| AC Operation | |
| Network Structure | Star Network (TN, TT, IT (PE)) |
| Nominal Input Voltage Range | 3x 400V AC ... 500 V AC |
| Input Voltage Range | 3x 400V AC ... 500 V AC -20% ... +10% |
| 2x 400V AC ... 500 V AC ±10% | |
| Typical Country Grid Voltage | 3x 400V AC |
| 3x 480V AC | |
| Supply Voltage Voltage Type | AC |
| Extra-current shut-off | < 13 A (25 °C) |
| Inrush current integral (I2t) | < 0.33 A2s |
| Frequency range (fN) | 50 Hz ... 60 Hz ±10% |
| Network Failure Bridging Time | Typ. 28 ms (3x 400 V AC) |
| Typ. 28 ms (3x 480 V AC) | |
| Current absorption | 3x 0.77 A (3x 400 V AC) |
| 3x 0.63 A (3x 500 V AC) | |
| 2x 1.37 A (2x 400 V AC) | |
| 2x 1.13 A (2x 500 V AC) | |
| Protection Circuit | Protection against transients; Varistor |
| Power Factor (cos phi) | 0.93 (3x 480 V AC) |
| Module Input Fuse | 3.15 A internal (device protection) |
| Selecting the Right Fuse for Ingress Protection | 3x 6 A ... 16 A (Characteristic B, C, D, K or comparable) |
| Ground Shunt Current (PE) | < 3.5 mA |
| Yield | Typ. 94.53% (3x 400 V AC) |
| Typ. 94.58% (3x 480V AC) | |
| Nominal Output Voltage | 24 V DC |
| Output Voltage Adjustment Range (Uset) | 24 V DC ... 28 V DC (> 24 V DC, limited by power constant) |
| Rated Output Current (IN) | 20 A |
| Dynamic Boost (IDyn.Boost) | max. 30 A (5 sec) |
| Short circuit resistant | Yes |
| Constant emptying | Yes |
| Derating | 60 °C ... 70 °C |
| Crest Factor | Typ. 1.51 (3x 400 V AC) |
| Typ. 1.69 (3x 480 V AC) | |
| Output Power (PN) | 480 W |
| Output Power (PDyn. Boost) | max. 720 W (5 sec) |
| Parallel connection possible | Yes, to increase power and redundancy with diode |
| Possibility of series connection | yes, to increase the tension (observe the SELV limit) |
| Recirculation Resistance | ≤ 35 V DC |
| Output Surge Protection (OVP) | ≤ 35 V DC |
| Residual ripple | Typ. 15 mVPP(with nominal values) |
| Dimming deviation | < 1% (static load change 10% ... 90 %) |
| < 3% (dynamic load change 10% ... 90 %) | |
| < 0.1% (input voltage change ±10%) | |
| Ascent Time | ≤ 1 sec (UOut= 10% ... 90 %) |
| Minimum power dissipated in vacuum mode | < 3 W (3x 400 V AC) |
| Maximum Open Circuit Dissipation | < 3.1 W (3x 480 V AC) |
| Power Dissipated at Minimum Rated Load | < 26.08 W (3x 400 V AC) |
| Maximum Rated Load Dissipation | < 27.35 W (3x 480 V AC) |
| Built-in protection | No |
| Relay signal 13/14 | |
| Position | 3.x |
| Pole Identification | 3.1 (13), 3.2 (14) |
| Switching contact (without potential) | OptoMOS |
| Switching voltage | MAX 30 V DC (SELV) |
| Current Capacity | max. 100 mA |
| Status Status | UOut> 21 V DC & IOutN (Closed Contact) |
| UOutOut > 0.9 x IN(averaged over a 60 sec interval) (Open contact) | |
| entrance | |
| Position | 1.x |
| Connection technology | |
| Pole Identification | 1.1 (L1), 1.2 (L2), 1.3 (L3), 1.4 () |
| Connecting Conductors | |
| Connection type | Push-in connection |
| rigid | 0.2 mm² ... 4 mm² |
| 1.5 mm² (recommended) | |
| flexible | 0.2 mm² ... 2.5 mm² |
| 1.5 mm² (recommended) | |
| Flexible toe cap without plastic sleeve | 0.25 mm² ... 2.5 mm² |
| 1.5 mm² (recommended) | |
| Flexible toe cap with plastic cuff | 0.25 mm² ... 1.5 mm² |
| 1.5 mm² (recommended) | |
| Rigid (AWG) | 24 ... 12 (Cu) |
| 16 (recommended) | |
| Peel Length | 10 mm (rigid/flexible) |
| 8 mm (Toebox) | |
| Exit | |
| Position | 2.x |
| Connection technology | |
