PHOENIX CONTACT VAL-SEC-T2-440-P VAL-SEC-T2-440-P 2909969 PHOENIX CONTACT Type 2 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-SEC-T2-440-P 2909969 PHOENIX CONTACT Type 2 surge protection plug

VAL-SEC-T2-440-P

2909969

PHOENIX CONTACT

1 Pcs.

Type 2 surge protection plug Replacement connector for surge arrester from the VALVETRAB SEC product line for L-N and L-PEN paths.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2909969
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 45 (C-4-2017)
GTIN4055626409061
Weight per Piece (excluding packing)63.420 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height46.4 mm
Width11.7 mm
Depth59.4 mm
Horizontal pitch0.6 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
TT
Mode of protectionL-N
L-PEN
Mounting typeon base element
Colorlight grey RAL 7035
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Additional descriptions

NoteUsable in all low-voltage systems between L-N or L-PEN.
Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE= RAaccordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a)

Protective circuit

Nominal voltage UN400 V AC (TN)
400 V AC (TT)
400 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC440 V AC
Standby power consumption PC≤ 180 mVA
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Short-circuit current rating ISCCR25 kA (in case of 315 A gG backup fuse)
50 kA (in case of 200 A gG backup fuse)
Voltage protection level Up≤ 1.9 kV
Residual voltage Ures≤ 1.9 kV (at In)
≤ 1.65 kV (at 10 kA)
≤ 1.5 kV (at 5 kA)
≤ 1.45 kV (at 4 kA)
≤ 1.35 kV (at 2 kA)
TOV behavior at UT581 V AC (5 s / withstand mode)
762 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring315 A (gG)

Connection data

Connection methodpluggable

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.