PHOENIX CONTACT VAL-SEC-AGK-25 VAL-SEC-AGK-25 1452282 PHOENIX CONTACT Branch terminal block, can only be used in combination with the VAL-S.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-SEC-AGK-25 1452282 PHOENIX CONTACT Branch terminal block, can only be used in combination with the VAL-S..

VAL-SEC-AGK-25

1452282

PHOENIX CONTACT

4 Pcs.

Branch terminal block, can only be used in combination with the VAL-SEC-T2 series, nominal voltage: 400 V, nominal current: 63 A, connection type: screw connection, dimensioning cross-section: 25 mm², cross-section: 1.5 mm² - 25 mm², colour: grey Bypass terminal block Pick-off terminal block, can only be used in combination with VAL-SEC-T2 series, nominal voltage: 400 V, nominal current: 63 A, connection method: screw connection, rated cross-section: 25 mm2, cross-section: 1.5 mm2 ... 25 mm2, color: gray

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
Product typePick-off terminal
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Connection data
Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 16 mm²
Conductor cross section rigid1.5 mm² ... 25 mm²
Conductor cross section AWG15 ... 4

Dimensions
Width12.5 mm
Height38.8 mm
Depth41.2 mm

Material specifications
Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPA6.6
Material groupI

Protective circuit
Nominal voltage UN400 V AC
400 V AC
Maximum continuous voltage UC440 V AC
450 V DC
Rated load current IL63 A
Nominal discharge current In(8/20) µs40 kA
Maximum discharge current Imax(8/20) µs80 kA
Short-circuit current rating ISCCR50 kA
Max. backup fuse with branch wiring63 A (gG / B / C)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Altitude2000 m (amsl)

Standards and regulations
Standards/specificationsIEC 61643-11
Note2011
EN 61643-11
Standards/specificationsEN 61643-11
Note2012

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.