| Pole Identification | 2.1, 2.2 (+), 2.3, 2.4, 2.5 (-) |
| Connecting Conductors | |
| Connection type | Push-in connection |
| rigid | 0.2 mm² ... 10 mm² |
| 4 mm² (recommended) | |
| flexible | 0.2 mm² ... 6 mm² |
| 6 mm² (recommended) | |
| Flexible toe cap without plastic sleeve | 0.25 mm² ... 6 mm² |
| 6 mm² (recommended) | |
| Flexible toe cap with plastic cuff | 0.25 mm² ... 6 mm² |
| 6 mm² (recommended) | |
| Rigid (AWG) | 24 ... 8 (Cu) |
| 12 (recommended) | |
| Peel Length | 12 mm (rigid/flexible) |
| 12 mm (Toe) | |
| Signal | |
| Position | 3.x |
| Connection technology | |
| Pole Identification | 3.1 (13), 3.2 (14) |
| Connecting Conductors | |
| Connection type | Push-in connection |
| rigid | 0.2 mm² ... 1.5 mm² |
| 0.5 mm² (recommended) | |
| flexible | 0.2 mm² ... 1.5 mm² |
| 0.5 mm² (recommended) | |
| Flexible toe cap without plastic sleeve | 0.25 mm² ... 1.5 mm² (Cu) |
| 0.5 mm² (recommended) | |
| Flexible toe cap with plastic cuff | 0.25 mm² ... 0.75 mm² |
| 0.5 mm² (recommended) | |
| Rigid (AWG) | 24 ... 16 (Cu) |
| 20 (recommended) | |
| Peel Length | 10 mm (rigid/flexible) |
| 8 mm (Toebox) | |
| LED Signage | |
| Type of signage | LED DC OK - Operating Signal Status (UN= 24 V DC, IOut= IN) |
| function | Visual indication of operating status |
| Colour | Red, Yellow, Green (Multicolor LED) |
| LED off | No supply voltage at Input AC (Off) |
| LED on (green), DC OK | UOut> 21 V DC & IOutN (on (green), DC OK) |
| LED On (Yellow), IOut > 90% | UOut> 21 V DC & IOut> 0.9 x IN(on (yellow), IOut> 90%) |
| LED On (Red), ISHORT | UOutOut > 0.9 x IN(on (red), ISHORTS) |
| LED On (Red Flashing) OVP | UOUT> OVP (Over voltage protection) (on (flashing red)) |
| Number of phases | 3,00 |
| Input/Output Insulation Voltage | 4 kV AC (type test) |
| 4 kV AC (Single Test) |
| Product Type | Power supply |
| Product Family | TRIO POWER |
| MTBF (IEC 61709, SN 29500) | > 1100000 h (25 °C) |
| > 600000 h (40 °C) | |
| > 230000 h (60 °C) | |
| Environmental Protection Directive | RoHS Directive 2011/65/EU |
| WEEE | |
| Reach | |
| Insulation Properties | |
| Kind of protection | I |
| Degree of pollution | 2 |
| Item Dimensions | |
| Width | 60 mm |
| Height | 135 mm |
| Depth | 132 mm |
| 125 mm (Equipment Depth (Rail Mount)) | |
| Mounting Size | |
| Right/Left Mounting Distance | 0 mm / 0 mm |
| Mounting Distance Up/Down | 50 mm / 50 mm |
| Type of mounting | Rail mounting |
| Installation instructions | Alignable: horizontal 0 mm, vertical 30 mm |
| Position for mounting | Horizontal rail NS 35, EN 60715 |
| Flammability class according to UL 94 | V0 (Housing, terminals) |
| Execution of the cap | Polycarbonate |
| Execution of the side elements | aluminium |
| Environmental conditions | |
| Protection Index | IP20 |
| Ambient Temperature (Service) | -25 °C ... 70 °C (> 60 °C Derating: 2.5%/K) |
| Ambient Temperature (Storage/Transport) | -40 °C ... 85 °C |
| Ambient temperature (Start-Up tested model) | -40 °C |
| Fixing height | ≤ 5000 m (> 2000 m, Derating: 10%/1000 m) |
| Max. permissible air humidity (service) | ≤ 95% (at 25°C, non-condensing) |
| Crashes (in service) | 18 ms, 30g, for each local address (IEC 60068-2-27) |
| Vibration (in service) | 10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6) |
| 50 Hz ... 150 Hz, 2.3g, 90 min. | |
| Surge Category | |
| EN 61010-1 | III (≤ 2000 m) |
| II (≤ 5000 m) | |
| Surge Category | |
| EN 61010-2-201 | III (≤ 2000 m) |
