| AC Operation | |
| Network Structure | Star Network (TN, TT, IT (PE)) |
| Nominal Input Voltage Range | 120 V AC ... 240 V AC |
| Input Voltage Range | 120 V AC ... 240 V AC ±10% |
| Operating Voltage | > 85 V AC |
| Disconnect voltage | < 85 V AC |
| Maximum dielectric strength | ≤ 300 V AC 15 sec |
| Typical Country Grid Voltage | 120 V AC |
| 230 V AC | |
| Supply Voltage Voltage Type | AC |
| Extra-current shut-off | ≤ 25 A (typical) |
| Inrush current integral (I2t) | < 0.5 A2s |
| Shut-off current voltage limitation | Typ. 25 A (after 1 ms) |
| AC Frequency Range | 50 Hz ... 60 Hz ±10% |
| Frequency range (fN) | 50 Hz ... 60 Hz ±10% |
| Network Failure Bridging Time | > 17 ms (120 V AC) |
| > 17 ms (230 V AC) | |
| Current absorption | 2.3 A (120 V AC) |
| 1.2 A (240 V AC) | |
| Nominal power input | 285 VA |
| Protection Circuit | Protection against transient overvoltages; Varistor |
| Connection Time | < 1 sec |
| Inlet fuse | 6.3 A (internal (device protection)) |
| Selecting the Right Fuse for Ingress Protection | 6 A ... 16 A (US/CAN: branch circuit protection |
| Ground Shunt Current (PE) | < 3.5 mA |
| Yield | Typ. 90% (120 V AC) |
| Typ. 92% (230 V AC) | |
| Nominal Output Voltage | 24 V DC ±1% |
| Rated Output Current (IN) | 10 A |
| Static Boost (IBoost est.) | 12.5 A (UN 230 V AC) |
| Static boost derating | > 40 °C ... 50 °C 1 %/K> 50 ... 60 °C 0.22 %/K (UN 230 V AC, PStat.Boost= PNx 1:25) |
| Dynamic Boost (IDyn.Boost) | 15 A (5 sec) |
| Derating | > 40 °C ... 50 °C (1%/K) |
| Recirculation Resistance | ≤ 35 V DC |
| Output Surge Protection (OVP) | ≤ 30 V DC |
| Dimming deviation | < 1% (static load change 10% ... 90 %) |
| < 3% (Dynamic Load Change 10 ... 90%, 10 Hz) | |
| < 0.1% (input voltage change ±10%) | |
| Residual ripple | ≤ 10 mVPP |
| Short circuit resistant | Yes |
| Output power | 240 W |
| 300 W | |
| 360 W (5 sec) | |
| Maximum Open Circuit Dissipation | < 2 W (120 V AC) |
| < 2 W (230 V AC) | |
| Maximum Rated Load Dissipation | < 25 W (120 V AC) |
| < 21 W (230 V AC) | |
| Ascent Time | ≤ 12 ms (UOUT(10 % ... 90 %)) |
| Parallel connection possible | Yes, for redundancy and power boost |
| Possibility of series connection | Yes |
| Relay signal 13/14 | |
| Default | closed |
| Digital | 30 V AC 30 V DC 100 mA |
| entrance | |
| Connection type | M12 Cylindrical Connector |
| Codification | s |
| Lock Type | M12 Screw Lock |
| Number of poles | 3 |
| Exit | |
| Connection type | M12 Cylindrical Connector |
| Codification | L |
| Lock Type | M12 Screw Lock |
| Number of poles | 5 |
| Type of signage | LED |
| Potential-free signal contact | |
| Status Indication | 2 x Green LED |
| Signal Output: LED Status Indication | |
| Designation Signage | AC OK |
| Status Indication | LED |
| Colour | green |
| AC OK | AcIn> 0.45 x ACN(ACN= 108 V AC) |
| Signal Output: LED Status Indication | |
| Designation Signage | DC OK |
| DC OK | UOUT> 0.9 x UN(UN= 24 V DC) |
| Number of phases | 1,00 |
| Input/Output Insulation Voltage | 3 kV AC (type test) |
| 1.5 kV AC (Single test) |
| Product Type | Power supply |
| Product Family | TRIO POWER |
| MTBF (IEC 61709, SN 29500) | > 850000 h (25 °C) |
| > 460000 h (40 °C) | |
| > 190000 h (60 °C) | |
| Insulation Properties | |
| Kind of protection | I |
| Degree of pollution | 3 |
| Item Dimensions | |
| Width | 136 mm |
| Height | 240 mm |
| Depth | 53 mm |
| Orifice | |
| Diameter | 5.6 mm |
| Mounting Size | |
