PHOENIX CONTACT TTC-6P-2X1-M-24DC-UT-I TTC-6P-2X1-M-24DC-UT-I 2906741 PHOENIX CONTACT Surge protection, consisting of protective plug and base elem.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TTC-6P-2X1-M-24DC-UT-I 2906741 PHOENIX CONTACT Surge protection, consisting of protective plug and base elem..

TTC-6P-2X1-M-24DC-UT-I

2906741

PHOENIX CONTACT

1 Pcs.

Surge protection, consisting of protective plug and base element, with integrated status indicator and disconnect knife for two signal wires with common reference potential, e.g., Digital IN/OUT. Surge protection, consisting of plug-in protection and base element, with integrated status display and disconnector blade for two signal conductors with common reference potential, e.g. digital INPUT/OUTPUT. Surge protection, consisting of protective plug and base element, with integrated status indicator and disconnect knife for two signal wires with common reference potential, e.g., digital IN/OUT. Can be used in safety-related circuits up to SIL 3.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
Product typeSurge protection for MCR technology
Product familyTERMITRAB complete
IEC test classificationC1
C2
C3
D1
TypeDIN rail module, two-section, divisible
Data management status
Article revision04
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal voltage UN24 V DC

Connection data
Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Dimensions
Dimensional drawinglyhflqyjxr.jpg
Width6.2 mm +0.1 mm
Height105.8 mm
Depth100 mm (incl. DIN rail 7.5 mm)

Material specifications
Color (Base element)gray (RAL 7042)
Color (Male connector)light gray (RAL 7035)
Flammability rating according to UL 94V-0
Insulating materialPBT
Housing materialPBT

Mechanical properties
Mechanical data
Open side panelNo

Protective circuit
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC30 V DC
21 V AC
Rated current600 mA (56 °C)
Operating effective current ICat UC≤ 5 µA
Residual current IPE≤ 10 µA
Nominal discharge current In(8/20) µs (line-ground)5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Total discharge current Itotal(8/20) µs10 kA
Voltage protection level Up(line-earth)≤ 140 V (C1 - 1 kV / 500 A)
≤ 190 V (C2 - 10 kV / 5 kA)
≤ 45 V (C3 - 25 A)
≤ 50 V (C3 - 100 A)
Voltage protection level Upstatic (line-earth)≤ 55 V (C1 - 1 kV / 500 A)
≤ 120 V (C2 - 10 kV / 5 kA)
Response time tA(line-earth)≤ 1 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 270 kHz/150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω systemtyp. 960 kHz
Capacity (Core-Earth)typ. 2.2 nF
Resistance per path1.65 Ω ±20 %
Surge protection fault messageoptical
Max. required back-up fuse630 mA (FF)
Impulse durability (line-earth)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-earth)≤ 300 ms
Additional technical data
Max. total discharge current Itotal max(8/20) µs20 kA (1x)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Standards and regulations
Standards/specificationsIEC 61643-21
Note2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21
Standards/specificationsEN 61643-21
Note2001 + A1:2009 + A2:2013

Mounting
Mounting typeDIN rail: TH 35 - 7.5 mm

ETIM for 2906741 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage DC (EF008799) 24 V

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.