PHOENIX CONTACT USLKG 35-1 USLKG 35-1 0449014 PHOENIX CONTACT Ground modular terminal block View larger
Images are for illustrative purposes only. Please refer to data sheet for details

USLKG 35-1 0449014 PHOENIX CONTACT Ground modular terminal block

USLKG 35-1

0449014

PHOENIX CONTACT

25 Pcs.

Ground modular terminal block Ground terminal, For connection sections >= 35 mm² / AWG 2 a copper rail NS 35/15-2.3 must be inserted. In a joint alignment with a pitch terminal of equal contour, a cover for insulation voltages > 690 V must be inserted, number of connections: 2, number of poles: 1, type of connection: Screw connection, cross-section: 0.75 mm² - 50 mm², type of fixing: PE foot with fixing screw, M5, mounting class: NS 35/15-2.3, Color: Yellow-Green

Automation > Ground terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey 0449014
Packing unit 25 pc
Catalog page Page 219 (CL-2005)
GTIN 4017918002350
Weight per Piece (excluding packing) 84.670 g
Custom tariff number 85369010
Country of origin DE (Germany)

General

Note Use an NS 35/15-2.3 copper DIN rail for connection cross sections >= 35 mm²/2 AWG. When aligning with a feed-through terminal block of the same shape, a cover must be used for insulation voltages > 690 V.
Number of positions 1
Number of levels 1
Number of connections 2
Color green-yellow
Insulating material PA
Flammability rating according to UL 94 V0
Rated surge voltage 8 kV
Degree of pollution 3
Overvoltage category III
Insulating material group I
Open side panel No
Terminal block mounting 2.5 Nm ... 3 Nm (PE foot with mounting screw, M5)
Relative insulation material temperature index (Elec., UL 746 B) 130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 125 °C
Static insulating material application in cold -60 °C
Behavior in fire for rail vehicles (DIN 5510-2) Test passed
Flame test method (DIN EN 60695-11-10) V0
Oxygen index (DIN EN ISO 4589-2) >32 %
NF F16-101, NF F10-102 Class I 2
NF F16-101, NF F10-102 Class F 2
Surface flammability NFPA 130 (ASTM E 162) passed
Specific optical density of smoke NFPA 130 (ASTM E 662) passed
Smoke gas toxicity NFPA 130 (SMP 800C) passed
Calorimetric heat release NFPA 130 (ASTM E 1354) 27,5 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3

Dimensions

Width 15.2 mm
Length 50 mm
Height NS 35/7,5 62 mm
Height NS 35/15 69.5 mm
Height NS 32 67 mm

Connection data

Note Please observe the current carrying capacity of the DIN rails.
Connection method Screw connection
Connection in acc. with standard IEC 60947-7-2
Conductor cross section solid min. 0.75 mm²
Conductor cross section solid max. 50 mm²
Conductor cross section AWG min. 18
Conductor cross section AWG max. 1/0
Conductor cross section flexible min. 0.75 mm²
Conductor cross section flexible max. 35 mm²
Min. AWG conductor cross section, flexible 18
Max. AWG conductor cross section, flexible 2
Conductor cross section flexible, with ferrule without plastic sleeve min. 0.75 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 35 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 0.75 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 35 mm²
2 conductors with same cross section, solid min. 0.75 mm²
2 conductors with same cross section, solid max. 16 mm²
2 conductors with same cross section, stranded min. 0.75 mm²
2 conductors with same cross section, stranded max. 10 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. 0.75 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. 6 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. 0.75 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. 10 mm²
Connection in acc. with standard IEC/EN 60079-7
Conductor cross section solid min. 0.75 mm²
Conductor cross section solid max. 50 mm²
Conductor cross section AWG min. 18
Conductor cross section AWG max. 1/0
Conductor cross section flexible min. 0.75 mm²
Conductor cross section flexible max. 35 mm²
Stripping length 15 mm
Screw thread M6
Tightening torque, min 3.2 Nm
Tightening torque max 3.7 Nm

Standards and Regulations

Connection in acc. with standard CSA
IEC 60947-7-2
Flammability rating according to UL 94 V0
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.