PHOENIX CONTACT VAL-MS-CN 1000DC-PV-ST VAL-MS-CN 1000DC-PV-ST 2801309 PHOENIX CONTACT Replacement plug-in protection for PV arrester combinations f.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-MS-CN 1000DC-PV-ST 2801309 PHOENIX CONTACT Replacement plug-in protection for PV arrester combinations f..

VAL-MS-CN 1000DC-PV-ST

2801309

PHOENIX CONTACT

1 Pcs.

Replacement plug-in protection for PV arrester combinations from the VAL-MS 1000DC-PV product line-... Replacement plug for PV arrester combinations from the VAL-MS 1000DC-PV-... product range

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
IEC test classificationPV T2
PV T2
EN typeT2
IEC power supply systemDC
TypeMale
Product typeReplacement plug
Product familyVALVETRAB MS
Installation locationInterior
Installation location of the disconnect deviceInternal
AccessibilityAccessible
SPD failure behaviorOCFM (Open-Circuit Failure Mode)
Surge protection fault messageoptical
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Connection data
Connection methodpluggable

Dimensions
Dimensional drawingcyfdztxmee.jpg
Width17.5 mm
Height52.4 mm
Depth55.3 mm
Horizontal pitch1 Div.

Material specifications
Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPA 6.6-FR
Material groupI
Housing materialPA 6.6-FR

Protective circuit
Standby power consumption PC≤ 25 mVA
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Voltage protection level Up≤ 1.9 kV
Residual voltage Ures≤ 1.9 kV (at In)
≤ 1.4 kV (at 2 kA)
≤ 1.5 kV (at 5 kA)
≤ 1.7 kV (at 10 kA)
≤ 1.8 kV (at 15 kA)
≤ 2.2 kV (at 30 kA)
≤ 2.4 kV (at 40 kA)
Response time tA≤ 25 ns
Protective circuit DC voltage side (DC)
Open circuit voltage UOCSTC≤ 487.5 V DC
Maximum discharge current Imax(8/20) µs40 kA
Response time tA≤ 25 ns
Insulation resistance Riso> 5 GΩ (at 500 V DC)
Nominal discharge current In(8/20) µs20 kA
Continuous operating current ICPV< 20 µA
Maximum continuous operating voltage UCPV585 V DC
Short-circuit current rating ISCPV2000 A
Residual voltage Ures≤ 1.9 kV (at In)
≤ 1.4 kV (at 2 kA)
≤ 1.5 kV (at 5 kA)
≤ 1.7 kV (at 10 kA)
≤ 1.8 kV (at 15 kA)
≤ 2.2 kV (at 30 kA)
≤ 2.4 kV (at 40 kA)
Voltage protection level Up≤ 1.9 kV
Standby power consumption PC≤ 25 mVA

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl)
Permissible humidity (operation)5 % ... 95 %
Shock (operation)60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)7.5g (5-500 Hz/2.5 h/XYZ)

Standards and regulations
Standards/specificationsEN 61643-31
Note2019
Standards/specificationsIEC 61643-31
Note2018

Mounting
Mounting typeon base element

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.