Commercial Series
ISOLATORS-HR Series
Synthetical description
SWITCH DISCONNECTOR
Construction type
Enclosed
Mounting version
SURFACE MOUNTING
Installation temperature
-25°C/+60°C
Rated insulation voltage (Ui)
1000VAC
Rated impulse voltage (Uimp)
12KV
Thermal current (Ithe)
1600A
Current (Ie) in AC21A (415V)
1600A
Current (Ie) in AC21A (500V)
1600A
Current (Ie) in AC21A (690V)
1250A
Current (Ie) in AC22A (415V)
1600A
Current (Ie) in AC22A (500V)
1250A
Current (Ie) in AC22A (690V)
400A
Current (Ie) in AC23A (415V)
1250A
Current (Ie) in AC23A (500V)
800A
Current (Ie) in AC23A (690V)
400A
Short-time current
60kA Icw(1s)
Catalogue notes
TOP/BOTTOM = Top/Bottom connection
Equipped with door interlock
Handle padlockable in OFF position only (3 padlocks)
With late break and early make neutral pole
Gland plate cable entry on bottom side
Neutral pole 1250A. Full current neutral pole on request.