PHOENIX CONTACT TC-2KS50-DO16-ESD-AR-RS TC-2KS50-DO16-ESD-AR-RS 2904113 PHOENIX CONTACT Module carrier View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TC-2KS50-DO16-ESD-AR-RS 2904113 PHOENIX CONTACT Module carrier

TC-2KS50-DO16-ESD-AR-RS

2904113

PHOENIX CONTACT

1 Pcs.

Module carrier Termination Carrier for redundant connection of 16 PSR-FSP modules to digital output cards of the Yokogawa ProSafe-RS control system, via two KS50, 50-pole plug-in connectors. Solution for Emergency Shut Down (ESD) applications. Suitable for Yokogawa SDV 541 card.

Automation > Interface module
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2904113
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 525 (C-5-2017)
GTIN4046356783743
Weight per Piece (excluding packing)1,447.000 g
Custom tariff number85369010
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

General

Nominal voltage UN24 V DC (21.1 V ... 26.4 V)
Max. permissible current1 A (Per signal/channel)
Degree of protectionIP00

Supply

DesignationDevice supply
Input voltage range21.1 V ... 26.4 V
Input current≤ 2 A
Redundant supplyyes, decoupled from diodes
Polarization and surge protectionYes
Output nameSwitching output
Contact type1 N/C contact (alarm = open)
Fuse2.5 A on PCB, slow-blow (replaceable)
Status display2 x red LED (error)
2x green LEDs (PWR1 and PWR2)

Connection 1

Connection namePower supply
Connection methodScrew connection
Stripping length7 mm
Number of connections1
Number of positions6
Conductor cross section solid0.14 mm² ... 2.5 mm²
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 12

Connection 2

Connection nameController level
Connection methodYokogawa KS-compatible
Number of connections2
Number of positions50

Ambient conditions

Ambient temperature (operation)-20 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Shock15g, according to IEC 60068-2-27
Vibration (operation)2g, according to IEC 60068-2-6

Dimensions

Width304 mm
Height170 mm
Depth160 mm

Standards and Regulations

DesignationAir clearances and creepage distances
Standards/regulationsDIN EN 50178
Rated insulation voltage50 V
Rated surge voltage0.5 kV
InsulationBasic insulation
Shock15g, according to IEC 60068-2-27
Vibration (operation)2g, according to IEC 60068-2-6
UL, USA/CanadaUL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2904113 PLC's (EC002780)
Feature Name Feature Value
Number of poles (EF001391) 50
Rated voltage (EF000228) 24 V
Rated current (EF000227) 1 A
Depth (EF000049) 159.5 mm
Width (EF000008) 304 mm
Height (EF000040) 170 mm
Mounting method (EF000003) DIN rail (top hat rail) 35 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.