PHOENIX CONTACT CB TM1 5A M1 P CB TM1 5A M1 P 2800851 PHOENIX CONTACT Thermomagnetic device circuit breaker View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CB TM1 5A M1 P 2800851 PHOENIX CONTACT Thermomagnetic device circuit breaker

CB TM1 5A M1 P

2800851

PHOENIX CONTACT

1 Pcs.

Thermomagnetic device circuit breaker Interruption. Protec. thermomagnetic, 1 pole, characteristic curve. activ. M1 (semi-lens), 1 inverted contact, connector for base element.

Automation > Device circuit breaker
Over Current Protection

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2800851
Packing unit1 pc
Catalog pagePage 329 (C-4-2017)
GTIN4046356690027
Weight per Piece (excluding packing)44.800 g
Custom tariff number85362010
Country of originID (Indonesia)

Dimensions

Height45 mm
Width12.3 mm
Depth52 mm
Complete module height90 mm
Complete module width12.3 mm
Complete module depth77.3 mm

Ambient conditions

Ambient temperature (operation)-30 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Humidity test240 h, 95 % RH, 40 °C
Shock (operation)30g (According to IEC 60068-2-27, Test Ea)
Vibration (operation)8g (In accordance with IEC 60068-2-6, Test Fc)
Degree of protectionIP30 (Actuation area)

General

Installation instructionsWhen mounted in rows, the nominal device current can be limited to just 80% or must be overdimensioned accordingly.
Flammability rating according to UL 94V0
Mounting typeon base element
Colorgray
Number of positions1
Insulating material groupII
Degree of pollution2
TypeMale

Electrical data

Fuse typenormal blow
Rated surge voltage2.5 kV (Increased insulation in actuation area)
Rated voltage50 V DC (IEC 60934)
50 V DC (UL 1077)
50 V DC (UL 508 - with plug-in base)
240 V AC (Ue according to IEC 60934)
277 V AC (UL 1077)
277 V AC (UL 508 - with plug-in base)
Rated current IN5 A (IEC 60934)
5 A AC (inductive load according to UL 1077)
5 A DC (low-induction load according to UL 1077)
5 A AC (inductive load according to UL 508 - with plug-in base)
5 A DC (low-induction load according to UL 508 - with plug-in base)
Rated insulation voltage Ui277 V AC (UL 1077)
250 V AC (IEC 60934)
Power dissipation1.5 W (in nominal operation per channel)
Device resistance60 mΩ
Insulation resistance Riso> 100 MΩ (500 V DC)
Type of actuationS type
Tripping methodTM (thermomagnetic)
Tripping levelTrip-free mechanism (positive)
Rated short-circuit switching capacity Icn300 A (240 V AC)
600 A (50 V DC)
Required backup fuse20 A (I > Icn)
Short-circuit switching capacity Ik1000 A AC (277 V AC)
1000 A DC (50 V DC)
Dielectric strength3000 V AC (Actuation area)
1500 V AC (Main to auxiliary circuit)
1500 V AC (Open main circuit)
1000 V AC (Open auxiliary circuit)
Voltage drop0.31 V (at 1 x In)
Switching cycles, max.6000 (at 1 x In)
Auxiliary circuit277 V AC / 0.5 A (Low-induction)
277 V AC / 1 A (Low-induction, maximum of 2000 cycles)
50 V DC / 1 A (Low-induction)
Minimum auxiliary contact operating voltage10 V
Maximum auxiliary contact operating voltage240 V
240 V
Minimum auxiliary contact operating current10 mA
Maximum auxiliary contact operating current1 A

Standards and Regulations

Standards/specificationsEN 60934
UL 1077 UL/C-UL recognized
UL 508 UL/C - UL listed
CSA 22.2 No. 235-04

Classifications


ETIM for 2800851 Circuit breakers and fuses (EC003538)
Feature Name Feature Value
Inflammability class of insulation material according to UL94 (EF002521) Other
Number of poles (EF001391) 1
Construction type (EF000767) Plug
Width (EF000008) 12.3 mm
Height (EF000040) 45 mm
Depth (EF000049) 52 mm
Mounting method (EF000003) Other
Operating voltage (EF000111) 50 V
Nominal current (EF000001) 5 A
Active current limitation x IN (EF011922) 0
Fuse type (EF011923) Other
With remote signalling contact (EF000422) No
Ambient temperature during operating (EF007515) -30 °C

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.