PHOENIX CONTACT TRIO3-PS/3AC/24DC/20 TRIO3-PS/3AC/24DC/20 1159044 PHOENIX CONTACT Primary switching power supplies, TRIO POWER, Push-in connectio.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TRIO3-PS/3AC/24DC/20 1159044 PHOENIX CONTACT Primary switching power supplies, TRIO POWER, Push-in connectio..

TRIO3-PS/3AC/24DC/20

1159044

PHOENIX CONTACT

1 Pcs.

Primary switching power supplies, TRIO POWER, Push-in connection, Rail mounting, input: 3 phase, output: 24 V DC / 20 A, adjustable from 24 V DC ... 28 V DC Primary Switching Power Supplies, TRIO POWER, Push-in Connection, Rail Mount, Input: 3-Phase, Output: 24 VDC / 20 A

Automation > DC-power supply

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Technical data

Input data
AC Operation
Network StructureStar Network (TN, TT, IT (PE))
Nominal Input Voltage Range3x 400V AC ... 500 V AC
Input Voltage Range3x 400V AC ... 500 V AC -20% ... +10%
2x 400V AC ... 500 V AC ±10%
Typical Country Grid Voltage3x 400V AC
3x 480V AC
Supply Voltage Voltage TypeAC
Extra-current shut-off< 13 A (25 °C)
Inrush current integral (I2t)< 0.33 A2s
Frequency range (fN)50 Hz ... 60 Hz ±10%
Network Failure Bridging TimeTyp. 28 ms (3x 400 V AC)
Typ. 28 ms (3x 480 V AC)
Current absorption3x 0.77 A (3x 400 V AC)
3x 0.63 A (3x 500 V AC)
2x 1.37 A (2x 400 V AC)
2x 1.13 A (2x 500 V AC)
Protection CircuitProtection against transients; Varistor
Power Factor (cos phi)0.93 (3x 480 V AC)
Module Input Fuse3.15 A internal (device protection)
Selecting the Right Fuse for Ingress Protection3x 6 A ... 16 A (Characteristic B, C, D, K or comparable)
Ground Shunt Current (PE)< 3.5 mA

Output Data
YieldTyp. 94.53% (3x 400 V AC)
Typ. 94.58% (3x 480V AC)
Nominal Output Voltage24 V DC
Output Voltage Adjustment Range (Uset)24 V DC ... 28 V DC (> 24 V DC, limited by power constant)
Rated Output Current (IN)20 A
Dynamic Boost (IDyn.Boost)max. 30 A (5 sec)
Short circuit resistantYes
Constant emptyingYes
Derating60 °C ... 70 °C
Crest FactorTyp. 1.51 (3x 400 V AC)
Typ. 1.69 (3x 480 V AC)
Output Power (PN)480 W
Output Power (PDyn. Boost)max. 720 W (5 sec)
Parallel connection possibleYes, to increase power and redundancy with diode
Possibility of series connectionyes, to increase the tension (observe the SELV limit)
Recirculation Resistance≤ 35 V DC
Output Surge Protection (OVP)≤ 35 V DC
Residual rippleTyp. 15 mVPP(with nominal values)
Dimming deviation< 1% (static load change 10% ... 90 %)
< 3% (dynamic load change 10% ... 90 %)
< 0.1% (input voltage change ±10%)
Ascent Time≤ 1 sec (UOut= 10% ... 90 %)
Minimum power dissipated in vacuum mode< 3 W (3x 400 V AC)
Maximum Open Circuit Dissipation< 3.1 W (3x 480 V AC)
Power Dissipated at Minimum Rated Load< 26.08 W (3x 400 V AC)
Maximum Rated Load Dissipation< 27.35 W (3x 480 V AC)
Built-in protectionNo
Relay signal 13/14
Position3.x
Pole Identification3.1 (13), 3.2 (14)
Switching contact (without potential)OptoMOS
Switching voltageMAX 30 V DC (SELV)
Current Capacitymax. 100 mA
Status StatusUOut> 21 V DC & IOutN (Closed Contact)
UOutOut > 0.9 x IN(averaged over a 60 sec interval) (Open contact)

