PHOENIX CONTACT TTC-6P-3-HF-M-12DC-UT-I TTC-6P-3-HF-M-12DC-UT-I 2906744 PHOENIX CONTACT Surge protection, consisting of protective plug and base ele.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TTC-6P-3-HF-M-12DC-UT-I 2906744 PHOENIX CONTACT Surge protection, consisting of protective plug and base ele..

TTC-6P-3-HF-M-12DC-UT-I

2906744

PHOENIX CONTACT

1 Pcs.

Surge protection, consisting of protective plug and base element, with integrated status indicator and knife disconnection for three signal wires with common reference potential. For HF applications and telecommunications interfaces without supply voltage. Surge protection, consisting of plug-in protection and base element, with integrated status indication and blade interrupt for three signal conductors with common reference potential. For high-frequency applications and telecommunication interfaces without supply voltage, EX e approval for zone 2. Surge protection, consisting of protective plug and base element, with integrated status indicator and knife disconnection for three signal wires with common reference potential. For HF applications and telecommunications interfaces without supply voltage, EX e approval for zone 2. Can be used in safety-related circuits up to SIL 3.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
Product typeSurge protection for information technology
Product familyTERMITRAB complete
IEC test classificationC1
C2
C3
D1
TypeDIN rail module, two-section, divisible
Data management status
Article revision07
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal voltage UN12 V DC

Connection data
Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Ex data
Maximum input current600 mA (T4 / ≤ 30 °C)
500 mA (T4 / > 30 °C ... ≤ 50 °C)
400 mA (T4 / > 50 °C ... ≤ 70 °C)
Maximum input voltage15 V DC
Altitude≤ 2000 m (amsl)
Ambient temperature (operation)-40 °C ... 70 °C (T4)

Dimensions
Dimensional drawinglyhflqyjxr.jpg
Width6.2 mm +0.1 mm
Height105.8 mm
Depth100 mm (incl. DIN rail 7.5 mm)

Material specifications
Color (Base element)gray (RAL 7042)
Color (Male connector)light gray (RAL 7035)
Flammability rating according to UL 94V-0
Insulating materialPBT
Housing materialPBT

Mechanical properties
Mechanical data
Open side panelNo

Protective circuit
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC15 V DC
10 V AC
Rated current600 mA (56 °C)
Operating effective current ICat UC≤ 100 µA
Residual current IPE≤ 200 µA
Nominal discharge current In(8/20) µs (line-line)5 kA
Nominal discharge current In(8/20) µs (line-ground)5 kA
Pulse discharge current Iimp(10/350) µs (line-line)0.5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Total discharge current Itotal(8/20) µs10 kA
Voltage protection level Up(line-line)≤ 145 V (C1 - 1 kV / 500 A)
≤ 260 V (C2 - 10 kV / 5 kA)
≤ 25 V (C3 - 25 A)
≤ 30 V (C3 - 100 A)
Voltage protection level Up(line-earth)≤ 80 V (C1 - 1 kV / 500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
≤ 25 V (C3 - 25 A)
≤ 30 V (C3 - 100 A)
Voltage protection level Upstatic (line-line)≤ 40 V (C1 - 1 kV / 500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
Voltage protection level Upstatic (line-earth)≤ 40 V (C1 - 1 kV / 500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 1 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 8.7 MHz/150 Ω)
Input attenuation aE, asym.typ. 0.3 dB (≤ 10.5 MHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ω systemtyp. 60 MHz
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω systemtyp. 60 MHz
Capacity (Core-Core)typ. 32 pF
Capacity (Core-Earth)typ. 32 pF
Resistance per path1.65 Ω ±20 %
Surge protection fault messageoptical
Max. required back-up fuse630 mA (FF)
Impulse durability (line-line)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
Impulse durability (line-earth)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-line)≤ 30 ms
Pulse reset time (line-earth)≤ 30 ms
Additional technical data
Max. total discharge current Itotal max(8/20) µs20 kA (1x - non Ex)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Standards and regulations
Standards/specificationsIEC 61643-21
Note2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21
Standards/specificationsEN 61643-21
Note2001 + A1:2009 + A2:2013
Standards/specificationsIEC 60079-0
Note2017
Standards/specificationsIEC 60079-7
Note2017
Standards/specificationsEN IEC 60079-0
Note2018
Standards/specificationsEN IEC 60079-7
Note2015 + A1:2018

Mounting
Mounting typeDIN rail: TH 35 - 7.5 mm

ETIM for 2906744 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage AC (EF008798) 12 V

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.