PHOENIX CONTACT S-PT-EX(I)-24DC S-PT-EX(I)-24DC 2880671 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

S-PT-EX(I)-24DC 2880671 PHOENIX CONTACT Surge protection device

S-PT-EX(I)-24DC

2880671

PHOENIX CONTACT

1 Pcs.

Surge protection device Overvoltage protection. in IP67 screw-on module for circ measurement probes. intrinsically safe, direct mounting via ext. thread. M20 x 1.5, cable gland for signal line, circ. of Protec. two-tiered. Suitable for HART.

Automation > Combined arrester for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2880671
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 130 (C-4-2017)
GTIN4046356049016
Weight per Piece (excluding packing)402.000 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height33.5 mm
Width33.5 mm
Depth137 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 50 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Degree of protectionIP67

General

Housing materialZinc die-cast, surface bronzed and nickel-plated
Colorsilver
Standards for cearances and creepage distancesIEC 60664-1
EN 60079-0
EN 60079-11
Mounting typedirect screw connection
TypeScrew-in module
Number of positions3
Direction of actionLine-Line & Line-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous voltage UC30 V DC
21 V AC
Rated current350 mA (50 °C)
Operating effective current ICat UC≤ 10 µA
Residual current IPE≤ 2 µA
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-earth)10 kA (per path)
Nominal discharge current In(8/20) µs (shield-earth)10 kA (optional)
Pulse discharge current Iimp(10/350) µs1 kA
Max. discharge current Imax(8/20) µs maximum (line-line)10 kA
Max. discharge current Imax(8/20) µs maximum (line-earth)10 kA (per path)
Max. discharge current Imax(8/20) µs maximum (shield-earth)10 kA
Nominal pulse current Ian (10/1000) µs (line-line)30 A
Nominal pulse current Ian (10/1000) µs (line-earth)100 A (per path)
Nominal pulse current Ian (10/1000) µs (Shield-Earth)100 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 50 V
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 1.4 kV (Direct grounding)
Output voltage limitation at 1 kV/µs (shield-earth) spike≤ 600 V (optional)
Output voltage limitation at 1 kV/µs (line-line) static≤ 50 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 1.4 kV (Direct grounding)
Residual voltage at In(line-line)≤ 50 V
Residual voltage with Ian (10/1000) µs (line-line)≤ 50 V
Voltage protection level Up(line-line)≤ 50 V (C1 - 0.5 kV / 250 A)
≤ 55 V (C1 - 1 kV/500 A)
≤ 55 V (C2 - 2 kV/1 kA)
≤ 55 V (C2 - 10 kV / 5 kA)
≤ 50 V (C3 - 10 A)
≤ 50 V (C3 - 25 A)
≤ 80 V (D1 - 1 kA)
Voltage protection level Up(line-earth)≤ 1.4 kV (C1 - 1 kV/500 A)
≤ 1.4 kV (C2 - 2 kV/1 kA)
≤ 1.4 kV (C2 - 10 kV / 5 kA)
≤ 1.4 kV (C3 - 25 A)
≤ 1.4 kV (C3 - 100 A)
≤ 1.4 kV (D1 - 1 kA)
Voltage protection level Up(shield-ground)≤ 600 V (C1 - 0.5 kV / 250 A)
≤ 650 V (C1 - 1 kV/500 A)
≤ 650 V (C2 - 2 kV/1 kA)
≤ 650 V (C2 - 10 kV / 5 kA)
≤ 650 V (C3 - 10 A)
≤ 750 V (C3 - 25 A)
≤ 750 V (C3 - 100 A)
≤ 650 V (D1 - 1 kA)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Response time tA (shield-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.5 dB (≤ 1 MHz / 50 Ω)
typ. 0.2 dB (≤ 400 kHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm systemtyp. 6 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 2.5 MHz
Resistance in series2.2 Ω ±10 %
Surge protection fault messagenone
Impulse durability (line-line)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 25 A
D1 - 1 kA
Impulse durability (line-earth)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 100 A
D1 - 1 kA
Impulse durability (shield-earth)C1 - 1 kV/500 A
C2 - 10 kV / 5 kA
C3 - 100 A
D1 - 1 kA
Alternating current carrying capacity (line-earth)10 A - 1 s
Alternating current carrying capacity (shield-earth)10 A - 1 s

Connection data

Connection methodScrew connection
Connection method INScrew terminal blocks
Connection method OUTConnection line
Connection technologyScrew connection
Screw threadM3
Tightening torque0.6 Nm
Stripping length6 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG26 ... 16

Standards and Regulations

Standards/specificationsEN 61643-21 A2:2013
EN 60079-0 2012
EN 60079-11 2012
EN 60079-26 2007
IEC 60079-0 2011
IEC 60079-11 2011
IEC 60079-26 2006

General

Maximum inner capacitance Ci2 nF
Max. internal inductance Li1 µH
Max. input current Ii350 mA (T4 / ≤ 50 °C)
350 mA (T5 / ≤ 50 °C)
350 mA (T6 / ≤ 50 °C)
Max. input voltage Ui30 V
max. input power Pi3 W
Insulation voltage to ground500 V AC
Ambient temperature (operation)-40 °C ... 50 °C

Conformity / approvals

ATEX II 1G Ex ia IIC T4...T6 Ga
IECExEx ia IIC T4...T6 Ga

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.