Commercial Series
ISOLATORS-HR Series
Synthetical description
SWITCH DISCONNECTOR
Construction type
Enclosed
Mounting version
SURFACE MOUNTING
Installation temperature
-25°C/+60°C
Rated insulation voltage (Ui)
1000VAC
Rated impulse voltage (Uimp)
12KV
Thermal current (Ithe)
250A
Current (Ie) in AC21A (415V)
250A
Current (Ie) in AC21A (500V)
250A
Current (Ie) in AC21A (690V)
250A
Current (Ie) in AC22A (415V)
200A
Current (Ie) in AC22A (500V)
200A
Current (Ie) in AC22A (690V)
200A
Current (Ie) in AC23A (415V)
200A
Current (Ie) in AC23A (500V)
160A
Current (Ie) in AC23A (690V)
125A
Short-time current
8kA Icw(1s)
Conditional short circuit cur.
50kAeff
Associate fuse - type gG
200A
Catalogue notes
BOTTOM/BOTTOM = Bottom/Bottom connection with busbar
Equipped with door interlock
Handle padlockable in OFF position only (3 padlocks)
With late break and early make neutral pole
Gland plate cable entry on bottom side