| II (≤ 5000 m) | |
| Safety of power supplies up to 1100 V (isolation distances) | |
| Denomination of standard | Safety of power supplies up to 1100 V (isolation distances) |
| Rules/Provisions | DIN EN 61558-2-16 |
| Electrical Safety | |
| Denomination of standard | Electrical Safety |
| Rules/Provisions | IEC 61010-2-201 (SELV) |
| Equipping high-intensity installations with electronic equipment | |
| Denomination of standard | Equipping high-intensity installations with electrical appliances |
| Rules/Provisions | EN 50178/VDE 0160 (PELV) |
| Safety of measuring, controlling, regulating and laboratory equipment | |
| Denomination of standard | Safety for measuring, controlling, regulating and laboratory equipment |
| Rules/Provisions | IEC 61010-1 |
| Minimum protective voltage with safe insulation | |
| Denomination of standard | Minimum protective voltage with safe insulation |
| Rules/Provisions | IEC 61010-1 (SELV) |
| IEC 61010-2-201 (PELV) | |
| Secure Isolation | |
| Denomination of standard | Safe Separation |
| Rules/Provisions | IEC 61558-2-16 |
| IEC 61010-2-201 | |
| Limitation of harmonic mains currents | |
| Denomination of standard | Limitation of harmonic currents in the network |
| Rules/Provisions | EN 61000-3-2 |
| Mains/Low Voltage Variation | |
| Denomination of standard | Mains/Low Voltage Variation |
| Rules/Provisions | SEMI F47 |
| EN 61000-4-11 | |
| Ul | |
| Marked | UL/C-UL Listed UL 61010-1 |
| Ul | |
| Marked | UL/C-UL Listed UL 61010-2-201 |
| ANSI/UL 121201 | |
| Marked | PROCESS CONTROL EQUIPEMENT FOR HAZARDOUS LOCATIONS |
| This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, Hazardous Locations, or non-hazardous locations only. (FR) Cet appareil convient uniquement pour une utilisation en atmosphères explosibles de classe I, division 2, groupes A, B, C et D ou en atmosphères non explosibles. | |
| WARNING: Explosion Hazard - Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. (FR) AVERTISSEMENT : risque d'explosion - ne pas connecter ou déconnecter les équipements sauf si l'alimentation a été coupée ou si la zone est réputée non dangereuse. | |
| If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. (FR) Si l'équipement est utilisé d'une manière non spécifiée par le fabricant, la protection fournie par cet équipement peut être altérée. | |
| This equipement must be installed in a suitable, tool secured/key locked enclosure. (FR) Cet équipement doit être installé dans un boîtier approprié, verrouillé par une clé ou dont l'ouverture nécessite l'utilisation d'un outil. | |
| Low Voltage Directive | Compliance with the Low Voltage Directive 2014/35/EU |
| Interference emission | Interference emission in accordance with EN 61000-6-3 (residential and commercial areas) and EN 61000-6-4 (industrial areas) |
| Interference resistance | Immunity to interference according to EN 61000-6-1 (domestic use), EN 61000-6-2 (industrial use) |
| Electromagnetic compatibility | Compliance with EMC Directive 2014/30/EU |
| Emission of Conducted Interference | EN 55016 |
| EN 61000-6-3 (class B) | |
| Radiated spurious emissions | EN 55016 |
| EN 61000-6-3 (class B) | |
| Harmonic currents | |
| Standards/Specifications | EN 61000-3-2 |
| EN 61000-3-2 (class A) | |
| Frequency Range | 0 kHz ... 2 kHz |
| Flicker | |
| Standards/Specifications | EN 61000-3-3 |
| EN 61000-3-3 | |
| Frequency Range | 0 kHz ... 2 kHz |
| Static Electricity Discharge | |