| Right/Left Mounting Distance | 20 mm / 20 mm |
| Mounting Distance Up/Down | 50 mm / 100 mm |
| Type of mounting | Wall Mounting |
| Installation instructions | Stackable: horizontal 20 mm, vertical up 50 mm, vertical down 100 mm |
| With protective paint | No |
| Flammability class according to UL 94 (housing/terminals) | V0 |
| Housing Material | Metal |
| Execution of the housings | Aluminum (AlMg3) |
| Environmental conditions | |
| Protection Index | IP67 |
| Ambient Temperature (Service) | -25 °C ... 60 °C |
| Ambient Temperature (Storage/Transport) | -40 °C ... 85 °C |
| Ambient temperature (Start-Up tested model) | -40 °C |
| Fixing height | ≤ 4000 m (> 2000 m, Derating: 10%/1000 m) |
| Weather Class | 4K26 (EN 60721-3-4) |
| Max. permissible air humidity (service) | ≤ 100% (at 25°C, non-condensing) |
| Permissible air humidity (service) | ≤ 100% (at 25°C, non-condensing) |
| Crash | 18 ms, 30g, per direction in space (according to IEC 60068-2-27) |
| Vibration (service) | < 15 Hz, width ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 4g, 90 min. | |
| Surge Category | |
| EN 61010-1 | III (≤ 2000 m) |
| II (≤ 4000 m) | |
| Electrical Safety | |
| Denomination of standard | Electrical Safety |
| Rules/Provisions | IEC 61010-1 |
| Minimum protective voltage with safe insulation | |
| Denomination of standard | Minimum protective voltage with safe insulation |
| Rules/Provisions | IEC 61010-1 (SELV) |
| IEC 61010-2-201 (PELV) | |
| Secure Isolation | |
| Denomination of standard | Safe Separation |
| Low-voltage power supplies with direct current output | |
| Denomination of standard | Low-voltage power supplies with direct current output |
| Rules/Provisions | EN 61204-3 |
| Safety Standards for Electrical Measurement, Control, Regulation, and Laboratory Equipment | |
| Denomination of standard | Safety Standards for Electrical Measurement, Control, Regulation, and Laboratory Devices |
| Rules/Provisions | IEC 61010-1 |
| Limit values for harmonic currents | |
| Denomination of standard | Limit values for harmonic currents |
| Rules/Provisions | EN 61000-3-2 |
| Enclosure protection ratings (IP code) | |
| Denomination of standard | Enclosure protection ratings (IP code) |
| Rules/Provisions | EN/IEC 60529 |
| Ul | |
| Marked | UL/C-UL Listed UL 61010-1 |
| Ul | |
| Marked | UL/C-UL Listed UL 61010-2-201 |
| Low Voltage Directive | Compliance with the Low Voltage Directive 2014/35/EU |
| Interference emission | Interference emission in accordance with EN 61000-6-3 (residential and commercial areas) and EN 61000-6-4 (industrial areas) |
| Interference resistance | Immunity to interference according to EN 61000-6-1 (domestic use), EN 61000-6-2 (industrial use) |
| Electromagnetic compatibility | Compliance with EMC Directive 2014/30/EU |
| Emission of Conducted Interference | EN 55016 |
| EN 61000-6-3 (class B) | |
| Interference emission | EN 55011 (EN 55022) |
| Radiated spurious emissions | EN 55016 |
| EN 61000-6-3 (class B) | |
| Harmonic currents | |
| Standards/Specifications | EN 61000-3-2 |
| EN 61000-3-2 (class A) | |
| Static Electricity Discharge | |
| Standards/Specifications | EN 61000-4-2 |
| Static Electricity Discharge | |
| Download contact us | 6 kV (Test Severity 3) |
| Observation | Criterion A |
| Electromagnetic field AF | |
| Standards/Specifications | EN 61000-4-3 |
| Electromagnetic field AF | |
| Frequency Range | 80 MHz ... 1 GHz |
