PHOENIX CONTACT PT-IQ-1X2-TELE-PT PT-IQ-1X2-TELE-PT 2801290 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PT-IQ-1X2-TELE-PT 2801290 PHOENIX CONTACT Surge protection device

PT-IQ-1X2-TELE-PT

2801290

PHOENIX CONTACT

1 Pcs.

Surge protection device Surge protection device, consisting of connector and base element, with multi-level status indication integrated into the module, to protect a two-wire circuit for analogue and digital telecommunication interfaces (VDSL up to 50 MBit/s), in short distances (< 300 m) up to 100 MBit/s).

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2801290
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 163 (C-4-2017)
GTIN4046356766715
Weight per Piece (excluding packing)108.900 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height109.3 mm
Width17.7 mm
Depth77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Mounting typeDIN rail: 35 mm
TypeDIN rail module, two-section, divisible
Direction of actionLine-Line & Line-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
D1
B2
VDE requirement classC1
C2
C3
D1
B2
Nominal voltage UN180 V DC
Maximum continuous voltage UC180 V DC
Rated current150 mA (25 °C)
Operating effective current ICat UC≤ 1 µA
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-earth)10 kA
Pulse discharge current Iimp(10/350) µs (line-earth)2.5 kA
Total discharge current Itotal(8/20) µs20 kA
Voltage protection level Up(line-line)≤ 290 V (B2 - 100 A)
≤ 290 V (C1 - 1 kV)
≤ 290 V (C2 - 10 kV)
≤ 300 V (C2 - 10 kA)
≤ 290 V (C3 - 50 A)
Voltage protection level Up(line-earth)≤ 500 V (B2 - 100 A)
≤ 600 V (C1 - 1 kV)
≤ 600 V (C2 - 10 kV)
≤ 650 V (C2 - 10 kA)
≤ 700 V (C3 - 50 A)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 5 MHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 25 MHz
Capacity (line-line)typ. 60 pF
Resistance in series1.2 Ω ±5 %
Surge protection fault messageOptical, multi-stage
Max. required back-up fuse150 mA (slow-blow)
Impulse durability (line-line)C1 - 500 A
C2 - 10 kA
C3 - 50 A
B2 - 100 A
Impulse durability (line-earth)C1 - 500 A
C2 - 10 kA
C3 - 50 A
B2 - 100 A
D1 - 2.5 kA
Pulse reset time (line-line)≤ 30 ms

Connection data

Connection methodPush-in connection
Stripping length10 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + A1:2008 + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013
EN 61000-6-2 2005
EN 61000-6-3 2007 + A1:2011

Environmental Product Compliance

REACh SVHCLead 7439-92-1

Classifications


ETIM for 2801290 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage AC (EF008798) 180 V

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.