PHOENIX CONTACT VAL-MS 230/FM VAL-MS 230/FM 2839130 PHOENIX CONTACT Type 2 surge arrester View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-MS 230/FM 2839130 PHOENIX CONTACT Type 2 surge arrester

VAL-MS 230/FM

2839130

PHOENIX CONTACT

1 Pcs.

Type 2 surge arrester Surge arrester consisting of a base element with FM remote indication contact and plug-in protection with high-power varistor, for mounting on NS 35/7.5, nominal voltage: 230 V AC, 1 channel.

Automation > Surge protection device for power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2839130
Packing unit1 pc
Catalog pagePage 44 (C-6-2015)
GTIN4017918182595
Weight per Piece (excluding packing)135.200 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height96.8 mm
Width17.6 mm
Depth65.7 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
TT
Mode of protectionL-N
L-PEN
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6
PBT
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions1
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN240/415 V AC (TN)
240/415 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC275 V AC
Rated load current IL80 A
Residual current IPE≤ 0.45 mA
Standby power consumption PC≤ 120 mVA
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 1.35 kV
Residual voltage Ures≤ 1.35 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
TOV behavior at UT335 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with V-type through wiring80 A (gG)
Max. backup fuse with branch wiring125 A (gG)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
30 V DC
Operating current5 mA AC ... 1 A AC
1 A DC
Connection methodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm (1,5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 25 mm²
Conductor cross section solid1.5 mm² ... 35 mm²
Conductor cross section AWG15 ... 2
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-N)275 V AC
Nom. voltage230 V AC
Mode of protectionL-N
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)1900 V
Nominal discharge current In(L-N)20 kA

UL indicator/remote signaling

Operating voltage125 V AC
Operating current1 A AC
Tightening torque4 lbf-in.

UL connection data

Conductor cross section AWG10 ... 2
Tightening torque30 lbf-in.

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Product Datasheet