PHOENIX CONTACT PT-IQ-4X1-48DC-UT PT-IQ-4X1-48DC-UT 2801219 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PT-IQ-4X1-48DC-UT 2801219 PHOENIX CONTACT Surge protection device

PT-IQ-4X1-48DC-UT

2801219

PHOENIX CONTACT

1 Pcs.

Surge protection device Surge protection, consisting of plug-in protection and base element, with indica. Multi-level diagnostics and status integrated in module for four signal conductors with joint reference potential.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Key Commercial Data

Orderkey2801219
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 111 (C-4-2017)
GTIN4046356745093
Weight per Piece (excluding packing)125.900 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height91 mm
Width17.7 mm
Depth77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Mounting typeDIN rail: 35 mm
TypeDIN rail module, two-section, divisible
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground

Additional descriptions

NoteRemote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN48 V DC
Maximum continuous voltage UC53 V DC
37 V AC
Rated current300 mA
Operating effective current ICat UC≤ 6 µA (per path)
Residual current IPE≤ 6 µA (per path)
Nominal discharge current In(8/20) µs (line-earth)10 kA
Pulse discharge current Iimp(10/350) µs (line-earth)2.5 kA
Total discharge current Itotal(8/20) µs20 kA
Voltage protection level Up(line-earth)≤ 105 V (C1 - 1 kV/500 A)
≤ 160 V (C2 - 10 kV / 5 kA)
≤ 90 V (C3 - 25 A)
Response time tA(line-earth)≤ 1 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 530 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm systemtyp. 1.9 MHz
Capacity (line-signalground)typ. 1.5 nF
Resistance in series1.2 Ω ±5 %
Surge protection fault messageOptical, multi-stage
Max. required back-up fuse315 mA (FF)
Impulse durability (line-earth)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C2 - 10 kA
C3 - 25 A
D1 - 2.5 kA
Pulse reset time (line-earth)≤ 1500 ms

Connection data

Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Remote indication contact

Switching functionvia DIN rail connector

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + A1:2008, modified
EN 61643-21 2001 + A1:2009
EN 61000-6-3 2007 + A1:2011
EN 61000-6-2 2005

Environmental Product Compliance

REACh SVHCLead 7439-92-1

Classifications


ETIM for 2801219 Earthing, lightning and surge protection (EC000943)
Feature Name Feature Value
Nominal voltage DC (EF008799) 48 V

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.