PHOENIX CONTACT TTC-6P-1X2-EX-24DC-UT-I TTC-6P-1X2-EX-24DC-UT-I 1065312 PHOENIX CONTACT Surge protection, consisting of protective plug and base ele.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TTC-6P-1X2-EX-24DC-UT-I 1065312 PHOENIX CONTACT Surge protection, consisting of protective plug and base ele..

TTC-6P-1X2-EX-24DC-UT-I

1065312

PHOENIX CONTACT

1 Pcs.

Surge protection, consisting of protective plug and base element, with integrated status indicator for a 2-wire floating Ex i signal circuit, e.g. 0(4) - 20 mA current loop. Surge protection, consisting of plug-in protection and base element, with integrated status indication for a potential-free 2-wire intrinsically safe signal circuit, e.g. 0(4) current loop... 20 mA, suitable for HART. Surge protection, consisting of protective plug and base element, with integrated status indicator for a 2-wire floating Ex i signal circuit, e.g., 0(4) mA … 20 mA current loop, HART-compatible. Can be used in safety-related circuits up to SIL 3.

Automation > Combined arrester for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
Product typeSurge protection for MCR technology
Product familyTERMITRAB complete
IEC test classificationC1
C2
C3
D1
TypeDIN rail module, two-section, divisible
Wire pairs per module1
Data management status
Article revision10
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal voltage UN24 V DC

Connection data
Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Ex data
Maximum inner capacitance Cinegligible
Max. internal inductance Linegligible
Max. input current Ii400 mA (T4 / -40 °C ... +50 °C)
250 mA (T4 / -40 °C ... +70 °C)
350 mA (T6 / -40 °C ... +35 °C)
100 mA (T6 / -40 °C ... +70 °C)
Max. input voltage Ui30 V DC
Insulation voltage to ground> 180 V DC
Ambient temperature (operation)-40 °C ... 70 °C (with current derating)

Dimensions
Dimensional drawinglyhflqyjxr.jpg
Width6.2 mm +0.1 mm
Height105.8 mm
Depth100 mm (incl. DIN rail 7.5 mm)

Material specifications
Colorblue (RAL 5015)
light gray (RAL 7035)
Flammability rating according to UL 94V-0
Insulating materialPBT
Housing materialPBT

Mechanical properties
Mechanical data
Open side panelNo

Protective circuit
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC30 V DC
Rated current600 mA (40 °C)
Operating effective current ICat UC≤ 5 µA
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-line)5 kA
Nominal discharge current In(8/20) µs (line-ground)5 kA
Pulse discharge current Iimp(10/350) µs (line-line)0.5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Total discharge current Itotal(8/20) µs10 kA
Voltage protection level Up(line-line)≤ 55 V (C1 - 1 kV / 500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
≤ 55 V (C3 - 100 A)
Voltage protection level Up(line-earth)≤ 900 V (C1 - 1 kV / 500 A)
≤ 1.05 kV (C2 - 10 kV / 5 kA)
≤ 1.4 kV (C3 - 100 A)
Voltage protection level Upstatic (line-line)≤ 50 V (C1 - 1 kV / 500 A)
≤ 65 V (C2 - 10 kV / 5 kA)
Voltage protection level Upstatic (line-earth)≤ 900 V (C1 - 1 kV / 500 A)
≤ 1.05 kV (C2 - 10 kV / 5 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 250 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ω systemtyp. 940 kHz
Capacity (Core-Core)typ. 2 nF
Resistance per path1.65 Ω ±20 %
Surge protection fault messageoptical
Max. required back-up fuse630 mA (FF)
Impulse durability (line-line)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
Impulse durability (line-earth)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-line)≤ 700 ms
Pulse reset time (line-earth)≤ 30 ms

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Approvals
Conformity/Approvals
UL, USA / CanadaClass I, Div. 2, Groups A, B, C, D T4A

Standards and regulations
Standards/specificationsEN 60079-0
Note2018
Standards/specificationsEN 60079-11
Note2012
EN 61643-21
Standards/specificationsEN 61643-21
Note2001 + A1:2009 + A2:2013
Standards/specificationsIEC 60079-0
Note2017
Standards/specificationsIEC 60079-11
Note2008
Standards/specificationsIEC 61643-21
Note2000 + corrigendum 2001 + A1:2008, modified + A2:2012

Mounting
Mounting typeDIN rail: TH 35 - 7.5 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.