PHOENIX CONTACT VAL-MS 690 ST VAL-MS 690 ST 1068842 PHOENIX CONTACT Type 2 surge protection plug with high-capacity varistor for VAL-MS ba.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-MS 690 ST 1068842 PHOENIX CONTACT Type 2 surge protection plug with high-capacity varistor for VAL-MS ba..

VAL-MS 690 ST

1068842

PHOENIX CONTACT

1 Pcs.

Type 2 surge protection plug with high-capacity varistor for VAL-MS base element, thermal monitoring, visual fault warning. Design: 690 V AC Plug-in type 2 surge protection with high-voltage varistor for VAL-MS base element, with thermal control, optical fault indication. Version: 690 V AC

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey1068842
Packing unit1
GTIN4055626743905
Custom tariff number85363010

Drawings



Dimensional drawing

Dimensional drawing

Circuit diagram

Circuit diagram



Back to top

Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.
Back to top

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Back to top

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
IT
Mode of protectionL-PE (IT)
L-PEN (TN-C)
Mounting typeon base element
Colorjet black RAL 9005
Housing materialPA 6.6
Degree of pollution2
Distance between live and grounded parts8 mm
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical
Back to top

Additional descriptions

NoteFor use in all low-voltage systems between L-PEN.
Only for use in IT systems between L-PE if the bodies of the equipment in the low-voltage system are connected to the grounding system of the transformer station. (common grounding of the HV transformer station and the bodies of the LV consumer's installation. RE= RAaccording to IEC 60364-4-442/VDE 0100-442 Figure 44D/example a)
A maximum backup fuse (with branch line wiring) of F=250 A gG can be used for systems with a prospective short-circuit current of between 3 kA to 50 kA.
Back to top

Protective circuit

Nominal voltage UN554/960 V AC (TN)
690 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC760 V AC
Residual current IPE≤ 0.5 mA
Standby power consumption PC≤ 400 mVA
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs30 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 2.9 kV
TOV behavior at UT1005 V AC (5 s / withstand mode)
1056 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring200 A (gG)
Back to top

Connection data

Connection methodpluggable
Back to top

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-N)750 V AC
Nom. voltage690 V AC
Mode of protectionL-N
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)3040 V
Nominal discharge current In(L-N)20 kA
Back to top

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012
Back to top

Classifications

eCl@ss

eCl@ss 10.0.127130890
eCl@ss 8.027130890
eCl@ss 9.027130890
Back to top

ETIM

ETIM 5.0EC002496
Back to top

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.