PHOENIX CONTACT TT-SLKK5/ 24DC TT-SLKK5/ 24DC 2794903 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

TT-SLKK5/ 24DC 2794903 PHOENIX CONTACT Surge protection device

TT-SLKK5/ 24DC

2794903

PHOENIX CONTACT

1 Pcs.

Surge protection device Terminal block with varistor as surge protection between the active part and the rail, separate PE connection, nominal voltage: 24 V DC, installation on NS 35/7.5, terminal width: 6.2 mm, terminal height: 69 mm

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2794903
Packing unit50 pc
Catalog pagePage 99 (C-6-2013)
GTIN4017918072971
Weight per Piece (excluding packing)21.940 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height69.5 mm
Width6.2 mm
Length66.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialPA
Flammability rating according to UL 94V-2
Colorblack
Mounting typeDIN rail: 35 mm
TypeSingle-level terminal block – separate PE connection
Direction of actionLine-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
VDE requirement classC1
C2
C3
Nominal voltage UN24 V DC
Maximum continuous voltage UC31 V DC
25 V AC
Rated current32 A (50 °C)
Operating effective current ICat UC≤ 30 µA
Residual current IPE≤ 30 µA
Nominal discharge current In(8/20) µs (line-earth)700 A
Total discharge current Itotal(8/20) µs2 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)2 kA
Nominal pulse current Ian (10/1000) µs (line-earth)70 A
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 90 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 80 V
Residual voltage at In(line-earth)≤ 125 V
Response time tA(line-earth)≤ 25 ns
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm systemtyp. 300 kHz
Surge protection fault messagenone

Connection data

Connection methodScrew connection
Connection method INScrew terminal blocks
Connection method OUTScrew terminal blocks
Screw threadM3
Tightening torque0.8 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 4 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/regulationsIEC 61643-21

Environmental Product Compliance

REACh SVHC4-Nonylphenol, ethoxylated
Lead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.