PHOENIX CONTACT TTC-6-3-HF-12DC-PT TTC-6-3-HF-12DC-PT 1065316 PHOENIX CONTACT Surge protection for three signal wires with common reference pot.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TTC-6-3-HF-12DC-PT 1065316 PHOENIX CONTACT Surge protection for three signal wires with common reference pot..

TTC-6-3-HF-12DC-PT

1065316

PHOENIX CONTACT

1 Pcs.

Surge protection for three signal wires with common reference potential. For HF applications and telecommunications interfaces without supply voltage (up to 90 Mbps). Surge protection for three signal wires with common reference potential. For HF applications and telecommunications interfaces without supply voltage (up to 90 Mbps). Can be used in safety-related circuits up to SIL 3.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Product properties
Product typeSurge protection for information technology
Product familyTERMITRAB complete
IEC test classificationC1
C2
C3
D1
TypeDIN rail module, one-piece
Data management status
Article revision04
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal voltage UN12 V DC

Connection data
Connection methodPush-in connection
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Dimensions
Dimensional drawingdgldaeyfvg.jpg
Width6.2 mm +0.1 mm
Height105.8 mm
Depth69.5 mm (incl. DIN rail 7.5 mm)

Material specifications
Colorgray (RAL 7042)
light gray (RAL 7035)
Flammability rating according to UL 94V-0
Insulating materialPBT
Housing materialPBT

Mechanical properties
Mechanical data
Open side panelNo

Protective circuit
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC15 V DC
10 V AC
Rated current600 mA (40 °C)
Operating effective current ICat UC≤ 100 µA
Residual current IPE≤ 200 µA
Nominal discharge current In(8/20) µs (line-line)5 kA
Nominal discharge current In(8/20) µs (line-ground)5 kA
Pulse discharge current Iimp(10/350) µs (line-earth)0.5 kA
Total discharge current Itotal(8/20) µs10 kA
Voltage protection level Up(line-line)≤ 45 V (C1 - 1 kV / 500 A)
≤ 85 V (C2 - 10 kV / 5 kA)
≤ 30 V (C3 - 100 A)
Voltage protection level Up(line-earth)≤ 50 V (C1 - 1 kV / 500 A)
≤ 90 V (C2 - 10 kV / 5 kA)
≤ 30 V (C3 - 100 A)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 1 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 8.7 MHz/150 Ω)
Input attenuation aE, asym.typ. 0.3 dB (≤ 10.5 MHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ω systemtyp. 60 MHz
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω systemtyp. 60 MHz
Capacity (Core-Core)typ. 32 pF
Capacity (Core-Earth)typ. 32 pF
Resistance per path1.65 Ω ±20 %
Surge protection fault messagenone
Max. required back-up fuse630 mA (FF)
Impulse durability (line-line)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
Impulse durability (line-earth)C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-line)≤ 30 ms
Pulse reset time (line-earth)≤ 30 ms
Additional technical data
Max. total discharge current Itotal max(8/20) µs20 kA (1x)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Standards and regulations
Standards/specificationsIEC 61643-21
Note2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21
Standards/specificationsEN 61643-21
Note2001 + A1:2009 + A2:2013

Mounting
Mounting typeDIN rail: TH 35 - 7.5 mm

ETIM for 1065316 Earthing, lightning and surge protection (EC000943)