| Test Field Intensity | 10 V/m (Test Severity 3) |
| Frequency Range | 1 GHz ... 2 GHz |
| Test Field Intensity | 10 V/m (Test Severity 3) |
| Frequency Range | 2 GHz ... 6 GHz |
| Test Field Intensity | 10 V/m (Test Severity 3) |
| Observation | Criterion A |
| Fast Transients (Burst) | |
| Standards/Specifications | EN 61000-4-4 |
| Fast Transients (Burst) | |
| entrance | 4 kV (Test Severity 3, Asymmetric) |
| Exit | 2 kV (Test Severity 3, Asymmetric) |
| Signal | 2 kV (Test Severity 3, Asymmetric) |
| Observation | Criterion A |
| Transient Voltage Load (Surge) | |
| Standards/Specifications | EN 61000-4-5 |
| entrance | 2 kV (Test Severity 4, Symmetrical) |
| 4 kV (Test Severity 4, Asymmetric) | |
| Exit | 1 kV (Test Severity 3, Symmetrical) |
| 2 kV (Test Severity 3, Asymmetric) | |
| Signal | 1 kV (Test Severity 2, Asymmetric) |
| Observation | Criterion A |
| Conducted Disturbances | |
| Standards/Specifications | EN 61000-4-6 |
| Conducted Disturbances | |
| Input/Output | asymmetric |
| Frequency Range | 0.15 MHz ... 80 MHz |
| Observation | Criterion A |
| tension | 10 V (Test Severity 3) |
| Voltage drops | |
| Standards/Specifications | EN 61000-4-11 |
| tension | 230 V AC |
| frequency | 50 Hz |
| Voltage Error | 70 % |
| Number of periods | 25 periods |
| Observation | Criterion A |
| Voltage Error | 40 % |
| Number of periods | 10 periods |
| Observation | Criterion A |
| Voltage Error | 0 % |
| Number of periods | 1 period |
| Observation | Criterion A |
| Interference emission | |
| Standards/Specifications | EN 61000-6-3 |
| Radio interference voltage according to EN 55011 | EN 55011 (EN 55022) Class B Application in industry and residential |
| Radio interference according to EN 55011 | EN 55011 (EN 55022) Class B Application in industry and residential |
| Criteria | |
| Criterion A | Normal service behavior within the specified limits. |
| Criterion B | Transient alteration of service behavior, which is corrected by the device itself. |
| Criterion C | Temporary adverse effects on performance that are automatically corrected by the equipment or that can be reset by operating the control elements. |
| Feature Name | Feature Value |
|---|---|
| Voltage type (supply voltage) (EF002991) | AC |
| 1st secondary output voltage (EF006792) | 24 V |
| Max. output current 1 (EF008284) | 15 A |
| Secondary voltage adjustable (EF007002) | No |
| Nominal value output voltage 1 (EF009393) | 24 V |
| Nominal value output current 1 (EF009396) | 10 A |
| Short-circuit-proof (EF007332) | Yes |
| Rated supply voltage AC 50 Hz (EF007076) | 120 V |
| Rated supply voltage AC 60 Hz (EF007077) | 120 V |
| Output voltage stabilized (EF003092) | No |
| Power consumption (EF000346) | 285 VA |
| Power output (EF003034) | 240 W |
| Stabilized (EF005302) | Yes |
| Type of electric connection (EF003961) | Plug-in connection |
| Suitable for rail mounting (EF003972) | Yes |
| Wall mounting possible (EF003973) | Yes |
| Modular version (EF001126) | No |
| Built-in height (EF000332) | 240 mm |
| Direct mounting possible (EF005689) | No |
| Width (EF000008) | 136 mm |
| Height (EF000040) | 240 mm |
| Depth (EF000049) | 53 mm |
| Suitable for safety functions (EF001597) | Yes |
| SIL according to IEC 61508 (EF009889) | None |
| Performance level according to EN ISO 13849-1 (EF007399) | None |
| Degree of protection (IP) (EF005474) | IP67 |
| Degree of protection (NEMA) (EF011959) | Other |