PHOENIX CONTACT VAL-MB-T2 1500DC-PV/2+V-FM VAL-MB-T2 1500DC-PV/2+V-FM 2905646 PHOENIX CONTACT Type 2 surge arrester View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-MB-T2 1500DC-PV/2+V-FM 2905646 PHOENIX CONTACT Type 2 surge arrester

VAL-MB-T2 1500DC-PV/2+V-FM

2905646

PHOENIX CONTACT

1 Pcs.

Type 2 surge arrester Surge protection device for isolated and grounded systems of 1500 V DC photovoltaic 2-pole direct voltage, for rail mounting, with remote indication contact, temperature-controlled protection elements, status message on the module.

Automation > Surge protection device for power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2905646
Packing unit1 pc
Catalog pagePage 64 (C-4-2017)
GTIN4046356984195
Weight per Piece (excluding packing)389.400 g
Custom tariff number85354000
Country of originDE (Germany)

Dimensions

Height120 mm
Width71.2 mm
Depth65.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch4 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 6000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)50g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 - 500 Hz/2.5 h/X, Y, Z)

General

IEC test classificationPV II
PV T2
EN typeT2
SPD failure behaviorOCM (Open-circuit mode)
Connection configurationY configuration
Installation locationInside
AccessibilityAccessible
Installation location of the disconnect deviceInternal
Mode of protection(L+) - (L-)
(L+) - PE
(L-) - PE
Mounting typeDIN rail: 35 mm
Colortraffic grey A RAL 7042
Housing materialPA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, one-piece
Surge protection fault messageOptical, remote indicator contact

Additional descriptions

NoteThe product is also suitable for applications in PV systems with a max. short-circuit current ISCPV= 15 kA (according to EN 50539-11:2013).

Protective circuit DC voltage side (DC)

Maximum continuous operating voltage UCPV1500 V DC
Short-circuit current rating ISCPV2000 A
Continuous operating current ICPV< 55 µA
Rated load current IL50 A
Residual current IPE≤ 55 µA DC
≤ 430 µA AC
Standby power consumption PC≤ 85 mVA
Nominal discharge current (8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Total discharge current Itotal(8/20) µs40 kA
Voltage protection level Up≤ 4.5 kV
Residual voltage Ures≤ 4.5 kV (at In)
≤ 3.3 kV (at 3 kA)
≤ 3.6 kV (at 6.25 kA)
≤ 3.8 kV (at 10 kA)
≤ 4.2 kV (at 15 kA)
≤ 5.4 kV (at 40 kA)
Response time tA≤ 25 ns
Insulation resistance Riso> 5 GΩ (at 500 V DC)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
5 V DC ... 30 V DC
Operating current5 mA AC ... 1.5 A AC
5 mA DC ... 1 A DC
Connection methodScrew connection
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm
Stripping length16 mm
Conductor cross section flexible2.5 mm² ... 35 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min.2.5 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max.10 mm²
Conductor cross section AWG14 ... 2

Standards and Regulations

Standards/regulationsEN 50539-11 2013

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2905646 Earthing, lightning and surge protection (EC000941)
Feature Name Feature Value
System configuration IT (EF009927) No

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.