Connection data
entrance
Position1.x
Connection technology
Pole Identification1.1 (L1), 1.2 (L2), 1.3 (L3), 1.4 ()
Connecting Conductors
Connection typePush-in connection
rigid0.2 mm² ... 4 mm²
1.5 mm² (recommended)
flexible0.2 mm² ... 2.5 mm²
1.5 mm² (recommended)
Flexible toe cap without plastic sleeve0.25 mm² ... 2.5 mm²
1.5 mm² (recommended)
Flexible toe cap with plastic cuff0.25 mm² ... 1.5 mm²
1.5 mm² (recommended)
Rigid (AWG)24 ... 12 (Cu)
16 (recommended)
Peel Length10 mm (rigid/flexible)
8 mm (Toebox)
Exit
Position2.x
Connection technology
Pole Identification2.1, 2.2 (+), 2.3, 2.4, 2.5 (-)
Connecting Conductors
Connection typePush-in connection
rigid0.2 mm² ... 10 mm²
4 mm² (recommended)
flexible0.2 mm² ... 6 mm²
6 mm² (recommended)
Flexible toe cap without plastic sleeve0.25 mm² ... 6 mm²
6 mm² (recommended)
Flexible toe cap with plastic cuff0.25 mm² ... 6 mm²
6 mm² (recommended)
Rigid (AWG)24 ... 8 (Cu)
12 (recommended)
Peel Length12 mm (rigid/flexible)
12 mm (Toe)
Signal
Position3.x
Connection technology
Pole Identification3.1 (13), 3.2 (14)
Connecting Conductors
Connection typePush-in connection
rigid0.2 mm² ... 1.5 mm²
0.5 mm² (recommended)
flexible0.2 mm² ... 1.5 mm²
0.5 mm² (recommended)
Flexible toe cap without plastic sleeve0.25 mm² ... 1.5 mm² (Cu)
0.5 mm² (recommended)
Flexible toe cap with plastic cuff0.25 mm² ... 0.75 mm²
0.5 mm² (recommended)
Rigid (AWG)24 ... 16 (Cu)
20 (recommended)
Peel Length10 mm (rigid/flexible)
8 mm (Toebox)

Signage
LED Signage
Type of signageLED DC OK - Operating Signal Status (UN= 24 V DC, IOut= IN)
functionVisual indication of operating status
ColourRed, Yellow, Green (Multicolor LED)
LED offNo supply voltage at Input AC (Off)
LED on (green), DC OKUOut> 21 V DC & IOutN (on (green), DC OK)
LED On (Yellow), IOut > 90%UOut> 21 V DC & IOut> 0.9 x IN(on (yellow), IOut> 90%)
LED On (Red), ISHORTUOutOut > 0.9 x IN(on (red), ISHORTS)
LED On (Red Flashing) OVPUOUT> OVP (Over voltage protection) (on (flashing red))

Electrical Properties
Number of phases3,00
Input/Output Insulation Voltage4 kV AC (type test)
4 kV AC (Single Test)

Item Properties
Product TypePower supply
Product FamilyTRIO POWER
MTBF (IEC 61709, SN 29500)> 1100000 h (25 °C)
> 600000 h (40 °C)
> 230000 h (60 °C)
Environmental Protection DirectiveRoHS Directive 2011/65/EU
WEEE
Reach
Insulation Properties
Kind of protectionI
Degree of pollution2

Dimensions
Item Dimensions
Width60 mm
Height135 mm
Depth132 mm
125 mm (Equipment Depth (Rail Mount))
Mounting Size
Right/Left Mounting Distance0 mm / 0 mm
Mounting Distance Up/Down50 mm / 50 mm

assembly
Type of mountingRail mounting
Installation instructionsAlignable: horizontal 0 mm, vertical 30 mm
Position for mountingHorizontal rail NS 35, EN 60715

