View larger
Images are for illustrative purposes only. Please refer to data sheet for details
590.HEM4005 SCAME SWITCH DISCONNECTOR 40A 3P+N IP65
590.HEM4005
10000
SCAME
1 Pcs.
SWITCH DISCONNECTOR 40A 3P+N IP65
MANOEUVRING INT. 40A 3P+N IP66
40A 3P+N IP66 105x150x82mm Y1 IK10 EMERGENCY YELLOW/RED
Connectors > Switch disconnector
Switches - SCAME
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteMore info
▲Commercial Series
ISOLATORS-AL Series
Synthetical description
SWITCH DISCONNECTOR
Construction type
Enclosed
Mounting version
SURFACE MOUNTING
Material
DIE-CAST ALUMINIUM
Protection degree IP
IP66
Installation temperature
-25°C/+60°C
Type
EMERGENCY
Colour
YELLOW/RED
Rated current
40A
Poles
3P+N
Switch size
Y1
Rated voltage
690V
Dimensions
105x150x82mm
Protection degree IK
IK10
Rated insulation voltage (Ui)
690VAC
Rated impulse voltage (Uimp)
4kV
Thermal current (Ithe)
40A
Current (Ie) in AC21A (415V)
40A
Current (Ie) in AC21A (500V)
32A
Current (Ie) in AC21A (690V)
32A
Current (Ie) in AC22A (415V)
40A
Current (Ie) in AC22A (500V)
32A
Current (Ie) in AC22A (690V)
32A
Current (Ie) in AC23A (415V)
35A
Current (Ie) in AC23A (500V)
25A
Current (Ie) in AC23A (690V)
25A
Current (Ie) in AC3 (415V)
28.5A
Current (Ie) in AC3 (690V)
20A
Current (Ie) in DC22A (250V)
32A
Current (Ie) in DC22A (600V)
10A
Power AC23A (415V)
18.5kW
Short-time current
400A Icw(1s)
Conditional short circuit cur.
10kAeff
Associate fuse - type gG
40A
Terminals - Flexible wires
1.5-10mm²
Terminals - Rigid wires
1.5-16mm²
Catalogue notes
Handle padlockable in OFF position only (3 padlocks)
Equipped with door interlock
With late break and early make neutral pole
Open threaded cable entry with cap / cable sleeve