PHOENIX CONTACT VAL-MS 1000DC-PV-ST/4 VAL-MS 1000DC-PV-ST/4 1019121 PHOENIX CONTACT Type 2 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-MS 1000DC-PV-ST/4 1019121 PHOENIX CONTACT Type 2 surge protection plug

VAL-MS 1000DC-PV-ST/4

1019121

PHOENIX CONTACT

4 Pcs.

Type 2 surge protection plug Replacement plug-in protection for PV arrester combinations from the VAL-MS 1000DC-PV product line-... Replacement plug for VAL-MS 1000DC-PV series PV combination surge arresters-...

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey1019121
Packing unit4 pc
Minimum order quantity4 pc
NoteMade to Order (non-returnable)
GTIN4055626504889
Weight per Piece (excluding packing)51.200 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)7.5g (5-500 Hz/2.5 h/XYZ)

General

IEC test classificationPV II
PV T2
EN typeT2
SPD failure behaviorOCM (Open-circuit mode)
Colorjet black RAL 9005
Housing materialPA 6.6-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Surge protection fault messageoptical

Protective circuit DC voltage side (DC)

Maximum continuous operating voltage UCPV585 V DC
Short-circuit current rating ISCPV1000 A
Continuous operating current ICPV< 20 µA
Standby power consumption PC≤ 25 mVA
Nominal discharge current (8/20) µs15 kA
Maximum discharge current Imax(8/20) µs40 kA
Voltage protection level Up≤ 1.9 kV
Residual voltage Ures≤ 1.9 kV (at In)
≤ 1.5 kV (at 5 kA)
≤ 1.7 kV (at 10 kA)
≤ 2 kV (at 20 kA)
≤ 2.3 kV (at 30 kA)
≤ 2.5 kV (at 40 kA)
Response time tA≤ 25 ns
Insulation resistance Riso> 5 GΩ (at 500 V DC)

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L+) - G1170 V DC
Nominal voltage970 V DC
Mode of protection(L+) - G
Power distribution systemSingle phase
Measured limiting voltage MLV (L+) - G1980 V
Nominal discharge current In(L+) - G10 kA

Standards and Regulations

Standards/regulationsEN 50539-11 2013

Classifications