Material Data
Flammability class according to UL 94V0 (Housing, terminals)
Execution of the capPolycarbonate
Execution of the side elementsaluminium

Environmental and life-life conditions
Environmental conditions
Protection IndexIP20
Ambient Temperature (Service)-25 °C ... 70 °C (> 60 °C Derating: 2.5%/K)
Ambient Temperature (Storage/Transport)-40 °C ... 85 °C
Ambient temperature (Start-Up tested model)-40 °C
Fixing height≤ 5000 m (> 2000 m, Derating: 10%/1000 m)
Max. permissible air humidity (service)≤ 95% (at 25°C, non-condensing)
Crashes (in service)18 ms, 30g, for each local address (IEC 60068-2-27)
Vibration (in service)10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6)
50 Hz ... 150 Hz, 2.3g, 90 min.

Standards & Specifications
Surge Category
EN 61010-1III (≤ 2000 m)
II (≤ 5000 m)
Surge Category
EN 61010-2-201III (≤ 2000 m)
II (≤ 5000 m)
Safety of power supplies up to 1100 V (isolation distances)
Denomination of standardSafety of power supplies up to 1100 V (isolation distances)
Rules/ProvisionsDIN EN 61558-2-16
Electrical Safety
Denomination of standardElectrical Safety
Rules/ProvisionsIEC 61010-2-201 (SELV)
Equipping high-intensity installations with electronic equipment
Denomination of standardEquipping high-intensity installations with electrical appliances
Rules/ProvisionsEN 50178/VDE 0160 (PELV)
Safety of measuring, controlling, regulating and laboratory equipment
Denomination of standardSafety for measuring, controlling, regulating and laboratory equipment
Rules/ProvisionsIEC 61010-1
Minimum protective voltage with safe insulation
Denomination of standardMinimum protective voltage with safe insulation
Rules/ProvisionsIEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Secure Isolation
Denomination of standardSafe Separation
Rules/ProvisionsIEC 61558-2-16
IEC 61010-2-201
Limitation of harmonic mains currents
Denomination of standardLimitation of harmonic currents in the network
Rules/ProvisionsEN 61000-3-2
Mains/Low Voltage Variation
Denomination of standardMains/Low Voltage Variation
Rules/ProvisionsSEMI F47
EN 61000-4-11

Approvals
Ul
MarkedUL/C-UL Listed UL 61010-1
Ul
MarkedUL/C-UL Listed UL 61010-2-201
ANSI/UL 121201
MarkedPROCESS CONTROL EQUIPEMENT FOR HAZARDOUS LOCATIONS
 This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, Hazardous Locations, or non-hazardous locations only.
(FR)  Cet appareil convient uniquement pour une utilisation en atmosphères explosibles de classe I, division 2, groupes A, B, C et D ou en atmosphères non explosibles.
 WARNING: Explosion Hazard - Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
(FR)  AVERTISSEMENT : risque d'explosion - ne pas connecter ou déconnecter les équipements sauf si l'alimentation a été coupée ou si la zone est réputée non dangereuse.
 If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
(FR)  Si l'équipement est utilisé d'une manière non spécifiée par le fabricant, la protection fournie par cet équipement peut être altérée.
 This equipement must be installed in a suitable, tool secured/key locked enclosure.
(FR)  Cet équipement doit être installé dans un boîtier approprié, verrouillé par une clé ou dont l'ouverture nécessite l'utilisation d'un outil.

