Commercial Series
ISOLATORS-HR Series
Synthetical description
SWITCH DISCONNECTOR
Construction type
Enclosed
Mounting version
SURFACE MOUNTING
Installation temperature
-25°C/+60°C
Rated insulation voltage (Ui)
Rated impulse voltage (Uimp)
12KV
Thermal current (Ithe)
400A
Current (Ie) in AC21A (415V)
400A
Current (Ie) in AC21A (500V)
400A
Current (Ie) in AC21A (690V)
400A
Current (Ie) in AC22A (415V)
400A
Current (Ie) in AC22A (500V)
400A
Current (Ie) in AC22A (690V)
400A
Current (Ie) in AC23A (415V)
400A
Current (Ie) in AC23A (500V)
315A
Current (Ie) in AC23A (690V)
250A
Current (Ie) in DC21A (220V)
400A
Current (Ie) in DC21A (400V)
400A
Current (Ie) in DC21A (600V)
400A
Conditional short circuit cur.
50kAeff
Associate fuse - type gG
400A
Catalogue notes
TOP/BOTTOM = Top/Bottom connection
Equipped with door interlock
Handle padlockable in OFF position only (3 padlocks)
Fuses not supplied
Gland plate cable entry on bottom side