View larger
TRIO-UPS-2G/1AC/1AC/120V/750VA
2905908
PHOENIX CONTACT
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Orderkey | 2905908 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 282 (C-4-2017) |
| GTIN | 4055626007397 |
| Weight per Piece (excluding packing) | 6,098.000 g |
| Custom tariff number | 85044030 |
| Country of origin | DE (Germany) |
| Ambient temperature (operation) | 0 °C ... 40 °C |
|---|---|
| Ambient temperature (storage/transport) | -15 °C ... 40 °C (with charged energy storage device) |
| Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
| Maximum altitude | ≤ 3000 mm (> 2000 m, observe derating) |
| Vibration (operation) | 5 Hz ... 100 Hz, 0.7g (EN 60068-2-6) |
| Shock | 20g in all directions (EN 60068-2-27) |
| 30g in each space direction with UWA 130 | |
| Degree of pollution | 2 |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Nominal input voltage | 120 V AC |
|---|---|
| Input voltage range | 96 V AC ... 138 V AC |
| Frequency range | 55 Hz ... 65 Hz |
| Current consumption | 6 A |
| Permissible backup fuse | B10 B16 Listed breaker |
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 10 mm |
| Apparent power | 750 VA |
|---|---|
| Rated Power (Real Power) | 600 W |
| Power factor (cos phi) | 0.8 |
| Crest factor | 2.8 |
| Switch-over time | < 10 ms |
| Classification according to IEC 62040-3 | VFD-SS-311 |
| Nominal output voltage (UN) | 120 V AC |
|---|---|
| Nominal output current (IN) | 6 A (750 VA) |
| Nominal output voltage (UN) | 120 V AC |
|---|---|
| Nominal output current (IN) | 6 A (750 VA) |
| Form of output voltage | Pure sine |
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 10 mm |
| Efficiency | > 95 % (with charged energy storage device) |
|---|---|
| MTBF (IEC 61709, SN 29500) | > 206000 h (40°C) |
| Degree of protection | IP20 |
| Protection class | I |
| Type of housing | DX51D+AZ (steel sheet / Galvalume) |
| Hood version | PC + ABS |
| Input fuse | 10 A 400 V gRL |
| Weight | 5.7 kg |
| Battery technology | Lead rechargeable battery module |
|---|---|
| Battery type | 2x Panasonic UP-VW1220P1 |
| Capacity | 3.4 Ah |
| Battery fuse | 40 A, 32 V |
| Charging time | 7 h |
| Service life | 6 Years ... 9 Years (20 °C) |
| Latest startup | 6 Months (0 °C ... 20 °C) |
| Buffer period | 20 min. (100 W) |
| 4 min. (300 W) | |
| 1 min. (600 W) | |
| Can be extended with external battery | 1x 24 V 3.4 Ah |
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 10 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 6 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 8 |
| Stripping length | 15 mm |
| Switching output | Transistor output, active |
|---|---|
| Output voltage | 24 V (SELV) |
| Continuous load current | ≤ 20 mA |
| Status display | LED red |
| Switching output | Transistor output, active |
|---|---|
| Output voltage | 24 V (SELV) |
| Continuous load current | ≤ 20 mA |
| Status display | Yellow LED |
| Switching output | Transistor output, active |
|---|---|
| Output voltage | 24 V (SELV) |
| Continuous load current | ≤ 20 mA |
| Connection method | Push-in connection |
|---|---|
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
| Designation | Remote |
|---|---|
| Low signal | Connection to SGnd with < 2.7 kΩ |
| High signal | Open (> 35 kΩ between remote and SGnd) |
| Low signal | Connection to SGnd with < 2.7 kΩ |
|---|---|
| High signal | Open (> 200 kΩ between bat. start and SGnd) |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise immunity | Noise immunity according to EN 62040-2-2006 |
| Standards/regulations | EN 61000-4-2 |
| Contact discharge | 4 kV (Test Level 2) |
| Standards/regulations | EN 61000-4-3 |
| Frequency range | 80 MHz ... 1 GHz |
| Test field strength | 10 V/m |
| Standards/regulations | EN 61000-4-4 |
| Comments | Criterion B |
| Standards/regulations | EN 61000-4-6 |
| Frequency range | 0.15 MHz ... 80 MHz |
| Voltage | 10 V |
| Conducted noise emission | EN 55016 EN 62040-02 (Class C2) |
| Standards/regulations | EN 61000-4-8 |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| UL approvals | UL/C-UL Recognized UL 1778 |
| Shock | 20g in all directions (EN 60068-2-27) |
| Vibration (operation) | 5 Hz ... 100 Hz, 0.7g (EN 60068-2-6) |
| China RoHS | Environmentally Friendly Use Period = 3 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
| Feature Name | Feature Value |
|---|---|
| Input voltage (EF003840) | 96 V |
| Output voltage (EF003933) | 120 V |
| SNMP (EF005284) | No |
| Voltage type (EF000187) | AC |
| Height (EF000040) | 170 mm |
| Width (EF000008) | 210 mm |
| Depth (EF000049) | 136 mm |
| Weight (EF000167) | 6.098 kg |
| Bridging time full load (EF000428) | 60 min |
| Input connection (EF009726) | Other |