||||||
| — at the side | 50 mm | |||||||||||||||||||||||||
| Connections/ Terminals | ||||||||||||||||||||||||||
| ● Type of electrical connection for main current circuit | screw-type terminals | |||||||||||||||||||||||||
| Type of connectable conductor cross-sections | ||||||||||||||||||||||||||
| ● for main contacts | ||||||||||||||||||||||||||
| — solid | 0.7 ... 35 mm², 2x (0.75 ... 25 mm²) | |||||||||||||||||||||||||
| — stranded | 0.7 ... 35 mm², 2x (0.75 ... 25 mm²) | |||||||||||||||||||||||||
| — finely stranded with core end processing | 0.75 ... 25 mm², 2x (0.75 ... 16 mm²) | |||||||||||||||||||||||||
| ● at AWG conductors for main contacts | 2x (30 ... 2) | |||||||||||||||||||||||||
| Connectable conductor cross-section for main contacts | ||||||||||||||||||||||||||
| ● single or multi-stranded | 0.7 ... 35 mm² | |||||||||||||||||||||||||
| ● stranded | 0.7 ... 35 mm² | |||||||||||||||||||||||||
| ● finely stranded with core end processing | 0.75 ... 25 mm² | |||||||||||||||||||||||||
| AWG number as coded connectable conductor cross section | ||||||||||||||||||||||||||
| ● for main contacts | 30 ... 2 | |||||||||||||||||||||||||
| Communication/ Protocol | ||||||||||||||||||||||||||
| ● protocol is supported PROFIBUS DP protocol | No | |||||||||||||||||||||||||
| ● protocol is supported PROFINET protocol | No | |||||||||||||||||||||||||
| product function bus communication | No | |||||||||||||||||||||||||
| Protocol is supported | ||||||||||||||||||||||||||
| ● AS-Interface protocol | No | |||||||||||||||||||||||||
| Inputs/ Outputs | ||||||||||||||||||||||||||
| ● number of digital inputs | 0 | |||||||||||||||||||||||||
| Certificates/ approvals | ||||||||||||||||||||||||||
| ||||||||||||||||||||||||||
| Further information | ||||||||||||||||||||||||||
Information- and Downloadcenter (Catalogs, Brochures,…) | ||||||||||||||||||||||||||
Industry Mall (Online ordering system) | ||||||||||||||||||||||||||
Cax online generator | ||||||||||||||||||||||||||
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) | ||||||||||||||||||||||||||
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) | ||||||||||||||||||||||||||
Characteristic: Tripping characteristics, I²t, Let-through current | ||||||||||||||||||||||||||
Further characteristics (e.g. electrical endurance, switching frequency) | ||||||||||||||||||||||||||
| last modified: | 08/13/2020 | |||||||||||||||||||||||||
| Product | ||
| Article Number (Market Facing Number) | 3RA1130-4GB36-0BB4 | |
| Product Description | Load feeder fuseless direct-on-line starting, 400 V AC 36...45 A, 24 V DC Size S2 Screw terminal on adapter Screw and snap-on mounting Type of coordination 2, Iq = 50 kA (also fulfills type of coordination 1) !!! Phased-out product !!! Successor is SIRIUS 3RA2 Preferred successor type is >>3RA2130-4VA36-0NB3<< | |
| Product family | Not available | |
| Product Lifecycle (PLM) | PM490:Start of final year of support | |
| PLM Effective Date | Product discontinued since: 01.04.2020 | |
| Notes | Product is no longer available Sucessor:SIRIUS Innovation 3RA2 If you need assistance please contact our local Siemens office | |
| Price data | ||
| Price Group | 41D | |
| Surcharge for Raw Materials | None | |
| Metal Factor | LCO----- | |
| Delivery information | ||
| Export Control Regulations | ECCN : N / AL : N | |
| Standard lead time ex-works | 20 Day/Days | |
| Net Weight (kg) | 2,688 Kg | |
| Product Dimensions (W x L x H) | Not available | |
| Packaging Dimension | 65,00 x 302,00 x 192,00 | |
| Package size unit of measure | MM | |
| Quantity Unit | 1 Piece | |
| Packaging Quantity | 1 | |
| Additional Product Information | ||
| EAN | 4011209313361 | |
| UPC | 754554681566 | |
| Commodity Code | 85364900 | |
| LKZ_FDB/ CatalogID | CC-IC10 | |
| Product Group | 3709 | |
| Group Code | R711 | |
| Country of origin | Germany | |
| Compliance with the substance restrictions according to RoHS directive | Since: 01.07.2006 | |
| Product class | C: products manufactured / produced to order, which cannot be reused or re-utilised or be returned against credit. | |
| WEEE (2012/19/EU) Take-Back Obligation | Yes | |
| REACH Art. 33 Duty to inform according to the current list of candidates |
| |
| Classifications | ||
| Not available | ||