PHOENIX CONTACT VAL-CP-MCB-1S-350/40/FM VAL-CP-MCB-1S-350/40/FM 2882763 PHOENIX CONTACT Type 2 surge arrester View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-CP-MCB-1S-350/40/FM 2882763 PHOENIX CONTACT Type 2 surge arrester

VAL-CP-MCB-1S-350/40/FM

2882763

PHOENIX CONTACT

1 Pcs.

Type 2 surge arrester Combination of type 2 surge protection and arrester pre-fuse, with unloader and pre-fuse monitoring, in combination with remote indication contact. Execution: 3-conductor system (L1, N, PE), NS 35 load-bearing rail mounting

Automation > Surge protection device for power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2882763
Packing unit1 pc
Catalog pagePage 66 (C-4-2017)
GTIN4046356175821
Weight per Piece (excluding packing)501.500 g
Custom tariff number85363010
Country of originHU (Hungary)

Dimensions

Height101 mm
Width72 mm
Depth76 mm
Horizontal pitch4 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-S
TT
Mode of protectionL-N
L-PE
N-PE
Mounting typeDIN rail: 35 mm
Colorlight grey RAL 7035
Housing materialPBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions2
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN240 V AC (TN-S)
240 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC(L-N)350 V AC
Maximum continuous operating voltage UC(L-PE)350 V AC
Maximum continuous voltage UC(N-PE)264 V AC
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs30 kA
Follow current interrupt rating Ifi(N-PE)100 A
Short-circuit current rating ISCCR25 kA
Voltage protection level Up(L-N)≤ 2.5 kV
Voltage protection level Up(N-PE)≤ 1.7 kV
Residual voltage Ures(L-N)≤ 2.3 kV (at In)
≤ 1.6 kV (at 10 kA)
≤ 1.3 kV (at 5 kA)
≤ 1 kV (at 3 kA)
Residual voltage Ures(L-PE)≤ 2.5 kV (at In)
≤ 2 kV (at 10 kA)
≤ 1.5 kV (at 5 kA)
≤ 1.1 kV (at 3 kA)
Residual voltage Ures(N-PE)≤ 1.2 kV (at 10 kA)
≤ 0.8 kV (at 5 kA)
≤ 0.5 kV (at 4 kA)
≤ 0.3 kV (at 3 kA)
TOV behavior at UT(L-N)415 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / withstand mode)
Response time tA(L-N)≤ 25 ns
Response time tA(L-PE)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
Max. backup fuse with V-type through wiring40 A (gG)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage250 V AC
250 V DC
Operating current1 mA AC ... 2 A AC
1 mA DC ... 50 mA DC
Connection methodPluggable screw connection
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection nameConnection protective circuit
Connection methodScrew connection
Tightening torque3.5 Nm
Stripping length14 mm
Conductor cross section flexible4 mm² ... 25 mm²
Conductor cross section solid4 mm² ... 35 mm²
Conductor cross section AWG18 ... 2
Connection nameProtective ground connection
Connection methodScrew connection
Screw threadM5
Tightening torque4.5 Nm
Stripping length16 mm
Conductor cross section flexible2.5 mm² ... 16 mm²
Conductor cross section solid2.5 mm² ... 25 mm²
Conductor cross section AWG12 ... 4

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012
IEC 60364-4-443
IEC 60364-5-534

Classifications


ETIM for 2882763 Earthing, lightning and surge protection (EC000941)
Feature Name Feature Value
System configuration DC (EF009926) No
System configuration IT (EF009927) No
System configuration TN (EF009928) No
System configuration TN-C (EF009929) No
System configuration TN-C-S (EF009933) No
System configuration TN-S (EF009930) Yes
System configuration TT (EF009931) No
System configuration other (EF009932) No
Nominal discharge surge current (8/20) (EF004214) 15 kA
Max. discharge surge current (8/20) (EF012274) 30 kA
Max. continuous voltage AC (EF004198) 350 V
Voltage protection level L-N (EF004236) 2.5 kV
Voltage protection level N-PE (EF008796) 1.7 kV
Max. overcurrent protection device, series connection (fuse) (EF015963) 40 A
Short-circuit breaking capacity (Isccr) (EF012627) 25 kA
Integrated backup fuse (EF008797) Yes
Leakage-current free (EF016002) No
Mounting method (EF000003) DIN rail (top hat rail) 35 mm
Construction size (EF002566) Other
Max. conductor cross section solid (solid, stranded) (EF008827) 4 mm²
Max. conductor cross section flexible (fine-strand) (EF008828) 25 mm²
With remote signalling contact (EF000422) Yes
Signalling at the device (EF004241) Optic
Category type 2 (EF004230) Yes
Degree of protection (IP) (EF005474) IP20

Product Datasheet