PHOENIX CONTACT TC-2KS40-AO16-EX-PR-CS TC-2KS40-AO16-EX-PR-CS 2905201 PHOENIX CONTACT Module carrier View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TC-2KS40-AO16-EX-PR-CS 2905201 PHOENIX CONTACT Module carrier

TC-2KS40-AO16-EX-PR-CS

2905201

PHOENIX CONTACT

1 Pcs.

Module carrier Termination Carrier for the redundant connection of 16 MACX Analog Ex-i separation amplifiers to analog input/output cards of the Yokogawa Centum VP control system, via two KS40, 40-pole connectors. Suitable for Yokogawa AAI543 card.

Automation > Interface module
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2905201
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 525 (C-5-2017)
GTIN4046356951395
Weight per Piece (excluding packing)1,696.000 g
Custom tariff number85366990
Country of originDE (Germany)

General

Nominal voltage UN< 30 V DC (Per signal/channel)
Max. permissible current1 A (Signal/channel)
Degree of protectionIP00

Supply

DesignationPower module
NotePower supply via 2904673 TC-MACX-MCR-PTB power supply and error signaling module.
Input voltage24 V DC
Input voltage range19.2 V DC ... 30 V DC
Input current≤ 2 A
Redundant supplyyes, decoupled from diodes
Polarization and surge protectionYes
Output nameSwitching output
Contact type1 N/C contact (alarm = open)
Maximum switching voltage30 V DC (2 A)
Fuse2x 2.5 A on PCB, slow-blow (replaceable)
Status display1 x red LED (error)
2x green LEDs (PWR1 and PWR2)

Connection 1

Connection namePower supply
Connection methodScrew connection
Stripping length7 mm
Number of connections1
Number of positions6
Conductor cross section solid0.14 mm² ... 2.5 mm²
Conductor cross section flexible0.14 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 12

Connection 2

Connection nameController level
Connection methodYokogawa KS-compatible
Number of connections2
Number of positions40

Ambient conditions

Ambient temperature (operation)-20 °C ... 60 °C (Please observe module specifications)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Shock15g, according to IEC 60068-2-27
Vibration (operation)2g, according to IEC 60068-2-6
Maximum altitude≤ 2000 m

Dimensions

Width242 mm
Height170 mm
Depth160 mm

Standards and Regulations

DesignationAir clearances and creepage distances
Standards/regulationsDIN EN 50178
Rated insulation voltage50 V
Rated surge voltage0.5 kV
InsulationBasic insulation
Degree of pollution2
Overvoltage categoryII
Flammability rating according to UL 94V0
Shock15g, according to IEC 60068-2-27
Vibration (operation)2g, according to IEC 60068-2-6
UL, USA/CanadaUL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Articles in set

Classifications


ETIM for 2905201 PLC's (EC002780)
Feature Name Feature Value
Number of poles (EF001391) 40
Rated voltage (EF000228) 30 V
Rated current (EF000227) 1 A
Depth (EF000049) 159.5 mm
Width (EF000008) 242 mm
Height (EF000040) 170 mm
Mounting method (EF000003) DIN rail (top hat rail) 35 mm

Product Datasheet