EMC data
Low Voltage DirectiveCompliance with the Low Voltage Directive 2014/35/EU
Interference emissionInterference emission in accordance with EN 61000-6-3 (residential and commercial areas) and EN 61000-6-4 (industrial areas)
Interference resistanceImmunity to interference according to EN 61000-6-1 (domestic use), EN 61000-6-2 (industrial use)
Electromagnetic compatibilityCompliance with EMC Directive 2014/30/EU
Emission of Conducted InterferenceEN 55016
EN 61000-6-3 (class B)
Radiated spurious emissionsEN 55016
EN 61000-6-3 (class B)
Harmonic currents
Standards/SpecificationsEN 61000-3-2
EN 61000-3-2 (class A)
Frequency Range0 kHz ... 2 kHz
Flicker
Standards/SpecificationsEN 61000-3-3
EN 61000-3-3
Frequency Range0 kHz ... 2 kHz
Static Electricity Discharge
Standards/SpecificationsEN 61000-4-2
Static Electricity Discharge
Download contact us6 kV (Test Severity 3)
Discharge into the air8 kV (Test Severity 3)
ObservationCriterion B
Electromagnetic field AF
Standards/SpecificationsEN 61000-4-3
Electromagnetic field AF
Frequency Range80 MHz ... 1 GHz
Test Field Intensity10 V/m (Test Severity 3)
Frequency Range1 GHz ... 6 GHz
Test Field Intensity10 V/m (Test Severity 3)
ObservationCriterion A
Fast Transients (Burst)
Standards/SpecificationsEN 61000-4-4
Fast Transients (Burst)
entranceasymmetric 2 kV (Test Severity 3)
Exitasymmetric 2 kV (Test Severity 3)
Signalasymmetric 1 kV (Test Severity 3)
ObservationCriterion A
Transient Voltage Load (Surge)
Standards/SpecificationsEN 61000-4-5
entrancesymmetrical 2 kV (Test Severity 4)
asymmetric 4 kV (Test Severity 4)
Exitsymmetrical 1 kV (Test Severity 3)
asymmetric 2 kV (Test Severity 3)
Signalasymmetric 1 kV (Test Severity 2)
ObservationCriterion A
Conducted Disturbances
Standards/SpecificationsEN 61000-4-6
Conducted Disturbances
I/Oasymmetric
Frequency Range0.15 MHz ... 80 MHz
ObservationCriterion A
tension10 V (Test Severity 3)
Voltage drops
Standards/SpecificationsEN 61000-4-11
tension480 V AC
frequency50 Hz
Voltage Error70 %
Number of periods25 periods
Additional TextClass 3
ObservationCriterion A
Voltage Error40 %
Number of periods10 periods
Additional TextClass 3
ObservationCriterion B
Voltage Error0 %
Number of periods1 period
Additional TextClass 3
ObservationCriterion A
Criteria
Criterion ANormal service behavior within the specified limits.
Criterion BTransient alteration of service behavior, which is corrected by the device itself.
Criterion CTemporary adverse effects on performance that are automatically corrected by the equipment or that can be reset by operating the control elements.

ETIM for 1159044 Low-voltage industrial controls and switchgear (EC002540)
Feature Name Feature Value
Voltage type (supply voltage) (EF002991) AC
1st secondary output voltage (EF006792) 24 V
Max. output current 1 (EF008284) 30 A
Secondary voltage adjustable (EF007002) Yes
Nominal value output voltage 1 (EF009393) 24 V
Nominal value output current 1 (EF009396) 20 A
Short-circuit-proof (EF007332) Yes
Rated supply voltage AC 50 Hz (EF007076) 320 V
Rated supply voltage AC 60 Hz (EF007077) 320 V
Output voltage stabilized (EF003092) Yes
Power output (EF003034) 480 W
Stabilized (EF005302) Yes
Type of electric connection (EF003961) Other
Suitable for rail mounting (EF003972) Yes
Wall mounting possible (EF003973) No
Modular version (EF001126) No
Built-in height (EF000332) 135 mm
Direct mounting possible (EF005689) No
Width (EF000008) 60 mm
Height (EF000040) 135 mm
Depth (EF000049) 132 mm
Suitable for safety functions (EF001597) Yes
SIL according to IEC 61508 (EF009889) None
Performance level according to EN ISO 13849-1 (EF007399) None
Degree of protection (IP) (EF005474) IP20
Degree of protection (NEMA) (EF011959) Other

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.