PHOENIX CONTACT MINI MCR-SL-PT100-LP-NC MINI MCR-SL-PT100-LP-NC 2810308 PHOENIX CONTACT Temperature measuring transducer View larger
Images are for illustrative purposes only. Please refer to data sheet for details

MINI MCR-SL-PT100-LP-NC 2810308 PHOENIX CONTACT Temperature measuring transducer

MINI MCR-SL-PT100-LP-NC

2810308

PHOENIX CONTACT

1 Pcs.

Temperature measuring transducer Configurable Loop-powered temperature converter for Pt 100 temperature sensors, configurable via DIP switch, with screw connection, without presetting Configurable Loop Powered Converter for Pt 100 Temperature Sensors, DIP Switch Configurable, with Screw Connection, Not Preconfigured

Automation > Temperature transformer
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2810308
Packing unit1 pc
Catalog pagePage 106 (C-7-2015)
GTIN4046356134668
Weight per Piece (excluding packing)68.400 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width6.2 mm
Height93.1 mm
Depth102.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m

Input data

Configurable/programmableYes, unconfigured
Sensor types (RTD) that can be usedPt 100 (IEC 60751/EN 60751)
Sensor input current1 mA (constant)
Connection technology2, 3, 4-wire

Output data

Number of outputs1
Configurable/programmableYes, unconfigured
Current output signal4 mA ... 20 mA
20 mA ... 4 mA
Max. output current23 mA (output limit)
Load/output load current output(Usupply- 12 V) / 22 mA
Ripple< 20 mVPP(at 500 Ω)

Power supply

DesignationLoop-powered
Supply voltage range12 V DC ... 30 V DC
Max. current consumption< 4.5 mA (without signal current)
Power consumption< 150 mW (without signal current)

Connection data

Connection methodScrew connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.12
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Stripping length12 mm
Screw threadM3

General

Transmission error in the set measuring range((90 K / set measuring range [K]) + 0.05)%
Transmission error in the full measuring range≤ 0,25 %
Maximum temperature coefficient< 0.02 %/K
Linearity error< 0.05 % (for full measuring range)
Electrical isolationBasic insulation according to EN 61010
Overvoltage categoryII
Degree of pollution2
Rated insulation voltage30 V AC
Test voltage, input/output/supply1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgreen
Housing materialPBT
Mounting positionany
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value5 %
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value5 %
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value5 %

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
Connection in acc. with standardCUL
Standards/regulationsEN 61000-4-2
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
EN 61000-4-4
EN 61000-4-5
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Electrical isolationBasic insulation according to EN 61010
ConformanceCE-compliant
ATEX II 3 G Ex nA IIC T4 Gc X
UL, USA/CanadaUL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 2

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2810308 Sensors (EC002919)
Feature Name Feature Value
Measuring range (EF001836) -150 °C
Analogue output 0 mA ... 20 mA (EF006808) No
Analogue output 4 mA ... 20 mA (EF006810) Yes
Analogue output 0 V ... 2 V (EF009886) No
Analogue output 0 V ... 5 V (EF009887) No
Analogue output 0 V ... 10 V (EF006807) No
Analogue output 2 V ... 10 V (EF009888) No
With switching output (EF005225) No
Modular version (EF001126) Yes
Integrated configuration function (EF003064) Yes
EMC-version (EF001062) Yes
Ambient temperature (EF002386) 65 °C
Weight (EF000167) 0.0684 kg

Product Datasheet