PHOENIX CONTACT TRIO-PS-2G/1AC/48DC/5 TRIO-PS-2G/1AC/48DC/5 2903159 PHOENIX CONTACT Power supply unit View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TRIO-PS-2G/1AC/48DC/5 2903159 PHOENIX CONTACT Power supply unit

TRIO-PS-2G/1AC/48DC/5

2903159

PHOENIX CONTACT

1 Pcs.

Power supply unit Primary-switched TRIO power supply for rail mounting, input: 1 phase, output: 48 V DC / 5 A, dynamic boost, tool-free quick connect technology for rigid and flexible cables with ferrule

Automation > DC-power supply
Power Supplies (PS)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2903159
Packing unit1 pc
Catalog pagePage 225 (C-4-2017)
GTIN4055626255422
Weight per Piece (excluding packing)1,120.000 g
Custom tariff number85044030
Country of originCN (China)

Dimensions

Width42 mm
Height130 mm
Depth160 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
Ambient temperature (start-up type tested)-40 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Climatic class3K3 (in acc. with EN 60721)
Degree of pollution2
Installation height≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)

Input data

Nominal input voltage range100 V AC ... 240 V AC
110 V DC ... 250 V DC
Input voltage range100 V AC ... 240 V AC -15 % ... +10 %
110 V DC ... 250 V DC ±10 %
Dielectric strength maximum≤ 300 V AC 15 s
AC frequency range50 Hz ... 60 Hz ±10 %
Discharge current to PE< 3.5 mA
Current consumption2.9 A (100 V AC)
2.3 A (120 V AC)
1.2 A (230 V AC)
1.2 A (240 V AC)
Nominal power consumption285.7 VA
Mains bufferingtyp. 15 ms (120 V AC)
typ. 15 ms (230 V AC)
Input fuse6.3 A (internal (device protection))
Choice of suitable circuit breakers6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi)0.91

Output data

Nominal output voltage48 V DC ±1 %
Setting range of the output voltage (USet)36 V DC ... 55 V DC (> 48 V DC, constant capacity restricted)
Nominal output current (IN)5 A
Dynamic Boost (IDyn.Boost)7.5 A (5 s)
Derating> 60 °C ... 70 °C (2.5%/K)
Connection in parallelYes, for redundancy and increased capacity
Connection in seriesyes
Feedback resistance≤ 60 V DC
Output overvoltage protection≤ 60 V DC
Control deviation< 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple< 20 mVPP(with nominal values)
Output power240 W
Peak switching voltages nominal load< 15 mVPP
Maximum power dissipation in no-load conditiontyp. 4 W (120 V AC)
typ. 4.1 W (230 V AC)
Power loss nominal load max.typ. 24.5 W (120 V AC)
typ. 20.1 W (230 V AC)
Short-circuit current< 7 A DC (Permanent)

General

Net weight0.9 kg
Efficiencytyp. 90.5 % (120 V AC)
typ. 91 % (230 V AC)
Insulation voltage input/output3 kV AC (type test)
1.5 kV AC (routine test)
Protection classI (in closed control cabinet)
Degree of protectionIP20
MTBF (IEC 61709, SN 29500)> 2000000 h (25 °C)
> 1200000 h (40 °C)
> 620000 h (60 °C)
Mounting positionhorizontal DIN rail NS 35, EN 60715
Assembly instructionsalignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm

Connection data, input

Connection methodPush-in connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length10 mm

Connection data, output

Connection methodPush-in connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.4 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length8 mm

Connection data for signaling

Connection methodPush-in connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Standards and Regulations

Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Noise emissionEN 55011 (EN 55022)
Noise immunityImmunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
Standards/regulationsEN 61000-4-2
Contact discharge4 kV (Test Level 2)
Standards/regulationsEN 61000-4-3
Frequency range80 MHz ... 1 GHz
Test field strength10 V/m (Test Level 3)
Frequency range1.4 GHz ... 2 GHz
Test field strength3 V/m (Test Level 2)
Standards/regulationsEN 61000-4-4
CommentsCriterion B
Standards/regulationsEN 61000-6-3
EN 61000-4-6
Frequency range0.15 MHz ... 80 MHz
Voltage10 V (Test Level 3)
Conducted noise emissionEN 55016 EN 61000-6-4 (Class A)
Standards/regulationsEN 61000-4-11
Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
Standard - Electrical safetyIEC 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltageIEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolationDIN VDE 0100-410
Standard – Limitation of mains harmonic currentsEN 61000-3-2
UL approvalsUL Listed UL 508
UL/C-UL Recognized UL 60950-1
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)DNV GL CG-0339 / Class B
2 Hz - 100 Hz resonance search, 90 min. in resonance,
2 Hz - 25 Hz, ±1.6 mm amplitude,
25 Hz - 100 Hz, 4g acceleration
Rail applicationsEN 50121-4
Overvoltage category (EN 60950-1)II
Overvoltage category (EN 62477-1)III

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2903159 Low-voltage industrial controls and switchgear (EC002540)
Feature Name Feature Value
Voltage type (supply voltage) (EF002991) AC/DC
1st secondary output voltage (EF006792) 36 V
Max. output current 1 (EF008284) 7.5 A
Secondary voltage adjustable (EF007002) Yes
Nominal value output voltage 1 (EF009393) 48 V
Nominal value output current 1 (EF009396) 5 A
Short-circuit-proof (EF007332) Yes
Rated supply voltage AC 50 Hz (EF007076) 100 V
Rated supply voltage AC 60 Hz (EF007077) 100 V
Rated supply voltage DC (EF007078) 110 V
Output voltage stabilized (EF003092) Yes
Power consumption (EF000346) 285.7 VA
Power output (EF003034) 240 W
Stabilized (EF005302) Yes
Type of electric connection (EF003961) Other
Suitable for rail mounting (EF003972) Yes
Wall mounting possible (EF003973) No
Modular version (EF001126) No
Built-in height (EF000332) 130 mm
Direct mounting possible (EF005689) No
Width (EF000008) 42 mm
Height (EF000040) 130 mm
Depth (EF000049) 160 mm
Suitable for safety functions (EF001597) Yes
SIL according to IEC 61508 (EF009889) None
Performance level according to EN ISO 13849-1 (EF007399) None
Degree of protection (IP) (EF005474) IP20
Degree of protection (NEMA) (EF011959) Other

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.