PHOENIX CONTACT VAL-MS 230 IT ST VAL-MS 230 IT ST 2807599 PHOENIX CONTACT Type 2 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-MS 230 IT ST 2807599 PHOENIX CONTACT Type 2 surge protection plug

VAL-MS 230 IT ST

2807599

PHOENIX CONTACT

1 Pcs.

Type 2 surge protection plug Plug-in type 2 surge protection with high-power varistor for VAL-MS base element, with thermal control, optical fault indication. Execution: 230 V AC (IT system)

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2807599
Packing unit10 pc
Catalog pagePage 59 (C-4-2017)
GTIN4017918075286
Weight per Piece (excluding packing)47.550 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN
TT
IT
Mode of protectionL-N
L-PE
L-PEN
Mounting typeon base element
Colorjet black RAL 9005
Housing materialPA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.10
Surge protection fault messageoptical

Additional descriptions

NoteUsable in all low-voltage systems between L-N or L-PEN.
Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE= RAaccordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a)

Protective circuit

Nominal voltage UN240/415 V AC (TN)
240/415 V AC (TT)
230 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC385 V AC
Residual current IPE≤ 0.45 mA
Standby power consumption PC≤ 175 mVA
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 1.8 kV
Residual voltage Ures≤ 1.8 kV (at In)
≤ 1.6 kV (at 10 kA)
≤ 1.4 kV (at 5 kA)
≤ 1.3 kV (at 3 kA)
TOV behavior at UT415 V AC (5 s / withstand mode)
440 V AC (120 min / withstand mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring125 A (gG)

Connection data

Connection methodpluggable

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-N)385 V AC
Nom. voltage230 V AC
Mode of protectionL-N
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)2200 V
Nominal discharge current In(L-N)20 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.