| Standards/Specifications | EN 61000-4-2 |
| Static Electricity Discharge | |
| Download contact us | 6 kV (Test Severity 3) |
| Discharge into the air | 8 kV (Test Severity 3) |
| Observation | Criterion B |
| Electromagnetic field AF | |
| Standards/Specifications | EN 61000-4-3 |
| Electromagnetic field AF | |
| Frequency Range | 80 MHz ... 1 GHz |
| Test Field Intensity | 10 V/m (Test Severity 3) |
| Frequency Range | 1 GHz ... 6 GHz |
| Test Field Intensity | 10 V/m (Test Severity 3) |
| Observation | Criterion A |
| Fast Transients (Burst) | |
| Standards/Specifications | EN 61000-4-4 |
| Fast Transients (Burst) | |
| entrance | asymmetric 2 kV (Test Severity 3) |
| Exit | asymmetric 2 kV (Test Severity 3) |
| Signal | asymmetric 1 kV (Test Severity 3) |
| Observation | Criterion A |
| Transient Voltage Load (Surge) | |
| Standards/Specifications | EN 61000-4-5 |
| entrance | symmetrical 2 kV (Test Severity 4) |
| asymmetric 4 kV (Test Severity 4) | |
| Exit | symmetrical 1 kV (Test Severity 3) |
| asymmetric 2 kV (Test Severity 3) | |
| Signal | asymmetric 1 kV (Test Severity 2) |
| Observation | Criterion A |
| Conducted Disturbances | |
| Standards/Specifications | EN 61000-4-6 |
| Conducted Disturbances | |
| I/O | asymmetric |
| Frequency Range | 0.15 MHz ... 80 MHz |
| Observation | Criterion A |
| tension | 10 V (Test Severity 3) |
| Voltage drops | |
| Standards/Specifications | EN 61000-4-11 |
| tension | 480 V AC |
| frequency | 50 Hz |
| Voltage Error | 70 % |
| Number of periods | 25 periods |
| Additional Text | Class 3 |
| Observation | Criterion A |
| Voltage Error | 40 % |
| Number of periods | 10 periods |
| Additional Text | Class 3 |
| Observation | Criterion B |
| Voltage Error | 0 % |
| Number of periods | 1 period |
| Additional Text | Class 3 |
| Observation | Criterion A |
| Criteria | |
| Criterion A | Normal service behavior within the specified limits. |
| Criterion B | Transient alteration of service behavior, which is corrected by the device itself. |
| Criterion C | Temporary adverse effects on performance that are automatically corrected by the equipment or that can be reset by operating the control elements. |
| Feature Name | Feature Value |
|---|---|
| Voltage type (supply voltage) (EF002991) | AC |
| 1st secondary output voltage (EF006792) | 24 V |
| Max. output current 1 (EF008284) | 30 A |
| Secondary voltage adjustable (EF007002) | Yes |
| Nominal value output voltage 1 (EF009393) | 24 V |
| Nominal value output current 1 (EF009396) | 20 A |
| Short-circuit-proof (EF007332) | Yes |
| Rated supply voltage AC 50 Hz (EF007076) | 320 V |
| Rated supply voltage AC 60 Hz (EF007077) | 320 V |
| Output voltage stabilized (EF003092) | Yes |
| Power output (EF003034) | 480 W |
| Stabilized (EF005302) | Yes |
| Type of electric connection (EF003961) | Other |
| Suitable for rail mounting (EF003972) | Yes |
| Wall mounting possible (EF003973) | No |
| Modular version (EF001126) | No |
| Built-in height (EF000332) | 135 mm |
| Direct mounting possible (EF005689) | No |
| Width (EF000008) | 60 mm |
| Height (EF000040) | 135 mm |
| Depth (EF000049) | 132 mm |
| Suitable for safety functions (EF001597) | Yes |
| SIL according to IEC 61508 (EF009889) | None |
| Performance level according to EN ISO 13849-1 (EF007399) | None |
| Degree of protection (IP) (EF005474) | IP20 |
| Degree of protection (NEMA) (EF011959) | Other |